installation and
servicing
Your Ideal installation and servicing guide
See reverse for users guide
When replacing any part on this appliance, use only spare parts that you can be
assured conform to the safety and performance specification that we require. Do not
use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
xtra
Models F320, F400, F480, F560
xtra
February 2010 UIN 202863 A06
2
xtra
-
Installation & Servicing
GENERAL
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning
of this appliance, care should be taken when handling edges of sheet steel components.
Table 1 Performance Data
Boiler
F320
F400
F480
F560
Boiler output
Max
kW
311.6
390.8
469.0
547.2
(non-condensing)
Btu/h
1,063,200
1,333,400
1,600,200
1,867,000
Mean 70
o
C
Min
kW
67.8
97.7
105.5
107.7
Btu/h
231,300
333,400
360,000
367,500
Boiler output
Max
kW
329.0
415.6
498.8
581.8
(condensing)
Btu/h
1,122,500
1,418,000
1,701,900
1,985,100
Mean 40
o
C
Min
kW
75.3
107.5
116.1
118.3
Btu/h
256,900
366,800
396,100
403,600
Boiler Input
Net
kW
320
400
480
560
Max Rate
Btu/h
1,091,800
1,364,800
1,637,800
1,910,700
Gross
kW
355.4
444.2
533.0
621.8
Btu/h
1,212,600
1,515,600
1,818,600
2,121,600
Boiler Input
Net
kW
70
100
108
110
Min Rate
Btu/h
238,800
341,200
368,500
375,300
Gross
kW
77.6
110.9
119.8
122.0
Btu/h
264,800
378,400
408,800
416,300
Maximum Gas Rate
m
3
/h
32.2
40.2
48.4
56.4
ft
3
/h
1138
1420
1710
1992
Approx. flue gas
@ max. rate
m
3
/h
484
604
726
846
volume (@80
o
C) i.e. non-condensing ft
3
/h
17,100
21,380
25,640
29,920
Max. Flue Resistance
Pa
145
145
145
145
Flue Gas CO
2
@ Max Rate
%
9.3/9.8
9.3/9.8
9.3/9.8
9.3/9.8
G20/LNG @ Min. Rate
%
9.1/9.6
9.1/9.6
9.1/9.6
9.1/9.6
NOx with O
2
= 0% mg/kWh
35
26
26
26
ppm
20
15
15
15
Seasonal Boiler Efficiency (Building Regs L2)
95.1
95.2
95.2
95.2
Note.
Natural gas consumption is calculated using a calorific value of
37.8MJ/m
3
(1038Btu/ft
3
) gross or 34 MJ/m
3
(910 Btu/ft
3
) nett at
15
o
C and 1013.25 mbar.
a. For l/s divide the gross heat input (kW) by the gross C.V. of
the gas (MJ/m
3
)
b. For ft/h
3
divide the gross heat input (Btu/h) by the gross C.V.
of the gas (Btu/ft
3
).
HEALTH & SAFETY DOCUMENT NO. 635
The electricity at work regulations, 1989. The manufacturer's
notes must NOT be taken, in any way, as overriding statutory
obligations.
IMPORTANT. These appliances are CE certified for safety and
performance. It is, therefore, important that no external control
devices, e.g. flue dampers, economisers etc., are directly
connected to these appliances unless covered by these
Installation and Servicing Instructions or as otherwise
recommended by Ideal Stelrad Group in writing. If in doubt
please enquire.
Any direct connection of a control device not approved by Ideal
Stelrad Group could invalidate the certification and the normal
appliance warranty. It could also infringe the Gas Safety
Regulations and the above regulations.
Electricity supply and Fuse rating for pumps etc. refer to manufacturer's instructions.
* OPTIONAL HEADER PACK HAS DN80 CONNECTIONS FOR FLOW AND RETURN AND 2" BSP GAS CONNECTION
Table 2 General Data
Boiler
F320
F400
F480
F560
Gas supply
2H - G20 - 20mbar
Gas supply connection
(in. BSP)
2 x R1
2 x R1
2 x R1
2 x R1
Flow connection
(in. BSP)
2 x R2
2 x R2
2 x R2
2 x R2
Return connection
(in. BSP)
2 x R2
2 x R2
2 x R2
2 x R2
Hydraulic Resistance @ 20
o
C
mbar
100
105
110
120
Max Press (sealed system)
bar (psi)
6 (87)
6 (87)
6 (87)
6 (87)
Maximum Static Head
m (ft)
61 (200)
61 (200)
61 (200)
61 (200)
Boiler Electricity Supply
230V - 50Hz
Boiler Fuse Rating
2 x External 5A supplies Internal 2AT.4AT (x2)
Power Consumption (boiler only)
W
800
800
800
800
Air Inlet
O/D
m m
110x2
110x2
110x2
110x2
Flue Size dia
m m
200
250
250
250
Condensate drain
m m
2x21.5
2x21.5
2x21.5
2x21.5
Boiler dry weight
(unpacked exc. headers)
kg (lb)
336 (740)
396 (874)
430 (948)
466 (1028)
Water Content
l (gal)
35 (7.8)
36.8 (8.2)
48.0 (10.6)
54.4 (12.0)
*
*
3
xtra
-
Installation & Servicing
GENERAL
xtra
CONTENTS
Boiler Assembly - exploded view. .................................. 11
Boiler Clearances. ............................................................ 9
Boiler Dimensions. ..................................................... 7,8,9
Commissioning and Testing. ......................................... 37
Electrical Connections. .................................................. 18
Electrical Supply. .............................................................. 6
Fault Finding. ................................................................... 50
Flue Installation. ................................................................ 5
Gas Safety Regulations .................................................... 4
Gas Supply. ........................................................................ 4
Hydraulic Resistance. ...................................................... 5
Initial Lighting. ................................................................. 37
Installation. ...................................................................... 11
Option Kits. ........................................................................ 4
Performance Data. ........................................................... 2
Servicing. ........................................................................ 38
Short List of Parts. ......................................................... 54
Ventilation. ........................................................................ 9
Water Circulation. ............................................................ 6
Water Connections. ....................................................... 17
Water System Requirements. ....................................... 10
Water Treatment. ............................................................. 6
Wiring Diagrams. ....................................................... 21,22
Natural Gas only
PI No. 0063 BR 3123
Destination Countries: GB, IE
Key to symbols
IE = Ireland, GB = United Kingdom (Countries of destination)
PMS =
Maximum operating pressure of water
C53 =
A room sealed appliance which is connected
via its separate ducts to two terminals that
may terminate in zones of different pressure.
C63 =
A room sealed appliance intended to be
connected to a separately approved and
marketed system for the supply of
combustion air and discharge of combustion
products. The fan is up stream of the
combustion chamber.
B23 =
An appliance intended to be connected to a
flue which evacuates the products of
combustion to the outside of the room
containing the boiler. The combustion air is
drawn directly from the room. The fan is up
stream of the combustion chamber.
NOTE TO THE INSTALLER: LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER.
4
xtra
-
Installation & Servicing
GENERAL
INTRODUCTION
The
xtra
boilers are fully automatically controlled, floor
standing, fanned, super efficient condensing appliances.
The imax xtra comprises of 2 modules, Master and Slave.
The comprehensive boiler controls built into the appliance
include:
-
0-10V Boiler control input
-
Volt free 'alarm' contacts (lockout)
-
Volt free 'boiler run' contacts
-
Burner hours run meters
-
System temperature indication
The boilers can draw their combustion air from the room or via
ducting from outside.
Through a sophisticated control system combined with premix
burner technology and an aluminium heat exchanger, the boilers
are capable of high operating efficiencies of 93% (gross) and low
emissions.
These boilers are certified to meet the requirements of the EC
Gas Appliance Directive, Boiler Efficiency Directive, EMC and Low
Voltage Directive.
OPTIONAL EXTRA KITS
·
Modulating Sequencer
- DHW Sensor
- Room Sensor
·
Programmable Room Stat
·
Outside Sensor
(only suitable for use in conjunction with Prog. Room Stat)
·
Water and Gas Header Pack
·
RS Air Duct Connector (F320 and F400 only)
·
Horizontal Flue Header *
·
Vertical Flue Header *
* A flue header kit (horizontal or vertical) must be fitted to boiler.
SAFETY
Current Gas Safety (Installation and Use) Regulations or rules in
force
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a CORGI Registered
Installer or in IE by a competent person. It must be carried out in
accordance with the relevant requirements of the:
·
Gas Safety (Installation and Use) Regulations
·
The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).
·
The Water Fittings Regulations or Water byelaws in Scotland.
·
The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Competent Person
and installed in accordance with the current Building Regulations
and reference should be made to the current ETCI rules for
electrical installation.
The boilers have been tested by Gastec and conform to EN483
and EN677 for use with Natural Gas.
Detailed recommendations are contained in the following
Standards and Codes of Practice:
BS. 5854
Flue and flue Structures in Buildings.
BS. 6644
Installation of gas fired hot water boilers of rated
inputs between 70kW and 1.8MW (net) (2nd and
3rd family gases).
BS. 6880
Low temperature hot water heating systems of
output greater than 45kW.
Part 1
Fundamental and design considerations.
Part 2
Selection of equipment.
Part 3
Installation, commissioning and maintenance.
IGE/UP/1
Soundness testing and purging of industrial and
commercial gas installations.
IGE/UP/2
Gas installation pipework, boosters and
compressors on industrial and commercial
premises.
IGE/UP/10
Installation of gas appliances in industrial and
commercial premises.
SAFE HANDLING OF SUBSTANCES
No asbestos, mercury or CFCs are included in any part of the
boiler or its manufacture.
FOUNDATION / LOCATION OF BOILER
The boiler must stand on a floor which must be flat, level and of a
suitable load bearing capacity to support the weight of the boiler
(when filled with water) and any ancillary equipment.
Ideally the boiler should be placed on a plinth exceeding the plan
area of the boiler by 75mm on each side and at least 100mm high.
The boiler must not be fitted outside.
GAS SUPPLY
The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an adequate
supply of gas. An existing service pipe must NOT be used without
prior consultation with the local gas supplier.
A gas meter can only be connected by the local gas supplier or by a
registered CORGI engineer or in IE by a competent person.
An existing meter should be checked, preferably by the gas
supplier, to ensure that the meter is adequate to deal with the rate
of gas supply required. A minimum working gas pressure of
15mbar MUST be available at the boiler inlet for Natural gas.
Do not use pipes of smaller size than the boiler inlet gas
connection.
The complete installation MUST be tested for gas soundness and
purged in accordance with the appropriate standards.
Gas Boosters
A gas booster is required if the gas pressure available at the boiler
is lower than that required by the boiler manufacturer to attain the
flow rate for maximum burner input rating.
Location of the booster requires careful consideration but should
preferably be closer to the burner rather than the gas meter.
Ventilation should also be considered to ensure ambient
temperature do not exceed designed recommendations. Further
guidance is provided in IGE/UP/2.
5
xtra
-
Installation & Servicing
GENERAL
FLUE INSTALLATION
The appropriate Ideal Flue Header Kit (veritcal or horizontal)
must be fitted to these boilers.
IMPORTANT. It is the responsibility of the installer to ensure, in
practice, that products of combustion discharging from the
terminal cannot re-enter the building or any other adjacent
building through ventilators, windows, doors, other sources of
natural air infiltration, or forced ventilation / air conditioning.
If this should occur the appliance MUST be isolated from the
gas supply and labelled as 'unsafe' until corrective action can be
taken.
Terminal Position
Due to the high efficiency of the boilers pluming will occur.
Particular care should be taken in the case of large output boiler
installations, and complying with the requirements of the Clean
Air Act.
The flue must be installed in accordance with the appropriate
Building Regulations and standards listed on page 4 and in
compliance with BS6644. In IE refer to I.S.820:2000.
FLUE SYSTEM DESIGN
Due to the high efficiency of these boilers, the flue gas
temperatures are low and the buoyancy in the stack will be
relatively small. The boiler is supplied with an integral fan which
is fully matched to the boiler in each case to provide correct
combustion air flow and overcome the flue resistance.
The power of this fan is such that there is a large reserve of
pressure available to overcome a significant length of flue
without affecting the combustion performance of the boiler. The
maximum pressure available at the base of the flue to overcome
flue resistance is 145Pa (0.58" w.g.) for F320, F400, F480 and
F560. This includes the resistance of any air ducts used to
connect the air inlet direct to outside air. Care should be taken
with tall flue systems to ensure excess buoyancy is not created.
A negative pressure must not be created at the boiler flue outlet.
See table below for approximate maximum straight flue length.
