CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning
of this appliance care should be taken when handling edges of sheet steel components.
All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be
recorded in your Log Book. You can check your installer by calling CORGI direct on 01256 372 300.
Introduction
The
xtra
boilers are fully automatically controlled, floor
standing, fanned, super efficient condensing appliances.
Due to the very high efficiency, condensate is produced from the
flue gases and this is drained to a suitable disposal point
through the plastic waste pipe at the bottom of the boiler. A
condensate 'plume' will also often be visible at the flue terminal.
S a f e t y
Current Gas Safety (Installation & Use)
Regulations or rules in force.
In your own interest, and that of safety, it is the law that this boiler
must be installed and maintained by a CORGI registered
installer or in IE a competent person, in accordance with the
above regulations.
The appliance should be serviced at least once a year by a
CORGI registered installer or in IE a competent person.
It is essential that the instructions in this booklet are strictly
followed, for safe and economical operation of the boiler.
Electricity Supply
The appliance must be earthed.
Supply 230 V - 50 Hz. The fusing should be 7A for F320-F560.
This appliance is intended to be connected to the supply via two
double-pole switches, having a 3mm contact separation in both
poles, serving only the boiler and system controls. Alternatively,
two 3-pin UNSWITCHED sockets may be used.
Important Notes
·
This appliance must not be operated without
the casing correctly fitted.
·
Do not store objects around or on the boiler, and keep
access clear at all times.
·
Do not obstruct ventilation ducts, grilles or openings in the
boiler room, room space or compartment that the appliance
is installed in, or the passage of combustion and ventilation
to the boiler.
·
Do not turn off the boiler if it is to be left unattended in frosty
weather.
·
If it is known or suspected that a fault exists on the boiler
then it MUST NOT BE USED until the fault has been
corrected by a CORGI registered installer or in IE a
competent person.
·
Flammable materials must not be placed in close proximity
to the appliance. Materials giving off flammable vapours
must not be stored in the same room as the appliance.
In cases of repeated or continuous shutdown a CORGI
registered installer or in IE a competent person should be called
to investigate and rectify the condition causing this and carry out
an operational test after each intervention on the device. Only the
manufacturers original parts should be used for replacement.
Minimum Clearances
Rear:
1000mm or adequate space from the rear of the jacket to make
the flue connections and access to the flue sample point, drain
connection, flue and any safety or control devices.
Left Side:
450mm.
Right Side:
450mm.
Front:
600mm; except, access doors may be closer, but not less than
200mm and 600mm must still be available for service across
the width of the boiler.
Top:
500mm.
To light the boiler
(Refer to Frame 1)
1. CHECK THAT THE ELECTRICITY SUPPLY TO THE BOILER
IS OFF.
2. Set the burner on/off switch (A) to off.
3. Switch on the electricity supply to the boiler and check that all
external controls, e.g. programmer, room thermostat etc. are
on. Allow the boiler to carry out a self check.
4. Set the burner on/off switch (A) to ON.
The boiler will commence the ignition sequence, supplying heat
to the system when required.
xtra
Natural Gas only
PI No. 0063 BR 3123
Destination Countries: GB,IE
2
0
I
xtra
MODE
STEP
STORE
RESET
+
A
B
C
D
E
F
G
H
I
im8219
MASTER MODULE
CONTROL PANEL
1
BOILER CONTROLS / DISPLAY (MASTER PANEL SHOWN)
In normal operation the display (C) shows the boiler status
(see table above) and the water system flow temperature.
Blocking Mode
The boiler will enter blocking mode under certain fault
conditions. Whilst in blocking mode the burner is switched off.
Once the fault conditions are clear the boiler will automatically
reset itself. In blocking mode the display will alternate
between showing a '9' in digit one, along with the flow
temperature in digits 2, 3 and 4, e.g.
Followed by the blocking code 'bxx', e.g.
Error Mode
In error mode the display will flash on and off with the error
code shown, e.g.
9 9 6
b 1 8
The boiler will enter error mode under certain fault conditions.
The unit will be inoperative until the fault is rectified. The reset
button is used to reset the boiler control module after an error
has occurred.
Self Check and Anti-Seize Modes
After switching on the mains power or after a reset, the boiler
performs a selfcheck, i.e. the DHW valve (if connected) is
energised first for 15 seconds then the CH pump is switched
on for a further 10 seconds. This cycle repeats itself every
24hrs, as long as no heat request is given in 24hrs.
Burner on/off Switch
With the burner switch set to 'off' the boiler will not respond to a
CH demand. However, it will respond to a DHW demand and
the pump anti-seize and frost protection modes are still
operational any one of which could cause the boiler to fire.
Note. The burner switch is NOT a mains isolation switch.
CH/DHW Systems
In standby mode pressing and holding the '+' button for 3
seconds turns the CH system on/off.
In standby mode pressing and holding the '-' button for 3
seconds turns the DHW system on/off.
E 3 6
3
RESET
C
D
SLAVE MODULE
CONTROL PANEL
Sequence
Boiler Status
A
DHW valve energised
0
Standby, no heat request
1
Pre-purge, post purge
2
Ignition
3
Burner on in CH mode
4
Burner on in DHW mode
5
Waiting for air pressure switch to open or close
6
Burner off because a set value has been reached
7
Pump overrun in CH mode
8
Pump overrun in DHW mode
Operation
LEGEND
A. Burner switch
B. Pressure gauge
C. Display
D. Reset button
E. Mode button
F. Step button
G. Store button
H. + button (to increase values)
I. - button (to decrease values)
Ideal Boilers, P.O. Box 103, National Ave, Kingston Upon Hull, HU5 4JN. Tel.
01482 492251 Fax. 01482 448858. Registration No. London 322 137.
Ideal Stelrad Group pursues a policy of continuing improvement in the design and performance
of its products. The right is therefore reserved to vary specification without notice.
Ideal Consumer Helpline
Tel: 01482 498376
www.idealboilers.com
To shut Down the Boiler
1. For short periods
Set the external controls to OFF. Wait 10 minutes and then
isolate the mains supply to the boiler.
2. For longer periods
Set the external controls to OFF. Wait 10 minutes and then
isolate the mains supply to the boiler. For longer periods
the entire system should be drained, including the
domestic hot water supply.
To Relight the Boiler
Refill the system if it has been drained, taking care to ensure
no air is in the boiler or system.
Repeat the procedure detailed in 'To light the boiler'.
Frost Protection
The
xtra
boiler has built into its control system the facility
to protect the boiler only against freezing.
Note.
This may not protect remote parts of the system, in which case
a separate frost protection should be fitted.
Boiler Overheat
Boiler overheating is detected by electrical sensors connected
to the boiler control module. If the boiler overheats it will shut
down and the display will show E18. Press the 'reset' button
(D) and the boiler will relight. If the fault recurs turn off the
boiler and consult a CORGI registered installer or in IE a
competent person.
Condensate Drain
The condensate drain must not be modified or blocked.
Blockage of the condensate drain, caused by debris or freezing,
can cause automatic shutdown of the boiler or leakage from the
condensate trap mounted on the bottom of the boiler.
If freezing is suspected and the pipe run is accessible an
attempt may be made to free the obstruction by pouring hot
water over the exposed pipe and clearing any blockage from the
end of the pipe. If this fails to remedy the problem the
assistance of a CORGI registered installer or in IE a competent
person should be sought.
Escape of Gas
Should a gas leak or fault be suspected contact your local gas
supplier without delay.
Do NOT search for gas leaks with a naked flame.
C l e a n i n g
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains use a damp cloth and
mild detergent.
DO NOT use abrasive cleaning materials.