Boiler
F320
F400
F480
F560
Flue Size (mm)
Ø200
Ø250
Ø250
Ø250
Approx. max.
Straight Flue
109
235
162
116
Length (m)
If the high level air inlet kit, supplied with this appliance, is to be
utilised, the following table shows the approximate maximum
straight flue lengths and pressures available.
Boiler
F320
F400
F480
F560
Flue Size (mm)
Ø200
Ø250
Ø250
Ø250
Approx. max.
Straight Flue
57
129
67
40
Length (m)
Flue Pressure (Pa)
76
80
60
50
The addition of elbows and their positions in the flue will have a
significant effect on the maximum allowable flue and air duct
lengths. Consult with your flue supplier for detailed design
work.
IMPORTANT NOTE.
If combustion air is drawn from within the boiler room, ensure
no dust or airborne debris can be ingested into the appliance.
Dusty concrete flooring should be sealed to reduce the
presence of dust. Ideally where possible duct the air supply
into the boiler room from a clean source outside the boiler
room / building.
Material
With no requirement for buoyancy to discharge flue products and
with low flue gas temperatures, single wall flues are suitable for
most installations. Care should still be taken to maintain
compliance with building regulations and relevant standards.
The flue used should be a suitably approved flue for use on a
pressurised condensing flue system. Materials choice includes
plastic, aluminium and 316 grade stainless steel. Unless the
flue is manufactured from aluminium, the condensate from
the flue must be collected and drained before entering the
sump of the boiler (when employing the vertical combined flue
outlet header, a flue condensate drain is provided for this
purpose). Advice regarding the availability of proprietary types of
flue system can be obtained by contacting Ideal Stelrad Group.
All joints or connections in the flue system must be impervious
to condensate leakage. Low points in the flue system should be
drained using pipe of material resistant to condensate
corrosion. All drains in the flue should incorporate a water trap.
Care should also be taken in the selection of flue terminals as
these tend to accentuate the formation of a plume and could
freeze in cold weather conditions.
Care should be taken to ensure the specification of the chimney
is suitable for the application by reference to the manufacturers
literature.
6
xtra
-
Installation & Servicing
GENERAL
WATER CIRCULATION SYSTEM
A circulation pump MUST be connected to the boiler, see below.
The boiler must NOT be used for direct hot water supply. The
hot water storage cylinder MUST be of the indirect type.
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating nor
are they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of
the useful heating surface, should be lagged to prevent heat
loss and any possible freezing - particularly where pipes run
through roof spaces and ventilated underfloor spaces.
The boiler must be vented. There must be no low points
between the boiler flow connection and a system vent point,
which should be positioned as close as practically possible to
the boiler flow connection.
Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler
and hot water storage vessel. They should be at least 1/2" BSP
nominal size and be in accordance with BS. 2879. Do not use
the boiler drain tap to drain the system as this can induce
sludge into the heat exchanger.
The central heating system should be in accordance with the
relevant standards listed on page 4.
Due to the compact nature of the boiler the heat stored within
the castings at the point of shutdown of the burner must be
dissipated into the water circuit in order to avoid overheating. In
order to allow pump operation after burner shutdown the boiler
control box incorporates a 5 minute pump overrun facility. In
order to make use of this, a pump must be supplied from the
terminals inside the boiler. Note: for pumps requiring greater
than 1.0 amp current, they must be connected via a relay.
When sizing pumps, reference should be made to the Hydraulic
Resistance Table on page 6 which show the boiler resistance
against flow rates, to achieve the required temperature
differential.
Flow rates for common systems using either 11
o
C or 20
o
C
temperature differentials are given in the table below.
Water flow rate temp.
Water flow rate temp.
difference 11
o
C (20
o
F)
difference 20
o
C (36
o
F)
l/s
m
3
/h
l/s
m
3
/h
F320
7.14
25.70
3.93
14.15
F400
9.02
32.47
4.96
17.86
F480
10.83
38.99
5.96
21.46
F560
12.63
45.47
6.95
25.02
Note.
·
With the boiler firing at maximum rate, the temperature
differential should not be less than 10
o
C. Higher flow rates
required for lower temperature differentials could lead to
erosion of the heat exchanger water ways.
·
With the boiler firing at minimum rate, the temperature
differential should not be greater than 35
o
C. Lower flow rates
generating higher temperature differentials will lead to lock
out of the boiler.
·
The lower the return temperature to the boiler, the higher the
efficiency. At return temperatures of 55
o
C and below, the
difference becomes marked because the water in the flue
gases starts to condense, releasing its latent heat.
In installations where all radiators have been provided with
thermostatic radiator valves, it is essential that water circulation
through the boiler is guaranteed. A mixing header will perform
this task. Alternatively this can be best achieved by means of a
differential pressure valve, which is installed in a bypass
between the flow and return pipes. The bypass should be fitted
at least 6m from the boiler, and should be capable of allowing a
minimum flow rate to achieve a temperature differential of no
greater than 35
o
C at minimum rate.
WATER TREATMENT
These boilers incorporate an ALUMINIUM heat exchanger.
IMPORTANT. The application of any other treatment to this
product may render the guarantee of Ideal Stelrad Group
INVALID.
Ideal Stelrad Group recommend Water Treatment in
accordance with Guidance Notes on Water Treatment in Central
Heating Systems.
Ideal Stelrad Group recommend the use of Fernox Copal or
MB1 or GE Betz Sentinel X100 inhibitors and associated water
treatment products, which must be used in accordance with the
manufacturers' instructions.
For further information contact:
Fernox Manufacturing Co. Ltd., Cookson Electronics,
Forsyth Road, Sheerwater, Woking, Surrey, GU21 5RZ
Tel: +44 (0) 1799 521133 or
Sentinel Performance Solutions.,
The Heath Business & Technical Park, Runcorn, Cheshire, WA7 4QX
Tel: 0800 389 4670. www.sentinel-solutions.net
1. It is most important that the correct concentration of the water
treatment products is maintained in accordance with the
manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable
additives MUST be removed by thorough cleansing.
3. In hard water areas, treatment to prevent limescale may be
necessary - however the use of artificially softened water is
NOT permitted.
4. Under no circumstances should the boiler be fired before
the system has been thoroughly flushed.
ELECTRICAL SUPPLY
WARNING. This appliance must be earthed.
Wiring external to the appliance MUST be in accordance with the
current I.E.E. (BS7671) Wiring Regulations and any local
regulations which apply. For Ireland reference should be made
to the current ETCI rules for electrical installations.
The point of connection to the mains should be readily
accessible and adjacent to the boiler.
CONDENSATE DRAIN
Condensate drains are provided on the boiler. These drains
must be connected to a drainage point on site. All pipework and
fittings in the condensate drainage system MUST be made of
plastic - no other materials may be used.
IMPORTANT. Any external runs must be insulated to avoid
freezing in cold weather causing blocking.
Boiler
Pressure Drop
Pressure Drop
(mbar) @ 20
o
C
(mbar) @ 11
o
C
F320
90
297
F400
95
314
F480
100
330
F560
105
347
HYDRAULIC RESISTANCE
7
xtra
-
Installation & Servicing
GENERAL
1
BOILER DIMENSIONS AND CONNECTIONS - HORIZONTAL FLUE CONNECTION KIT
FITTED
All dimensions shown in mm
im9615
Boiler Size
SIDE VIEW
FRONT VIEW
PLAN VIEW
REAR VIEW
G (Flow & Return)
17 (Condensate Drain)
110
91 (Gas)
113 (Air Inlet)
Flow
Connections
R2"
Return Connection R2"
Gas R1"
Air Inlet Ducts O110
Slave Module
High Level
Air Inlet Kit (If Fitted)
Master Module
8
xtra
-
Installation & Servicing
GENERAL
1
CONT'D...BOILER DIMENSIONS AND CONNECTIONS - VERTICAL FLUE CONNECTION
KIT FITTED
All dimensions shown in mm
110
High Level
Air Inlet Kit (If Fitted)
Boiler Size
REAR VIEW
Return Connection R2"
Air Inlet Ducts O110
Slave Module
Condensate
Drain
Master Module
SIDE VIEW
FRONT VIEW
PLAN VIEW
im9616
9
xtra
-
Installation & Servicing
GENERAL
2
BOILER DIMENSIONS AND CONNECTIONS
(Optional water and gas header kit and rs air duct connector (F320 & F400 only) fitted)
Note. F320 Model shown
4
VENTILATION
The ventilation requirements of these boilers are dependant
on the type of flue system used, and their heat input. All vents
must be permanent with no means of closing, and positioned
to avoid accidental obstructions by blocking or flooding.
Detail reference should be made to BS. 6644 for inputs
between 70kW and 1.8MW (net). In IE refer to the current
edition of I.S.820. The following notes are for general
guidance only:
Dust contamination in the combustion air may cause blockage
of the burner slots. Unless the boiler room provides a dust
free environment then direct connection of the air intake via
ducting to clean outside air should be used.
IMPORTANT NOTE.
If combustion air is drawn from within the boiler room,
ensure no dust or airborne debris can be ingested into the
appliance. Dusty concrete flooring should be sealed to
reduce the presence of dust.
The temperature within a boiler room shall not exceed 25
o
C
within 100 mm of the floor, 32
o
C at mid height and 40
o
C within
100 mm of the ceiling.
Open Flued Installations
If ventilation is to be provided by means of permanent high and
low vents communicating direct with outside air, then reference
can be made to the sizes below. For other ventilation options
refer to BS. 6644. In IE refer to the current edition of I.S.820.
Required area (cm
2
) per kW of total rated input (net)
Boiler Room
Enclosure
Low level (inlet)
4
10
High level (outlet)
2
5
Note: Where a boiler installation is to operate in summer
months (e.g. DHW) additional ventilation requirements are
stated, if operating for more than 50% of time (refer to BS6644).
Room Sealed Installations
A minimum of 2cm
2
free area per kW of net heat input at both
high and low level is required for boiler rooms. For enclosures
refer to BS6644.
3
BOILER CLEARANCES
The minimum dimensions as indicated must be respected to
ensure good access around the boiler.
Recommended minimum clearances are as follows.
Rear: 1000mm or adequate space from the rear of the jacket
to make the flue connections and access to the flue sample
point, drain connection, flue and any safety or control devices.
All dimensions shown in mm
SIDE VIEW
im9159
REAR VIEW
Flow
connection
Return
connection
Left Side: 450mm
Right Side: 450mm
Front: 600mm; except, access doors may be closer, but
not less than 200mm and 600mm must still be available
for service across the width of the boiler.
Top: 500mm.
10
xtra
-
Installation & Servicing
GENERAL
Rated output
Minimum bore
Nominal Size (DN)
kW
m m
in
301 to 600
50
2
'Steel pipe sizes complying with medium or heavy quality or BS 1387.
Detail reference should be made to the appropriate standards listed on
page 4.
The information and guidance given below is not intended to override any
requirements of the above publications or the requirements of the local
authority, gas or water undertakings.
The vertical distance between the pump and feed/expansion cistern MUST
comply with the pump manufacturer's minimum requirements, to avoid
cavitation. Should these conditions not apply either lower the pump
position or raise the cistern above the minimum requirement specified by
Ideal Stelrad Group. The isolation valves should be fitted as close to the
pump as possible.
The information provided is based on the following assumptions:
1. An independent open vent/safety pipe connection is made immediately
after the system flow pipe connection.
2. An independent cold feed/expansion pipe connection is made
immediately after the open vent/safety pipe connection.
3. The maximum flow rate through the boiler is based on a temperature
difference of 11
o
C at full boiler output.
4. The boiler is at the highest point of circulation in the system. Systems
designed to rise above the boiler flow tappings will automatically
require a minimum static head higher than that shown.
5. The position of the open vent/safety pipe above the expansion cistern
water level is given as a guide only. The final position will depend upon
the particular characteristics of the system. Pumping over of water into
the expansion cistern must be avoided.
6. Both open vent/safety pipe and cold feed/expansion pipes must be of
adequate diameter to suit the output of the boiler. Refer to Tables
below and BS 6644:2005.
5
OPEN VENTED SYSTEM REQUIREMENTS
Note.
·
With a cold feed head of <8m, the pump
must be fitted on the return to the boiler.
·
This diagram does not show safety valves,
water flow switches, etc. necessary for the
safe operation of the system.
6
SEALED SYSTEM REQUIREMENTS
Open Vent Pipe Sizes
Rated output
Minimum bore
Nominal Size (DN)
kW
m m
in
301 to 600
38
1
1
/
2
'Steel pipe sizes complying with medium or heavy quality or BS 1387.
Cold Feed Pipe Sizes
Note. Refer to Frame 29 for typical system arrangements.
Feed/expansion
cistern
Open vent
safety pipe
3 m
minimum
see notes
System
flow
Shunt Pump
(if required)
Inverted
cold feed
entry
Cold
Feed
Water
level
(cold)
Open vent
System
return
im8250
Connections
to boiler
Working pressure 6 bar maximum.
Particular reference should be made to BS. 6644 and
Guidance note PM5 "Automatically controlled steam and hot
water boilers" published by the Health and Safety Executive.
The information and guidance given below is not intended to
override any requirements of either of the above publications or
the requirements of the local authority, gas or water
undertakings.
In general commercial closed pressurised systems are
provided with either manual or automatic water make up.
In both instances it will be necessary to fit automatic controls
intended to protect the boiler, circulating system and ancillary
equipment by shutting down the boiler plant if a potentially
hazardous situation should arise.
Examples of such situations are low water level and operating
pressure or excessive pressure within the system. Depending
on circumstances, controls will need to be either manual or
automatic reset. In the event of a shutdown both visual and
audible alarms may be necessary.
Expansion vessels used must comply with BS. 4814 and must
be sized on the basis of the total system volume and initial
charge pressure.
Initial minimum charge pressure should not be less than 0.5
bar (7.2psi) and must take account of the static head and
specification of the pressurising equipment. The maximum
water temperatures permissible at the point of minimum
pressure in the system are specified in Guidance Note PM5.
When make up water is not provided automatically it will be
necessary to fit controls which shut down the plant in the event
of the maximum system pressure approaching to within
0.35bar (5psi) of the safety valve setting.
Other British Standards applicable to commercial sealed
systems are:
BS. 6880: Part 2
BS. 1212
BS. 6281: Part 1
BS. 6282: Part 1
BS. 6283: Part 4
11
xtra
-
Installation & Servicing
INSTALLATION
7
BOILER ASSEMBLY
Legend
2. Burner switch
3. Pressure gauge
8. Fan
9. Gas Valve
11. Venturi
12. Control Module
14. Damper Relay Board
19. Union Gas cock
20. Levelling feet
22. Heat exchanger
24. Sightglass
27. Burner manifold
31. Thermistor (flow)
33. Air pressure switch
37. Relay
38. Cable conduit
47. Ignition / detection electrode
54. OT Center
8
2
3
9
11
33
22
31
31
24
27
47
12
38
38
37
14
20
Data
Plate
19
54
im8496
INST
ALLA
TION
12
xtra
-
Installation & Servicing
INSTALLATION
im8481
2
4
3
5
3
Rear screw on
both sides to
be left in place
1
The boiler comprises of an equally sized Master
and Slave Module, separately packed on their
own pallets. This allows the boiler to be
handled by a forklift.
The packaged boiler will pass through a
930mm wide opening. Removing the casing
assembly pack from the Master Module will
allow Modules through a 700mm wide opening.
8
PACKAGING REMOVAL / REMOVAL FROM PALLET
To unpack the modules:
-
Carefully remove the straps, and lift off the casing assembly pack -
master only.
-
Open Master Module box and remove literature pack.
-
Remove the protective cardboard fittings.
-
Safely dispose of all packing materials.
To remove the Modules from base:
1. Remove 2 screws securing casing support outrigger and discard
item (Master only).
2. Remove the 3 front screws (2 screws on 320 model) on both sides
leaving the 2 rear screws in place.
3. Rotate bottom battens outwards allowing the front of the base to rest
on the floor.
4. Remove 4 screws and retaining brackets.
5. Slide the module off the base.
Repeat Steps 2 - 5 for slave module.
INST
ALLA
TION
13
xtra
-
Installation & Servicing
INSTALLATION
1. Fit spacers x 4 to the LH side corners of the Master Module chassis (located inside casing assembly pack).
2. Control Fascia Panel - Master Module: Remove the 2
screws securing the control fascia panel. Carefully lift it
slightly and lower the top forwards allowing it to rest on the
hinge lugs.
6. Remove and discard fascia retaining bracket (x 4) from Slave and Master modules.
9
ASSEMBLING THE MODULES
4. Control Fascia Panel - Slave Module: Remove 2 screws
securing the outer fascia panel. Lift and remove fascia,
store safely.
3. Release the ribbon cable from the display board.
Raise control fascia slightly and withdraw. Store safely.
5. Remove 2 screws securing inner fascia panel. Lift and
support panel while releasing ribbon cable from the
display board. Remove fascia and store safely.
Spacers (x4)
INST
ALLA
TION
14
xtra
-
Installation & Servicing
INSTALLATION
10. Replace with the one piece front controls channel and
secure with 6 screws (located in casing assembly pack).
7. Position Master Module and level feet using a 13mm spanner. Check module with spirit level.
IMPORTANT. ENSURE MODULE IS LEVEL IN BOTH DIRECTIONS TO ENSURE SATISFACTORY ASSEMBLY.
9. Remove 4 screws on each control box support
channel and discard channels.
8. Position Slave Module to LH side of Master Module (ensuring not to disturb levelled Master Module) and
repeat levelling process.
10 ASSEMBLING THE MODULES .... CONTINUED
INST
ALLA
TION
15
xtra
-
Installation & Servicing
INSTALLATION
11. Remove 4 screws on each rear gas pipe support
channel and discard channels.
16. Fit Slave inner fascia panel to Slave Module securing with 2
x M5 screws whilst re-fitting ribbon cable to display board.
12. Replace with the one piece rear gas pipe support channel and
secure with 6 screws (located in casing assembly pack).
15. Fit master fascia panel securing with 2 x M4
screws. Ensure ribbon cable is re-fitted.
14. Place top panel onto both modules and
secure at rear with 2 x M5 screws
(supplied).
13. Tie support the thermistor harnesses on each boiler
module. The thermistor harness is located towards the rear
of each boiler module. Using the 4 tie wraps supplied in the
casing assembly pack, tie the harnesses to the 4 holes
located on the inside face of the rear support channel.
11 ASSEMBLING THE MODULES .... CONTINUED
INST
ALLA
TION
16
xtra
-
Installation & Servicing
INSTALLATION
REAR VIEW
Flue
Sampling
Point
Air inlet duct O110
A
F
B
C
D
E
See Table on page 5 for guidance on maximum permissible
flue and air duct system design.
FLUE
Construct either the horizontal or vertical combined flue outlet
ductwork to create the manifold arrangement depicted. The
horizontal combined flue outlet can be installed with its outlet
facing left or right dependent upon the demands of each
particular installation.
A tube of ductwork seal lubricant is provided within the flue kit.
To ease flue connections lubricate all flue seals before
assembly. Flue sampling points are fitted within the ductwork
legs A and B as depicted to facilitate flue products sampling of
each boiler module.
IMPORTANT NOTES.
1. The flue manifold should be supported in such a way as
not to place load on the boiler module flue outlet sockets.
Propriety flue duct brackets must be used to provide
support as appropriate.
2. Unless the connecting flue is manufactured from
aluminium the condensate generated within the flue must
be collected and drained before entering the combined flue
outlet ductwork. When employing the vertical combined
flue outlet header, a flue condensate drain is provided for
this purpose.
12 FLUE / AIR DUCT INSTALLATION
KEY
A Flue Tube
D Bend x 45
o
B Flue Tube
E Connector
C Bend x 87
o
F Adaptor
REAR VIEW
Flue
Sampling
Point
A
D
B
C
im9161
Air inlet duct O110
AIR DUCT
Combustion air can be drawn directly from the boiler room
using the high level air inlet kit provided or ducted in from
outside the building in which the boiler is installed.
IMPORTANT NOTE. If combustion air is drawn from within the
boiler room, ensure no dust or airborne debris can be
ingested into the appliance. Dusty concrete flooring should
be sealed to reduce the presence of dust. Ideally where
possible duct the air supply into the boiler room from a clean
source outside the boiler room / building.
To draw air direct from outside, connection can be made using
separate ducts to each boiler Module. This can be done using
any propriety 110mm soil / drain pipe. Expansion to a larger
diameter may be required to reduce resistance, dependant on
total flue / air duct lengths required. (See Flue System Design
on Page 5). The air duct should be terminated with a suitable
fixed grille to prevent entry to vermin. This terminal should be
positioned as such to avoid blockages or entry of water.
An optional RS duct connector kit allows for the two individual
module air inlet connections to be combined into a single
200mm boiler air supply connection to simplify installation and
increase permissible air duct length (F320 and F400 only)
HORIZONTAL FLUE HEADER ARRANGEMENT
KEY
A Flue Tube
C Flue Tee Manifold
B Flue Tube
D Flue Condensate Drain Trap
VERTICAL FLUE HEADER ARRANGEMENT
INST
ALLA
TION
17
xtra
-
Installation & Servicing
INSTALLATION
12 AIR DUCT CONT'D....
Where ducting the air from outside is not practical it can be
drawn from the boiler room by assembling the air inlet
pipework as follows into the configuration shown in fig 1 & 2.
1. Fit the 93º elbow into the boiler air inlet pipe.
2. Fit the 112.5º bend into the 93º elbow.
3. Fit the 110 dia. tube into the 112.5º bend.
4. Fit the air inlet grille to 110 dia. tube and fix with the 3 off self
tapping screws provided.
5. Using the existing screws holding the upper or centre back
panel to the boiler, fit the support bracket assembly and re-
tighten the screws.
6. With the air inlet pipe assembly in position, retain it with the
pipe clamp, fixed with the 2 off M5 screws provided.
With this kit fitted the maximum straight flue length available
and maximum pressure available at the base of the flue to
overcome flue resistance will change, refer to the appropriate
table on page 5.
fig 1
5
4
6
3
2
1
fig 2
5
4
6
3
2
1
INST
ALLA
TION
18
xtra
-
Installation & Servicing
INSTALLATION
REAR VIEW
RETURN
FLOW
(Must be
connected
opposite side
to flow
connection)
(Must be
connected
opposite side
to return
connection)
im8482
13 CONDENSATE DRAIN (Slave and Master)
A condensate drain must be connected to the
condensate bulk head connector on the back of each
module and then connected to a drainage point,
preferably within the building.
The pipe size from the condensate connector on the
lower rear panel is 21.5mm.
The routing of the drain must be made to allow a
minimum fall of 1 in 20 away from the boiler, throughout
its length.
14 BOILER WATER CONNECTIONS
The boiler flow and return pipes are terminated with 2 x R2" BSP male
connections at the rear of the appliance. Water returning from the system
should be connected to a lower header pipe, with the flow water connection
coming from a top header pipe. An optional pre-
fabricated header pipe kit is available.
Refer to Frames 1 and 2 for dimensional
positions.
All flow and return pipework must be
independently supported.
Plastic plugs fitted on the open ends of the flow
and return pipes must be removed before
connecting the system pipework.
An air vent must be provided immediately after the
flow connection.
If installing the boiler onto an existing system it is
strongly recommended that the system be
thoroughly flushed before connecting the boiler.
When connecting to a new system it is still
important to flush the whole system in accordance
with the relevant standards.
Condensate Bulkhead Connector
If the vertical flue header is specified the flue manifold
condensate drain connection must also be connected in the
same manner.
IMPORTANT. Any external runs must be kept to a minimum
and insulated. This is to avoid freezing in cold weather
causing blocking.
All pipework and fittings in the condensate drain system
must be made of plastic. No other materials may be used.
Note.
Connection to the boilers using manifolds must
use a reverse return principle to ensure equal flow
distribution through both of the modules, see
example below.
Connection of opposing flow and return points can
be made either on the LH side or RH side,
dependent upon the particular needs of the boiler
installation.
INST
ALLA
TION
19
xtra
-
Installation & Servicing
INSTALLATION
18 INSTALLING THE MAINS AND CONTROL WIRING (MASTER AND SLAVE MODULES)
1. Route all 230V circuits in at the rear, through
conduit no. 1 on both Master and Slave
Modules.
2. Route all low voltage remote sensor/control
cables for the master module through conduit
no. 2.
3. Secure the cables with the cable clamps
provided on the main controls panel.
2
1
16 GAS CONNECTIONS
The boiler gas supply pipe is terminated in 2 x R1" BSP male
taper connections on the left-hand sides of the modules.
A gas header kit is available to combine the inlet connections
to a 2" manifold.
All gas supply pipework must be independently supported.
A minimum working gas pressure of 15mbar (6" w.g.) must
be available at the boiler inlet with the boiler firing.
Fit a gas supply pipe NOT LESS THAN 2" BSP to the boiler.
17 ELECTRICAL CONNECTIONS
Warning. This appliance MUST be efficiently earthed.
A mains supply of 230V 50Hz is required to be fitted to both the
Master and Slave Modules (see terminals marked 'Mains In'
Frame 19). External controls should NOT be wired in series
with these mains inputs. Controlling the boiler in this way will
prevent the pump over-run sequence and may cause damage
to the modules. The supply wiring MUST be suitable for mains
voltage. Wiring should be 3 core PVC insulated cable NOT
LESS than 0.75mm
2
(24 x 0.2 mm) and to BS. 6500, Table 16.
The fuse rating should be 7A.
Wiring external to the boiler MUST be in accordance with the
current I.E.E. (BS7671) wiring Regulations and any local
regulations. For Ireland reference should be made to the
current ETCI rules for electrical installations.
Connection should be made in a way that allows complete
isolation of the electrical supply - such as a double pole
switch, having a 3mm (1/8") contact separation in both poles,
or a plug and unswitched socket serving only the boiler and
system controls. The means of isolation must be accessible
to the user after installation.
When making mains electrical connections to the modules it
is important that the wires are prepared in such a way that the
earth conductor is longer than the current carrying conductors,
such that if the cord anchorage should slip the current carrying
conductors become taut before the earthing conductor.
WARNING. Sensor cables must be separated from cables in
the 230V circuit. For this purpose three conduits are
provided. Refer to Frame 19 for terminal strip connections.
15 FROST PROTECTION
The boiler has built into its control system the facility to protect
the boiler only against freezing.
If the boiler flow temperature T
1
, falls below 7
o
C the pump will
be activated without the boiler firing.
If the flow temperature falls below 5
o
C the boiler will fire until
the flow temperature exceeds 10
o
C. The pump will stay
running for a further 5 minutes.
Central heating systems fitted wholly inside the building do
not normally require frost protection as the building acts as a
'storage heater' and can normally be left at least 24 hours
without frost damage. However, if parts of the pipework run
outside the building or if the boiler will be left off for more than
a day or so, then frost protection for the system is
recommended.
INST
ALLA
TION
20
xtra
-
Installation & Servicing
INSTALLATION
19 INSTALLER CONNECTIONS
230V AC
permanent
mains supply
230V AC permanent
mains supply
230V AC
output for CH
system pump.
max 1 amp
Optional 230V AC
output for DHW pump
or divertor valve.
max 1 amp.
*
Optional call for CH
Optional call for DHW
im8483
MASTER MODULE
SLAVE MODULE
*
Optional connections for
programmable room stat
and modulating sequencer kits
Optional volt free connections for
boiler alarm during lock out condition.
(Closed circuit during lock out)
Optional connections for outside
temperature sensor kit
*
Optional connections 0-10V
boiler control
Test point for measuring
flame ionisation current using
0-10V DC meter - see Frame 61
Test point for measuring
flame ionisation current using
0-10V DC meter - see Frame 61
Optional volt free connections for
boiler 'run' inidication
(Closed circuit during burner on operation)
0-10V
Ground
*
Note.
BOTH OT CENTERS MUST BE CONFIGURED IN ACCORDANCE WITH BOILER CONTROL INPUT OPTION CHOSEN.
(See Frame 22 for details)
Input terminals are available for connecting a variety of system
controls for central heating demand. Only one method should
be employed on an individual boiler. OT Centers to be
configured in accordance with choice mode (see to Frame 22).
Heating demand can be controlled by:
1. ON/OFF using a 230V switched live to 'CH call' terminal.
(e.g. programmer and/or room thermostat).
A call for heat will cause the boiler to run and maintain a set
flow temperature controlled by parameter 4* (see Frame 31).
Connect switched live to Master Module terminal marked 'CH
CALL'.
2. Programmable Room Thermostat Kit.
The programmable room thermostat kit incorporates a room
temperature sensor and a programmer capable of
controlling the heat output from the boiler to satisfy different
temperature requirements at different time periods. The
addition of an Outside Sensor Kit will enable a weather
compensated flow temperature (see Instructions with kit for
more details).
Connect Programmable Room Thermostat to Master Module
using terminals marked 'CONTROLLER'. Wires have no
polarity and are low voltage control cables.
3. Modulating Sequencer Kit.
A Modulating Sequencer Kit is capable of controlling the
heat demand on up to 5 boilers simultaneously. (See
instructions with kit for more details.)
Connect Modulating Sequencer Kit to Master Module
using terminals marked 'CONTROLLER'. Wires have no
polarity and are low voltage control cables.
4. 0-10V
A call for heat can be generated using a 0-10V input with
the flow temperature setpoint controlled by the voltage
signal. 10V generates a maximum flow temperature top
limited by parameter 4* (see Frame 31).
Connect 0-10V signal to Master Module using terminals
marked '0-10V INPUT'. The ground wire should be
connected to the lower terminal and the 0-10V
modulating signal to the upper terminal.
CH Pump
Output terminals marked 'CH PUMP' are provided for a
circulating pump which must be connected to allow the
pump overrun function to operate. A pump requiring more
than 1 amp supply current must be connected via a relay.
20 CH CONTROL CONNECTIONS
* Changes to parameter 4 must be carried out in common to
both Master and Slave Modules.
INST
ALLA
TION
21
xtra
-
Installation & Servicing
INSTALLATION
S1
S2
Rear of OT Center
23 FITTING OT CENTER
22 OT CENTER CONFIGURATION
The OT Centers on each module are factory pre-set as
master and slave units for CH ON/OFF call for heat.
To check the settings or to configure for alternative control
options remove the OT Center and set switches "S1 and "S2"
according to the tables below (See Frame 67 for details of
how to remove and replace OT Centers).
If the boiler is providing both CH and DHW, and the CH circuit
is to operate for periods at a reduced temperature (i.e.
weather compensated), then it is necessary to differentiate
between CH and DHW heat demands. For this purpose a
DHW demand can be placed on the boiler using the method
shown below.
A demand for DHW has priority over CH by parameter 43 (see
Frame 38).
A call for DHW will cause the boiler to run and maintain a set
flow temperature of 80
o
C.
21 DHW CONTROLS CONNECTIONS
DHW heat demand can be controlled by:
1. ON/OFF using a 230V switched to live 'DHW call' terminal
(e.g. a cylinder thermostat and/ or programmer).
A call for heat will cause the boiler to run and maintain a set
flow temperature of 80
o
C.
Output terminals are provided for a DHW pump or valve. This
output can be used to control the diversion of flow to the DHW
circuit. A pump or valve requiring more than 1 amp supply
current must be connected via a relay.
* Changes to parameter 4 must be carried out in common to
both Master and Slave Modules.
Position S2
Function
1
Master - Module
2
Slave Module
Position S1
Function
1
N/A
2
N/A
3
Opentherm programmable
room stat or sequencer kit
4
CH ON-OFF call for heat
5
0 to 10 V Input
Note.
Both OT Centers (Master and Slave Modules) must
be configured similarly.
1. Locate the communication lead attached to the OT Center on the Master Module.
2. Route cable through grommet, and across behind control panels and back out
through grommet.
3
3
2
3. Plug remaining end into either
socket on Slave Module OT
Center.
INST
ALLA
TION
22
xtra
-
Installation & Servicing
INSTALLATION
24 PICTORIAL WIRING DIAGRAM (MASTER BOILER)
HT
11
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
Damper
T
r
ansformer
65
X1
4321
12
X2
GV
MCBA5407D
3456
789
10
11
1
2
12
X3/4
X5
SUPPRESSOR
SUPPRESSOR
SUPPRESSOR
R2
R1
X8
34
1234
56
789
10
11
1
2
1
2
3
4
5
6
7
8
910
11
1213
1415
16
X10
X7
AM3
MASTER
OT
CENTER
Connection to
Slave Wiring
Centre
TB1
CONTROLLER
DHW
CALL
CH
CALL
DHW PUMP
OR VA
LV
E
CH PUMP
MAINS IN
OUTSIDE
TEMP
0-10V
INPUT
BS*
RY
1
RY
2
* Note. For BS open circuit is on, closed circuit is of
f.
TTL
DISPLA
Y
TB2
FUSE
LEGEND
NTC1
NTC2
NTC5
NTC7
PW
R1
R2
RY
1
RY
2
GV
BS
A
PS1
KEY
-
-
-
-
-
-
-
-
-
-
-
-
Flow thermistor
Return thermistor
Flue thermistor
Heat exchanger thermistor
W
a
ter pressure switch
Relay 1 230V
AC coil
Relay 2 230V
AC coil
Relay 1 Switch (signal)
Relay 2 Switch (signal)
Gas valve
Burner switch
Air pressure switch
w
y/g
g
or
v
-
-
-
-
-
white
yellow/green
grey
orange
violet
b
bk
br
r
pk
y
-
-
-
-
-
-
blue
black
brown
red
pink
yellow
v
w
g
or
bk
gy
bk
br
br
br
b
br
br
br
br
b
b
b
b
g
v
g
bk
bk
bk
br
r
r
r
v
w
bk
r
y
pk
r
b
bk
w
pk
r
bk
y/g
y/g
y/g
y/g
y/g
y/g
v
g
w
w
bk
bk
or
br
pk
y
bk
w
PWM
+
ELN
TACH
APS1
PW
INST
ALLA
TION
23
xtra
-
Installation & Servicing
INSTALLATION
25 PICTORIAL WIRING DIAGRAM (SLAVE BOILER)
65
X1
4321
12
X2
3456
789
10
11
1
2
12
X3/4
X5
34
1234
56
789
10
11
1
2
HT
MCBA5407D
X8
X10
X7
Damper
Fuse
MAINS IN
T
r
ansformer
SUPPRESSOR
AM3
DISPLA
Y
1
2
3
4
5
6
7
8
910
11
1213
1415
16
SLA
VE
OT
CENTRE
Connection to
Master Wiring
Centre
1
TTL
g
GV
PWM
+
ELN
TACH
APS1
NTC5
NTC7
NTC1
NTC2
PW
b
b
br
bk
bk
w
w
g
v
bk
bk
b
r
pk
y
w
v
r
pk
w
br
br
b
br
br
3
2
1
y/g
y/g
y/g
LEGEND
NTC1
NTC2
NTC5
NTC7
PW
R1
R2
RY
1
RY
2
GV
BS
A
PS1
KEY
-
-
-
-
-
-
-
-
-
-
-
-
Flow thermistor
Return thermistor
Flue thermistor
Heat exchanger thermistor
W
a
ter pressure switch
Relay 1 230V
AC coil
Relay 2 230V
AC coil
Relay 1 Switch (signal)
Relay 2 Switch (signal)
Gas valve
Burner switch
Air pressure switch
w
y/g
g
or
v
-
-
-
-
-
white
yellow/green
grey
orange
violet
b
bk
br
r
pk
y
-
-
-
-
-
-
blue
black
brown
red
pink
yellow
INST
ALLA
TION
24
xtra
-
Installation & Servicing
INSTALLATION
26 CH ON/OFF NO SEPARATE DHW DEMAND
For simple ON/OFF control of the boiler with a fixed flow temperature setpoint (see parameter 4 Frame 31), then the following
method should be used for connecting the boiler.
27 MAINS VOLTAGE CH AND DHW CONTROLS WITH DHW PUMP OUTPUT
No parameter
modifications are
required.
Alternatives: The
Ideal programmable
room thermostat and
outside sensor kit
provides enhanced
user comfort. Full
instructions provided
with kits.
Pump
Pump
Non return
valve
Non return
valve
Cylinder
thermostat
Programmer
Room
stat
im8191
This system provides heating to one zone at a time with
DHW priority controlled by parameter 43. To heat more
than one zone simultaneously, use zone
thermostats to energise individual zone valves
with all calls for heat applied to 'CH CALL'.
The boiler will be limited to responding with
a set flow temperature set by parameter 4
(see Frame 31).
If all zones are fitted with individual zone
valves a hydraulic bypass will be required to
allow pump overrun. See pages 6 and 10
for details.
Frost Stat if required*
230 VAC
Permanent
mains supply
Switched live (230 VAC)
from external controls
generating call for heat*
System pump
(maximum load 1 amp)
connect via a relay for
greater currents
CH
CALL
DHW PUMP OR VALVE
N
L
CH PUMP
N
L
MAINS IN
N
L
DHW
CALL
230 VAC
Permanent
mains supply
MAINS IN
N
L
im8485
* The switched live from
external controls must be
from the same phase
supply as the boiler mains
supply to ensure that
when the boiler supply is
switched off the controls
are also isolated.
MASTER MODULE
SLAVE MODULE
No parameter modifications are required.
* The switched live from external controls must be from the same phase supply as the boiler
mains supply to ensure that when the boiler supply is switched off the controls are also isolated.
230 VAC
Permanent
mains supply
If either pump requires more than
1 amp supply current, connection
must be made via a relay
Room
stat
Cyl
stat
DHW
CH
External 230 VAC
Programmer *
CH
CALL
DHW PUMP OR VALVE
N
L
N
L
CH PUMP
N
L
MAINS IN
N
L
DHW
CALL
D H W
230 VAC
Permanent
mains supply
MAINS IN
N
L
im8486
SLAVE MODULE
MASTER MODULE
INST
ALLA
TION
25
xtra
-
Installation & Servicing
INSTALLATION
Alternatives: The Ideal programmable room thermostat and outside sensor kit provides enhanced user comfort. Full
instructions provided with kits.
Parameter modifications see Frames 35 to 39.
Parameter 46 = 03 If a live output is required for positioning of
the valve to satisfy CH demand.
Parameter 46 = 23 If a live output is required for positioning of
the valve to satisfy DHW demand.
This system provides heating to one zone at a time with DHW
priority controlled by parameter 43. To heat more than one
zone simultaneously, use zone thermostats to energise
individual zone valves with all calls for heat applied to 'CH
CALL'. The boiler will be limited to responding with a set flow
temperature set by parameter 4 (see Frame 31).
If all zones are fitted with individual zone valves a hydraulic
bypass will be required to allow pump overrun. See page 6
and 10 for details.
im8193
Motorised valve
Pump
Cylinder
thermostat
Programmer
Room
stat
28 MAINS VOLTAGE CH AND DHW CONTROLS WITH DHW VALVE OUTPUT
* The switched live from external controls must be from the same phase supply as the boiler
mains supply to ensure that when the boiler supply is switched off the controls are also isolated.
230 VAC
Permanent
mains supply
If pump requires more
than 1 amp supply current,
connection must be made
via a relay
Motorised
Valve
(Not Mid-position)
Room
stat
Cyl
stat
DHW
CH
External 230 VAC
Programmer *
CH
CALL
DHW PUMP OR VALVE
M V
D H W
N
L
N
L
CH PUMP
N
L
MAINS IN
N
L
DHW
CALL
230 VAC
Permanent
mains supply
MAINS IN
N
L
im8487
SLAVE MODULE
MASTER MODULE
INST
ALLA
TION
26
xtra
-
Installation & Servicing
INSTALLATION
29 EXAMPLES OF HEATING SYSTEMS
Heating system with DHW production (storage tank Output = Boiler Output) and mixing header.
Flow
Return
Primary
System
Pump
Filter
Mixing
Header
Heating circuit
Heating
System
Pump
im8196
Storage
tank output
=
boiler output
A
B
AB
3 way diverting valve
M
N
L
N
L
Primary
System
Pump
Filter
Mixing
Header
Heating circuit
Heating
System
Pump
im8197
N
L
Flow
Return
Note.
If PARA '46' 1st digit is set to 2, it means you wish to have a 3
way valve normally open towards the CH circuit (radiator
circuits from AB to A). Upon DHW request, terminal 'L' on
'DHW PUMP OR VALVE' is energised which, through a relay,
powers the 3-way valve, thus closing port A and opening port B.
Simultaneously terminal 'L' on 'CH PUMP' is energised which,
through another relay, powers the primary system pump.
If PARA '46' 1st digit is set to 0, it means you wish to have a 3
way valve normally open towards the storage tank (DHW
circuit from AB to B). Upon CH request, terminal 'L' on 'DHW
PUMP OR VALVE' is energised which, through a relay, powers
the 3-way valve, thus closing port B and opening port A.
Simultaneously terminal 'L' on 'CH PUMP' is energised which,
through another relay, powers the primary system pump.
Heating system with one group of radiators (controlled by thermostatic valves)
DHW storage tank with DHW pump installed on the secondary circuit, in parallel with the heating circuit
im8198
Filter
Primary
System
Pump
Mixing header
non return
valve
Heating circuit
Heating
system pump
DHW
pump
DHW
tank
Flow
Return
N
L
N
L
Note.
The primary system pump would be off while the DHW pump is running with PARA '46' 1st digit set to '1x'. This would only give
adequate circulation if the DHW pump was connected into the primary circuit, shown to the left of the mixing header above.
However, in the case shown it will be necessary to run the primary system pump with the DHW pump for correct circulation. To
achieve this set PARA '46' 1st digit '2x'.
INST
ALLA
TION
27
xtra
-
Installation & Servicing
INSTALLATION
30 BASIC CONTROLS DISPLAY (MASTER PANEL SHOWN)
During the operation of the
xtra
, the status of the
appliance can be determined by the display.
1. Normal Operation Mode
The unit will either be in standby or in operation. The first
digit on the display shows the boiler status (see table). The
last 3 digits show the flow temperature.
2. Blocking Mode
The Module will enter blocking mode under certain fault
conditions. Whilst in blocking mode the burner is switched
off. Once the fault conditions are clear the boiler will
automatically reset itself. In blocking mode the display will
alternate between showing a '9' in digit one, along with the
flow temperature in digits 2, 3 and 4.
9 9 6
Followed by the blocking code 'bxx'. Refer to page 54 for
Blocking Code references.
3. Error Mode
In error mode the display will show the error code.
Refer to Page 52 for error codes.
The Module will enter error mode under certain fault
conditions. The unit will be inoperative until the fault is
rectified. The reset button is used to reset the Module
control box after an error has occurred.
Self Check and Anti-seize Modes
After switching on the mains power or after a reset, the
boiler performs a selfcheck, i.e. the DHW valve is
energised and the CH pump is switched on for 10
seconds. This cycle repeats itself every 24hrs, as long as
no heat request is given in 24hrs.
Burner on/off switch
With the burner switch set to 'off' the boiler will not
respond to a CH demand. However, it will respond to a
DHW demand and the pump anti-seize and frost
protection modes are still operational any one of which
could cause the boiler to fire. Note. The burner switch is
NOT a mains isolation switch.
CH/DHW Systems
In standby mode pressing and holding the '+' button for 3
seconds turns the CH system on/off.
In standby mode pressing and holding the '-' button for 3
seconds turns the DHW system on/off.
E 3 6
Sequence
Boiler Status
A
DHW valve energised
0
Standby, no heat request
1
Pre-purge, post purge
2
Ignition
3
Burner on in CH mode
4
Burner on in DHW mode
5
Waiting for air pressure switch to open or close
6
Burner off because a set value has been
reached
7
Pump overrun in CH mode
8
Pump overrun in DHW mode
e.g.
A. Burner switch
B. Pressure gauge
C. Display
D. Reset button
E. Mode button
F. Step button
G. Store button
H. + button (to increase
values)
I. - button (to decrease
values)
0
I
xtra
MODE
STEP
STORE
RESET
+
A
B
C
D
E
F
G
H
I
im8219
MASTER MODULE
CONTROL PANEL
b 1 8
Both Master and Slave Modules employ a control panel.
Slave control panel can be fully accessed by first removing cover (see Frame 52).
INST
ALLA
TION
28
xtra
-
Installation & Servicing
INSTALLATION
Press the 'step' button until the desired parameter is displayed.
The dot after the 1st digit is illuminated to indicate that the boiler is in 'PARA' mode.
N/A
Do not
Do not
adjust
adjust
60
Press
Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
DHW System
00 = Off
01
01 = On
02 = Off + pump continuous
03 = On + pump continuous
1. 6 0
2. 0 1
CH System
00 = Off
01 = On
01
02 = Off + pump continuous
03 = On + pump continuous
3. 0 1
CH Flow Temperature (
o
C) (T1)
20
90
82
4. 8 2
Press the '+' or '-' buttons to change the values.
The parameter setting can be stored by pressing and releasing the 'store' button, the new setting flashes twice to show it
has been accepted. The new setting will become active when the parameter mode is left.
31 STANDARD CONTROLS ACCESS
Modes of Operation
The standby, parameter and information modes are accessible without the service code.
Standby Mode
P A R A
Press
Display
The standby mode will be shown after start up or reset of the Module control box. If no buttons are pressed for 20
minutes the display will automatically be set to standby mode. If new parameters have been stored they will then
become active.
Parameter Mode
S t b y
P A R A
In parameter mode it is possible to change the settings of the Module control box. The following settings can be changed.
NOTE. Changes to these parameters MUST be done in common to both Master and Slave Modules.
1.
DHW Temperature (T3)
2.
DHW System ON/OFF
3.
CH System ON/OFF
4.
Flow Temperature (T1)
Parameter settings and limits are listed below.
Parameter mode is entered from standby mode by pressing the 'mode' button once.
continued...........
INST
ALLA
TION
29
xtra
-
Installation & Servicing
INSTALLATION
Info Mode
32 STANDARD CONTROLS ACCESS CONT'D
I N F O
P A R A
Press
Display
I N F O
Actual Flow Temperature T1 (
o
C)
Press
Display
Description
Actual Return Temperature T2 (
o
C)
1. 2 1
2. 2 1
3. - 3 6
OUTSIDE Temperature T4 (
o
C)
(-36 displayed if outside sensor kit not fitted)
4. - 3 6
N/A
FLUE GAS Temperature T5 (
o
C)
Set Flow Temperature (
o
C)
5. 7 0
6. 8 2
7. 0. 0
Rate of Return Temperature Rise (
o
C/s)
8. 0. 0
Rate of Flow Temperature Rise (
o
C/s)
9. 0. 0
N/A
A. - 3 6
N/A
Flashing
Info mode is entered from standby mode by pressing the 'mode' button twice.
Press the step button until the desired information is displayed. The dot after the 1st digit will be flashing indicating
the Module is in 'info' mode. No settings can be changed in 'info' mode.
continued...........
INST
ALLA
TION
30
xtra
-
Installation & Servicing
INSTALLATION
33 STANDARD CONTROLS ACCESS CONT'D
N/A
Press
Display
Description
Heat Exchanger Temperature T7 (
o
C)
b. 0. 0
C. 8 2
d. 0. 1
Ionisation Current (micro amps)
E. 0. 1
Rate of increase in Temperature T7 (
o
C/s)
N/A
N/A
F. 0. 0
G. 0. 0
H. 3 5
Number of Ignitions, CH
100 thousands/10 thousands
I. 0 0
Boiler Control Module Internal Temperature (
o
C)
Number of Ignitions, CH
tens/units
Number of Ignitions, CH
thousands/hundreds
Info mode cont'd.........
continued...........
Burner Run Hours, CH
100 thousands/10 thousands
Burner Run Hours, CH
thousands/hundreds
J. 0 0
Number of Ignitions, DHW
100 thousands/10 thousands
L. 0 0
Burner Run Hours, CH
tens/units
Number of Ignitions, DHW
thousands/hundreds
Number of Ignitions, DHW
tens/units
I . 0 0
I. 0 0
I. 0 0
I . 0 0
I. 0 0
I . 0 0
INST
ALLA
TION
31
xtra
-
Installation & Servicing
INSTALLATION
Service Mode
34 STANDARD CONTROLS ACCESS CONT'D
L 6 0
H 8 0
or
It is possible for servicing purposes to run the boiler on maximum or minimum loads.
This mode is entered from normal operating mode.
As found
Press
Display
Description
Standby display
X X X X
S t b y
0 2 8
Normal Display
several times
Press the 'mode' and '-' button simultaneously for 3 seconds.
L 6 0
Press
Display
Description
'Min. Load'. Run for 15 mins
*
Press the 'mode' and '+' button simultaneously for 3 seconds.
H 8 0
Press
Display
Description
'Max. Load'. Run for 15 mins
*
OR
*
Last 3 digits are actual flow temperature
This mode will end automatically after 15 minutes. Alternatively to escape sooner press the '+' and '-' simultaneously.
In order to set the Module to a fixed fan speed proceed to CODE MODE (Page 32) and select 'PARA' mode 47 (Page 28).
Wait a few
seconds
Press
Display
Description
Info mode cont'd.........
Burner Run Hours, DHW
100 thousands/10 thousands
N. 0 0
Burner Run Hours, DHW
thousands/hundreds
Burner Run Hours, DHW
tens/units
I. 0 0
I . 0 0
INST
ALLA
TION
32
xtra
-
Installation & Servicing
INSTALLATION
35 ADVANCED CONTROLS ACCESS
C O D E
C O D E
Press
Display
C X X
Press
Display
C 5 4
Press
Display
or
C 5 4
Press
Display
FLASHING
There is little requirement for advanced controls access as factory preset values are satisfactory for most parameters. If
parameter changes are required with the optional kits then further instructions are provided with them.
This mode must only be entered by a competent engineer. This level of access MUST NOT be entered by the user.
Code Mode
By entering the service code the following additional features are accessible:
·
Parameters 5 to 53
·
Fan Speed Mode
·
Communication Mode
·
Error Mode
Code Mode is entered from 'standby' mode by pressing and holding the 'mode' and 'step' buttons. When the display
shows 'CODE' release the buttons.
Press the 'step' button once and the display will show 'C' as the first digit and a random number in the 3rd and 4th digits.
Use the '+' or '-' button to change the Code to 54.
Press and release the 'store' button, the display flashes to show the code has been accepted.
continued...........
Press the 'mode' button until the mode you want is displayed.
INST
ALLA
TION
33
xtra
-
Installation & Servicing
INSTALLATION
36 ADVANCED CONTROLS ACCESS CONT'D
Press
Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
N/A
Do not
Do not
adjust
adjust
60
P A R A
1. 6 0
2. 0 1
CH System
00 = Off
01
01 = On
02 = Off + pump continuous
03 = On + pump continuous
3. 0 1
DHW System
00 = Off
01
01 = On
02 = Off + pump continuous
03 = On + pump continuous
CH flow temperature (
o
C) T1 (max.)
20
90
82
CH flow temperature (min) (
o
C)
Lowest set flow temperature on the warmest day (papa 12)
15
60
25
4. 8 2
. 2 0
1
2
3
4
P10 appears
for 1 second then
10
Minimum outside temperature (
o
C)
-20
10
-05
Coldest outside temp. the system is designed to work against
11
P11
Maximum outside temperature (
o
C)
15
25
20
Warmest outside temp. the system is designed to work against
12
P12
Outside temperature (
o
C)
-30
10
-02
(at which frost protection starts)
13
P13
Steps 5 to 9 are not accessible.
Outside temperature correction (
o
C)
-05
05
00
(for boiler reading of outside temperature)
14
P14
N/A
20
45
40
15
P15
N/A
10
40
20
16
P16
N/A
01
30
03
17
P17
Blocking CH flow temperature (
o
C)
Boiler will not fire if the CH flow temperature set point is less than this
Do not
Do not
25
note 00 = Off
adjust
adjust
. 2 5
P18
18
continued...........
. - 0 5
. 2 0
. - 0 2
. 0 0
. 8 0
. 2 5
. 1 0
INST
ALLA
TION
34
xtra
-
Installation & Servicing
INSTALLATION
Press
Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
Booster time (minutes)
00
30
00
note 00 = Off
19
P19
CH flow parallel shift
00
80
10
For use with outside temperature sensor
20
P20
N/A
Do not
Do not
20
adjust
adjust
21
P21
Maximum fan speed CH (hundreds)
F320
52
F400
52
F480 Do not
Do not
55
F560 adjust
adjust
55
P22
37 ADVANCED CONTROLS ACCESS CONT'D
. 0 0
. 1 0
. 2 0
22
. 4 8
. 0 0
. 4 8
23
24
Ignition fan speed (hundreds)
F320
35
F400
25
F480 Do not
Do not
25
F560 adjust
adjust
25
. 3 5
28
P28
P23
Maximum fan speed CH (units)
F320
00
F400
00
F480 Do not
Do not
00
F560 adjust
adjust
00
P24
Maximum fan speed DHW (hundreds)
F320
52
F400
52
F480 Do not
Do not
55
F560 adjust
adjust
55
. 0 0
25
P25
Maximum fan speed DHW (units)
F320
00
F400
00
F480 Do not
Do not
00
F560 adjust
adjust
00
. 1 2
26
P26
Minimum fan speed (hundreds)
F320
18
F400
20
F480 Do not
Do not
19
F560 adjust
adjust
17
. 1 6
27
P27
Minimum fan speed (units)
F320
00
F400
00
F480 Do not
Do not
00
F560 adjust
adjust
00
continued...........
29
P29
Fan speed during forced low time (x100rpm)
F320
20
F400
20
F480 Do not
Do not
20
F560 adjust
adjust
20
. 1 6
INST
ALLA
TION
35
xtra
-
Installation & Servicing
INSTALLATION
DHW priority time over CH (secs)
0
120
30
0 = DHW always has priority
1-120 mins
The DHW has priority over CH until priority is switched back to CH.
Press
Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
Forced low time (x 9 seconds)
Do not
Do not
6
adjust
adjust
30
P30
Slow start
31
P31
CH post pump time (minutes)
00
99
05
Note 0 = 10 seconds
Do not set below 05
. 0 5
32
P32
DHW post pump time (x 10 seconds)
00
30
11
. 0 3
33
P33
CH modulation hysteresis on (
o
C)
Do not
Do not 05
(Master)
adjust
adjust 02
(Slave)
. 0 5
34
P34
CH modulation hysteresis off (
o
C)
Do not
Do not 05
(Master)
adjust
adjust 10
(Slave)
. 0 5
35
P35
DHW modulation hysteresis on (
o
C)
Do not
Do not 03
(Master)
adjust
adjust 02
(Slave)
. 0 5
36
P36
DHW modulation hysteresis off (
o
C)
Do not
Do not 03
(Master)
adjust
adjust 10
(Slave)
. 0 5
37
P37
. 0 3
. 0 3
. 0 0
. 0 0
Blocking time DHW to CH (seconds)
0
30
05
0=switch with burner on
(x10.2 seconds)
. 0 0
. 2 5
38
39
40
41
42
43
P38
N/A
Do not
Do not
03
adjust
adjust
N/A
Do not
Do not
03
adjust
adjust
Blocking time CH (seconds)
00
30
00
Minimum off period between CH demands to reduce cycling
Blocking time DHW (seconds)
00
30
00
Minimum off period between DHW demands to reduce cycling
P39
P40
P41
P42
P43
continued...........
38 ADVANCED CONTROLS ACCESS CONT'D
TIME - Temp. differential between flow temp &
set point at which slow start ends.
0
15
10
TIME - Modulation rate in slow start X 400rpm/min
0
15
02
. 0 0
RMCI address
Do not
Do not
00
Note -01=RMCI off
adjust
adjust
44
P44
INST
ALLA
TION
36
xtra
-
Installation & Servicing
INSTALLATION
DHW type
19
x0=N/A
x1=N/A
x2=N/A
x3=N/A
x4=N/A
x5=N/A
x6=N/A
x7=N/A
x8=N/A
x9=DHW ON/OFF call for heat
0x=3 way valve normally open
1x=hot water pump
2x=3way valve normally closed
Press
Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
. 0 0
CH type
Do not
Do not
00
adjust
adjust
45
P45
. 1 3
46
P46
. - 0 1
47
P47
Manual fanspeed (for service use)
-01
100
-01
Note -1=off
00 = min fan speed
50 = mid rate
100 = max fan speed
48
49
50
51
N/A
53
Low/Off cycle
00
x0=off
x1=on
Special pump function CH/DHW
0x=CH normal pump function, DHW normal pump function
1x=CH pump off during heat request, DHW normal pump function
2x=CH pump normal function, DHW pump 5 sec on delay after
heat request
3x=CH pump off during heat request, DHW pump 5 sec on delay
after heat request
N/A
Do not
Do not
70
adjust
adjust
54
Slow start
0=CH only
0
1
1
1=CH & DHW
56
39
ADVANCED CONTROLS ACCESS CONT'D
40 INFORMATION MODE (with code)
See Frame 32.
INST
ALLA
TION
37
xtra
-
Installation & Servicing
INSTALLATION
41 FAN MODE (with code)
Press
Display
Description
Fan speed
Actual fan speed e.g. 5500rpm
F A N
4 8 0 0
42 COMMUNICATION MODE (with code)
Press
Display
Description
C O N N
In this mode the communication between the boiler control module, optional control interface.
No communication
There is only communication between the boiler control module and controls interface kit.
There is communication between all devices.
FLASHING
FLASHING
43 ERROR MODE (with code)
Press
Display
Description
In error mode the last error is shown, and the boiler status and readings at that time are available
The 1st digit flashes and shows the current step.
The last two digits show the error code.
Error code
(see Table on pages 52 and 53 for full list)
E R RO
1 3 6
FLASHING
Boiler sequence at time of error (refer to Frame 30)
2 0 0
Flow temperature T1 at time of error
Return temperature T2 at time of error
3 0 0
4 0 0
DHW temperature T3 at time of error
5 - 3 6
Heat exchanger block temperature T4 at time of error
6 - 3 6
44 RETURN TO NORMAL OPERATING MODE
Press
Display
Description
Press the reset button, or press 'MODE' several times, to return to (Stby) normal operating
mode or
if no buttons are touched the boiler will automatically reset after 15 mins.
0 2 1
INST
ALLA
TION
38
xtra
-
Installation & Servicing
INSTALLATION
46 INITIAL LIGHTING
NOTE.
MASTER MODULE LEADS THE SLAVE MODULE WITH
SYNCHRONISED FIRING
1. Check that the system has been filled and the boiler is not
air locked - air in the boiler could damage the heat
exchanger. For this reason if an automatic air vent has
been fitted it must never be off.
2. Check that all the drain cocks are closed and any valves in
the flow and return are open.
3. Check that the GAS SERVICE COCKS ARE OPEN.
4. Check the indication on the pressure gauge. If the
pressure is less than 0.8 bar the installation should be
filled up first (sealed system only).
5. Switch the electricity supply ON to both modules and check
that all the external controls are calling for heat. Check
burner switch is set to on (Master module only).
6. The Master module will commence the ignition sequence.
The circulation pump is energised, whilst operating a DHW
valve if required. The fan is run up to starting speed and
the air pressure switch activated. The fan then carries out a
pre-purge before moving to ignition speed. A spark is
started and the gas valve opens. Ignition must occur in 3
seconds and once detected the module starts operating.
7. The Slave module will now start to operate as described in
no. 6, follow the sequence to ignition and operation. After
the stabilisation period both modules modulate to achieve
the set flow temperature at a restricted ramp up rate. As
each module gets within 10
o
C of the set point it is free to
modulate at normal rate.
If after 5 attempts the module has failed to light then it will
lock out. Press the reset button to restart the ignition
sequence.
8. The gas valves are preset at the factory to nominal values.
Dependant on site installation conditions (e.g. flue length)
the module performance can vary slightly. To check the
performance, measure the CO
2
values at maximum and
minimum rates whilst adjusting the gas valves if necessary
(Refer to Frame 51).
9. Operate the boiler for 10 minutes and check the gas rate
(Table 1). You should obtain a value at least 90% of the
nominal.
10. Set all the Module parameters (Master and Slave) to
appropriate settings (refer to Frame 35).
11. Fit outer fascia panel to Slave Module and secure with 2 x
M5 screws.
12. Fit the front panel by engaging the bottom retaining lugs
and then pushing home.
Make the following checks for correct operation.
1. The correct operation of ANY secondary system controls
should be proved. Operate each control separately and
check that the main burner or circulating pump, as the case
may be, responds.
2. Water circulation system;
a. With the system HOT examine all water connections for
soundness.
b. With the system still HOT, turn off the gas, water and
electricity supplies to the boiler and drain down to
complete the flushing process.
c. Refill and vent the system, clear all air locks and again
check for water soundness.
d. Balance the system.
3. Check the condensate drain for leaks and check it is
discharging correctly.
4. Finally set the controls to the User's requirements.
Note. If optional kits are fitted then refer to the instructions
supplied with the kits.
47 GENERAL CHECKS
45 COMMISSIONING AND TESTING
A. ELECTRICAL INSTALLATION
1. Checks to ensure electrical safety should be carried out
by a competent person.
2. ALWAYS carry out the preliminary electrical system
checks, i.e. earth continuity, polarity, resistance to earth
and short circuit, using a suitable meter.
WARNING. Whilst effecting the required gas soundness test and purging air from the gas
installation, open all windows and doors, extinguish naked lights and DO NOT SMOKE.
B. GAS INSTALLATION
1. The whole of the gas installation, including the meter,
should be inspected and tested for soundness and
then purged in accordance with the recommendations
of the relevant standards listed on page 4.
In IE refer to I.S.820:2002.
INST
ALLA
TION
39
xtra
-
Installation & Servicing
SERVICING
48 HANDING OVER
ROUTINE OPERATION
Full instructions covering routine lighting and operation of the
boiler are given on the Lighting and Operation Instruction
Label located behind the lower front door.
Draw the attention of the boiler owner or his representative to
the Lighting and Operating Instruction Label. Give a practical
demonstration of the lighting and shutting down of the boiler.
Describe the function of the boiler and system controls and
show how they are adjusted and used.
Hand these Installation and Servicing Instructions/User's
Instructions and Log book to the customer and request him to
keep them in a safe place for ready reference. For IE, it is
necessary to complete a "Declaration of Conformity" to
indicate compliance to the appropriate standard.
IMPORTANT.
Point out to the owner that the boiler must have regular
maintenance and cleaning, at least annually, in order to ensure
reliable and efficient operation. Regular attention will also
prolong the life of the boiler and should preferably be
performed at the end of the heating season.
After servicing, complete the service section of the log book and
return to the owner or their representative.
Recommend that a contract for this work should be made with
the regional gas authority or a CORGI registered heating
installer. In IE servicing work must be carried out by a
competent person.
49 SAFETY
It is the law that any service work must be carried out by a
registered CORGI installer. In IE service work must be carried
out by a competent person.
WARNING. Always turn off the gas supply at the gas service
cock, and switch off and disconnect the electricity supply to
the appliance and any external controls before servicing or
replacing components.
NOTE. When the burner switch is in the off position the boiler
control module remains live.
IMPORTANT. After completing the servicing or replacement of
components always:
·
Test for gas soundness.
·
Test the burner manifold flanges for soundness. This can be
done with leak detection spray whilst operating the boiler.
The gas valve and controls must be shielded from the spray.
·
Check the water system is correctly filled and free of air.
Air in the boiler could cause damage to the heat
exchanger. For this reason if an automatic air vent is fitted
it must never be shut off.
·
Check the inner front and outer jacket panels are correctly
fitted.
·
With the system hot examine all water connections for
soundness.
·
Check the gas rate and measure the combustion CO/CO
2
content. Refer to Frame 51 for reference on how to force
the burner to maximum and minimum gas rates. The
CO/CO
2
ratio of the flue gas on each module should not
be greater than 0.004 ratio. The CO
2
values should be
correct to the figures in Table 1 on Page 2.
·
Carry out functional checks as appropriate.
50 SERVICING SCHEDULE
To ensure the continued safe and efficient operation of the
appliance it is recommended that it is checked at regular
intervals and serviced as necessary. The frequency of
servicing will depend upon the installation condition and
usage but should be carried out at least annually.
Ideal Stelrad Group does not accept any liability resulting from
the use of unauthorised parts or the repair and servicing of
appliances not carried out in accordance with the Company's
recommendations and specifications.
Note.
Some aluminium oxide build-up within the heat exchanger
assembly is quite usual with this type of condensing boiler.
Though removal and cleaning is recommended annually, the
heat exchanger, sump and condensate trap must be inspected
and cleaned after a maximum of 2 years operation.
1. Light the boiler and carry out function checks, noting any
operational faults.
2. Run the boiler for 10 minutes and then check the gas
consumption rate. Refer to Frame 51 for reference on how
to force the burner to maximum and minimum rates.
3. For correct boiler operation the CO/CO
2
ratio of the flue gas
on each module should not be greater than 0.004 ratio and
the CO
2
values should be correct to the figures in Table at
front of book. If this is the case and the gas input is at least
90% of the nominal, once compliance with the note above is
ensured, then no further action need be taken. If not proceed
to 4. Refer to Frames 52 to 58 for guidance.
4. Refer to Frame 49.
5. Remove and inspect the fan/venturi assembly. Refer to
Frame 53.
6. Remove the burner manifold and inspect the electrodes and
sightglass. Refer to Frames 54 and 61.
7. Remove and clean the burner. Refer to Frame 55.
8. Inspect the heat exchanger through the burner opening.
Optionally remove the inspection covers on the left hand side
of the heat exchanger. If there are signs of aluminium oxide
build up, spray water down the flueways taking care not to
get water on the gas valve and controls. Refer to Frame 56.
9. Remove the sump cover and scrape out any deposits. Refer
to Frame 57.
10. Clean the condensate trap. Refer to Frame 58.
11. Check that the flue terminal and air inlet are unobstructed
and that the fluing and ducting are correctly sealed.
REPEAT PROCEDURE FOR BOTH SLAVE AND MASTER
MODULES.
12. After servicing refer to Frame 49 for final safety checks.
SER
VICING
40
xtra
-
Installation & Servicing
SERVICING
51 GAS VALVE ADJUSTMENT
The boiler contains 2 Modules with individual gas valves. Both
must be adjusted.
Maximum rate adjustment
1. Switch the boiler on and operate for 10 minutes.
2. To ensure the boiler operates at maximum rate without
modulating set the fan speeds to maximum.
3. Remove the outer fascia panel on the Slave Module (see
Frame 52).
4. To set the fan speed to maximum. Press and hold in the
'mode' and '+' buttons simultaneously on the Master
Module. The display will show as the first digit
indicating the boiler is operating at maximum rate.
Repeat on the Slave Module.
5. Connect a suitable flue analyser to the flue sampling point
of the Master Module (see Frame 12).
6. Using the maximum rate adjustment screw, adjust the
master module gas valve until the CO
2
measures 9.7% ±
0.2 (nb. clockwise reduces CO
2
).
7. Connect a suitable flue analyser to the flue sampling point
of the Slave Module (see Frame 12).
8. Using the maximum rate adjustment screw, adjust the
Slave Module gas valve until the CO
2
measures 9.7% ± 0.2
(nb. clockwise reduces CO
2
).
H
L
Maximum Rate Adjustment Screw
(Firstly remove plastic cap for access)
Minimum rate adjustment
9. To ensure the boiler operates at minimum rate without
modulating, set the fan speeds to minimum.
10. To set the fan speed to minimum. Press and hold in the
'mode' and '-' buttons simultaneously on the Master
Module. The display will show as the first digit
indicating the boiler is operating at minimum rate.
Repeat on the Slave Module.
11. Connect a suitable flue analyser to the flue sampling point
of the Master Module - see Frame 12.
12. Remove the protective cap and then using the offset
adjustment screw, adjust the valve on the master module
until the CO
2
value measures 9.5% ± 0.2 (nb. anti-
clockwise reduces CO
2
level). The offset adjustment is a
lot more sensitive than the throttle adjustment.
13. Connect a suitable flue analyser to the flue sampling point
on the Slave Module (see Frame 12).
14. Remove the protective cap and then using the offset
adjustment screw, adjust the valve on the Slave Module
until the CO
2
value measures 9.5% ± 0.2 (nb. anti-
clockwise reduces CO
2
level).
15. Re-check the CO
2
level at maximum rate and repeat steps
3 to 15 if necessary.
16. Press the '+' and '-' buttons simultaneously to return to
normal operating mode.
17. Seal adjustment screw with tamper proof paint.
Note.
It is possible to switch off the CH/DHW systems if the mode and +/- buttons are not held simultaneously. Refer to Frame 30
under the heading CH/DHW Systems for guidance.
Offset Adjustment Screw
(Firstly remove plastic cap for access)
SER
VICING
41
xtra
-
Installation & Servicing
SERVICING
52 CASING REMOVAL AND ACCESS
Front Panels
1. Pull the front panel forwards at the top, lift off the
bottom retaining lugs and remove.
Control Fascia Panel (MASTER MODULE)
3. Remove the 2 screws securing the control fascia
panel. Carefully lift it slightly and lower the top
forwards allowing it to rest on the hinge lugs.
2. Loosen 3 screws on one side of the inner front panel
and undo the 3 screws from the other side. The
panel will now slide to one side for removal.
REPEAT PROCEDURE FOR SLAVE MODULE.
4. To remove completely, release the ribbon
cable from the display board, raise slightly
and withdraw.
3
4
2
Control Fascia Panel (SLAVE MODULE)
5. Remove 2 screws securing the outer fascia panel.
Lift and remove fascia.
6. Remove 2 screws securing inner fascia panel. Lift
and support panel and remove ribbon cable and
remove fascia.
Top Panel
7. Remove 2 screws from rear top panel. Lift and
remove panel
Side Panels
8. Remove 2 screws from rear and 2 screws from
front of each side panel. Lift from Frame and
remove.
8
SER
VICING
42
xtra
-
Installation & Servicing
SERVICING
53 REMOVAL OF FAN / VENTURI INSPECTION
54 REMOVAL OF BURNER MANIFOLD
1. Refer to Frame 49.
2. Refer to Frame 53 for removal of fan/venturi
assembly.
3. Disconnect the ignition and earth lead from the
electrodes.
4. Whilst providing temporary support for the burner
manifold remove the 4 retaining nuts.
5. Withdraw the burner manifold from the boiler taking
care not to damage the electrodes.
6. Re-assemble in reverse order, replacing any seals/
gaskets which show signs of wear. The nyloc nuts
should be renewed. Ensure the short earth lead is
secured under the top LH nut.
REPEAT PROCEDURE FOR SLAVE MODULE.
7. Refer to Frame 49 for final safety checks.
4
3
3
1. Refer to Frame 49.
2. Remove the jacket front, inner front, jacket right, jacket
top and controls fascia panels. (Refer to Frame 52).
3. Disconnect the electrical connections from the fan.
4. Remove 4 bolts securing inlet air pipe/silencer to the
venturi taking care to retain O ring seal.
5. Whilst providing temporary support for the gas valve
remove the 4 screws securing the gas valve to the
venturi
6. Remove sensing pipe from venturi.
7. Whilst providing temporary support for the fan/venturi
remove the 4 fasteners securing the fan outlet
connection. Lift the fan/venturi assembly clear of the
boiler taking care to retain the fan outlet gasket.
8. Remove the 4 screws securing the venturi to the fan
inlet, taking care to retain the O ring.
9. Re-assemble in reverse order replacing any seals/
gaskets which show signs of wear.
REPEAT PROCEDURE FOR SLAVE MODULE.
10. Refer to Frame 49 for final safety checks.
6
SER
VICING
43
xtra
-
Installation & Servicing
SERVICING
55 REMOVAL / CLEANING OF BURNER
1. Refer to Frame 49.
2. Refer to Frame 54 for removal of burner
manifold.
3. Remove the gasket from the 4 studs.
4. Draw the burner out of the heat exchanger.
5. The burner can be cleaned on the inside
surface using a soft brush and/or vacuum.
The metal fibre outer surface must not be
brushed. If the burner is showing signs of
damage it must be replaced.
6. Re-assemble in reverse order replacing
any seals/gaskets which show signs of
wear. When re-fitting the burner there are 2
small lugs cast into the end of the
combustion chamber which support the
end of the burner.
REPEAT PROCEDURE FOR SLAVE MODULE.
7. Refer to Frame 49 for final safety checks.
56 REMOVAL OF HEAT EXCHANGER INSPECTION COVERS
1. Refer to Frame 49.
2. Remove the jacket front, inner front,
controls fascia, top and left side
panels. (Refer to Frame 52).
3. Remove the 6 securing nuts on each
inspection cover and withdraw, taking
care to retain the gasket.
4. Re-assemble in reverse order
replacing the gasket if it is showing
signs of wear.
5. Refer to Frame 49 for final safety
checks.
3
4
Inspection cover
SER
VICING
44
xtra
-
Installation & Servicing
SERVICING
57 REMOVAL OF SUMP COVER
1. Refer to Frame 49.
2. Remove the jacket front and inner front
panels. (Refer to Frame 52).
3. Remove the 6 nuts and withdraw the sump
cover plate taking care to retain the gasket.
4. Scrape out any deposits within the sump.
5. Re-assemble in reverse order replacing the
sump cover plate gasket if it is showing
signs of wear.
REPEAT PROCEDURE FOR SLAVE MODULE.
6. Refer to Frame 49 for final safety checks.
3
58 CLEANING CONDENSATE TRAP
1. Refer to Frame 49.
2. Remove the jacket front, inner front, controls fascia, top
and side panels. (Refer to Frame 52).
3. Place a container beneath the condensate trap to
collect the condensate contained within.
4. Remove bottom nut/plug from the condensate trap
whilst collecting the condensate which will drain out.
5. Withdraw the cartridge and ball from within the
condensate trap. Thoroughly clean the cartridge and
ball by flushing with water.
6. If deposits are visible in the condensate trap body, it
can be removed by unscrewing the inlet and outlet
nuts. Thoroughly flush the body with water.
7. Re-assemble in reverse order, replacing the
condensate trap if there are signs of wear to any seals
or the ball.
REPEAT PROCEDURE FOR SLAVE MODULE.
8. Refer to Frame 49 for final safety checks.
4
5
6
SER
VICING
45
xtra
-
Installation & Servicing
SERVICING
59 GAS VALVE REPLACEMENT
1. Refer to Frame 49.
2. Remove the jacket front, inner front and control
fascia panels. (Refer to Frame 52).
3. Remove the 4 screws securing the controls
fascia support bracket and withdraw.
4. Disconnect the electrical connections from the
gas valve.
5. Release the securing clip and disconnect the
pressure sensing tube from the gas valve.
6. Whilst providing temporary support for the inlet
gas pipe, remove the 4 screws securing the
inlet flange.
7. Whilst providing temporary support for the gas
valve, remove the 4 screws securing the gas
valve outlet.
8. Withdraw the gas valve taking care to retain the
inlet and outlet O rings.
9. Re-assemble in reverse order. Re-secure the
clip over the pressure sensing tube using
pliers to apply the grip. Replace gas valve inlet/
outlet O rings if showing signs of wear.
10. Refer to instruction sheet with spare gas valve
for correct setting procedure.
11. Refer to Frame 49 for final safety checks.
60 AIR PRESSURE SWITCH REPLACEMENT
1. Refer to Frame 49.
2. Remove the jacket front and inner front panels. (Refer
to Frame 52).
3. Remove the 2 electrical connections from the air
pressure switch (no polarity) which is located at the top
rear of the main control panel.
4. Release the securing clips and disconnect the
pressure sensing tubes.
5. The air pressure switch can now be unclipped from its
supporting cradle.
6. Re-assemble in reverse order. Connect the sensing
tube from the T-piece to P1 and the sensing tube from
the gas valve outlet elbow to P2.
7. Refer to Frame 49 for final safety checks.
Pressure
sensing
tubes
6
7
5
4
Left and right terminals
(no polarity)
SER
VICING
46
xtra
-
Installation & Servicing
SERVICING
61 IGNITION/DETECTION ELECTRODE TESTING/REPLACEMENT
1. Refer to Frame 49.
2. Remove the jacket front and inner front panels. Refer to
Frame 52.
3. It is possible to measure the ionisation current with a
voltmeter set at 0-10VDC. (0-10VDC = 0-10 micro amps
ionisation current).
4. With the boiler running, connect a meter between the
terminal marked and earth.
5. A reading below 3V indicates a fault.
6. To replace the ignition/detection electrode remove the
controls fascia, pull off the HT and earth leads from the
spark/detection electrode.
7. Remove the 2 nuts and washers.
8. Check the electrode gap is 4.0mm.
9. Replace the electrode using the new gasket provided.
10. Re-assemble in reverse order.
11. Refer to Frame 49 for final safety checks.
62 PRESSURE GAUGE REPLACEMENT (MASTER BOILER ONLY)
1. Refer to Frame 49, then:
2. Remove the jacket front, control fascia,
top, and right side panels. (Refer to
Frame 52).
3. Unscrew the nut retaining the capillary
from the self sealing fitting. (Refer to
'A' in Frame 63).
4. Compress the retaining lugs and
push forwards to remove the gauge
from the bracket.
5. Replace the pressure gauge.
6. Reassemble in reverse order.
7. Refer to Frame 49 for final safety
checks.
7
6
SER
VICING
47
xtra
-
Installation & Servicing
SERVICING
63 WATER PRESSURE SWITCH REPLACEMENT
1. Refer to Frame 49.
2. Remove the jacket front, control fascia, top
and side panel. (Refer to Frame 52).
3. Isolate water circuit and drain boiler.
4. Pull off the electrical connections (no
polarity) from the pressure switch.
5. Unscrew the water pressure switch
6. Fit the new water pressure switch.
7. Re-assemble in reverse order.
8. Re-fill the system ensuring all the air in the
heat exchanger is vented.
9. Refer to Frame 49 for final safety checks.
4
A
64 FLOW / RETURN / HEAT EXCHANGER / FLUE THERMISTOR REPLACEMENT
1. Refer to Frame 49.
2. Remove the jacket panels as appropriate.
(Refer to Frame 52).
3. Isolate water circuit and drain boiler.
4. Pull off the electrical connections from the
thermistor.
5. Unscrew the thermistor.
6. Fit the new thermistor with built in `O` ring
seal. Do not overtighten.
7. Re-assemble in reverse order.
8. Refill the system ensuring all the air in the
heat exchanger is vented.
9. Refer to Frame 49 for final safety checks.
4
5
Heat Exchanger Thermistor Shown
Return thermistor
SER
VICING
48
xtra
-
Installation & Servicing
SERVICING
1. Refer to Frame 49.
2. Remove the jacket front, inner front, controls
fascia and top panels. (Refer to Frame 52).
3. Disconnect the transformer connection from the
boiler control module. (Refer to 'A' in Frame 66).
4. Remove the 2 screws on the left side of the
transformer whilst supporting its weight.
5. Disengage the transformer from the 2 retaining
lugs by moving it to the left. Remove from boiler.
6. Re-assemble in reverse order.
7. Refer to Frame 49 for final safety checks.
65 TRANSFORMER REPLACEMENT
4
66 CONTROL MODULE REPLACEMENT
1. Refer to Frame 49.
2. Remove the front and inner front
panels. (Refer to Frame 52).
3. Disconnect the electrical
connections from the module.
4. Remove the 4 screws securing the
control module to the main control
panel.
5. Re-assemble in reverse order.
6. Refer to Frame 49 for final safety
checks.
A
3
4
3
3
im8254
Note. Control module must be fitted with clip-in Opentherm
interface device.
ima5407
Opentherm clip-in
interface device.
SER
VICING
49
xtra
-
Installation & Servicing
SERVICING
67 OT CENTER REPLACEMENT
1. Refer to Frame 49.
2. Remove the front and inner front
panels. Lower the controls fascia.
(Refer to Frame 52).
3. Disconnect the electrical connection
from the display board.
4. Undo and remove the 4 plastic nuts.
5. Lift the display board from the 4 studs.
6. Fit the new display board and re-
assemble in reverse order.
7. Refer to Frame 49 for final safety
checks.
4
3
68 DISPLAY BOARD REPLACEMENT
1. Refer to Frame 49.
2. Remove the front and inner front panels
(Refer to Frame 52).
3. Squeeze tab and pull to remove
connection lead.
4. Firmly pull up and down on module to
remove.
5. Replace with new module after setting
switches 'S1' and 'S2' according to
Frame 22.
6. Plug in communication lead to either
common socket.
7. Re-assemble in reverse order ensuring
OT Center module is pushed fully home
to its backing plate.
8. Refer to Frame 49 for final safety
checks.
3
4
SER
VICING
50
xtra
-
Installation & Servicing
SERVICING
69 MOTORISED DAMPER MOTOR REPLACEMENT
70 AIR DAMPER REPLACEMENT
1. Refer to Frame 49.
2. Loosen 2 securing screws from motor
cover and remove cover.
3. Disconnect electrical connections.
4. Remove 2 x M5 nuts and washers
located behind mounting plate and
remove motor.
5. Replace with new motor.
6. Re-assemble and re-wire in reverse
order.
7. Refer to Frame 49 for final safety
checks.
2
3
1. Refer to Frame 49.
2. Remove front and inner front panels (Refer to
Frame 52).
3. If replacing Slave Module air damper first remove
boiler LHS panel (Refer to Frame 52).
4. Remove 4 x M6 nuts, bolts and washers locating
air duct flange to venturi assembly on the module
that the air damper is to be removed.
5. Remove 2 x M5 nuts retaining air duct lower
support bracket on module that the air damper is
to be removed. Remove bracket.
6. Pull air duct assembly forward and pull air duct
flanges out of automatic air duct inlet and outlet
connections.
Inspection and Replacement:
7. Check butterfly flaps within air damper move
freely without sticking. Remove any dust/debris
with a soft brush. Check integrity of O-ring seals
within flange connectors.
8. Re-fit damper ensuring it is orientated such that
the butterfly flaps open inwards towards the front
of the boiler module. Also ensure inspection
window faces uppermost.
9. Re-fit ductwork in reverse order to disassembly.
Check venturi flange O-ring seal is in good
condition and correctly located in its groove
during assembly.
10. Refer to Frame 49 for final safety checks.
4
9
5
SER
VICING
51
xtra
-
Installation & Servicing
FAULT FINDING
FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING
Before attempting any electrical fault finding ALWAYS carry out
the preliminary electrical system checks as detailed in the
Instructions for the British Gas Multimeter or other similar
commercially available meter.
The preliminary electrical system checks are the FIRST
electrical checks to be carried out during a fault finding
procedure.
On completion of any service/fault finding task which has
required the breaking and remaking of electrical connections
the following checks MUST be repeated:
a
Earth continuity
b
Polarity
c
Resistance to earth
Detailed instructions on the replacement of faulty components
are contained in the 'Servicing' section of these Installation &
Servicing Instructions.
Before carrying out Fault Finding ensure that all external controls
are calling for heat. There should be 230V ± 10% available at the
control box connection. ALSO CHECK BOTH OT CENTERS ARE
CORRECTLY CONFIGURED (SEE FRAME 22).
The boiler control module has replaceable fuses protecting the
230V and 24V circuits. A common reason for the 230V fuse to
blow would be if the pump connected to the boiler was drawing
more than 1 amp.
If the 230V fuse has blown, the display will be blank. Check for
short circuits and pump loads before replacing the fuse.
OT CENTER FAULT FINDING
1. Top LED (Red)
Regular flashing indicates correct communication with OT Center
and electrical control module located to the right of the OT Center.
If regular flashing is not evident check:
a. Integrity of wiring between OT Center and electrical control
module.
b. Correct communication with electrical control module. (Refer to
Frame 42).
c. Correct fitment of Opentherm clip-in device. (Refer to Frame 66).
2. Middle LED (Yellow)
This indicates failure of boiler. If yellow LED is showing check fault
finding codes.
3. Bottom LED (Green)
Regular flashing indicates correct Center communication with OT
Center and connecting OT Center on adjoining module. If regular
flashing is not evident check correct fitment of both OT Centers and
adjoining communications lead. (Refer to Frame 23).
1
2
3
52
xtra
-
Installation & Servicing
FAULT FINDING
FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING
Code
Description
Action
FUSE 24V circuit dead
Check Transformer & replace if necessary
Check 24V fuse on Control Board
If 24V fuse blown check for short circuits before replacing
00
Flame Error (signal present when there should not be)
Replace Control Module
02
No ignition after restart
Check inlet gas pressure
Check wiring to ignition/detection electrode
Check condition of ignition/detection electrode
If above OK replace control module
03
Internal Failure
Check gas valve wiring
Check gas valve solenoids not open circuit
Check general wiring harness and connections
If all OK. replace control module
04
Non-volatile lockout
Press reset
05
Internal failure
Check wiring harness & connections
If wiring OK replace control module
06
Internal failure
Check wiring harness & connections
If wiring OK replace control module
07
Internal failure
Check wiring harness & connections
If wiring OK replace control module
08
Air Pressure Switch did not close
Check motorised damper operating
Check air damper is opening
Check flue for blockage
Check/clean burner
Check Air Pressure Switch sensing pipes condition
Check fan speed
Check air Pressure Switch & replace if necessary
11
EPROM read/write error
Press reset. If fault keeps re-occuring Replace Control Module.
12
24V fuse blown
Check 24V fuse on Control Board
If 24V fuse blown check for short circuits before replacing
Check gas valve leads & solenoids for short circuit
13
Internal failure
Check wiring harness & connections
If wiring OK replace control module
14
Internal failure
Check wiring harness & connections
If wiring OK replace control module
15
Internal failure
Check wiring harness & connections
If wiring OK replace control module
16
Internal failure
Check wiring harness & connections
If wiring OK replace control module
17
Internal failure
Check wiring harness & connections
If wiring OK replace control module
18
Flow temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
19
Return temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
25
Flow temperature rise too fast
Check no air in system or boiler
Check adequate flow of water through boiler
28
No tacho signal from fan
Check wiring to fan
If wiring OK replace fan
MASTER AND SLAVE BOILER CONTROL MODULE ERROR CODES
53
xtra
-
Installation & Servicing
FAULT FINDING
FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING
Code
Description
Action
29
Incorrect tacho signal from fan
Check wiring to fan. If wiring OK replace fan.
30
Flow/return temperature differential too high
Check no air in system or boiler
Check adequate flow of water through boiler
31
Flow thermistor short circuit
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Replace thermistor
32
Return thermistor short circuit
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Replace thermistor
33
Tank sensor short circuit
Not fitted check parameter 46 settings
35
Flue thermistor short circuit
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Replace thermistor
36
Flow thermistor open circuit
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
37
Return thermistor open circuit
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
38
Tank sensor open circuit
Not fitted check parameter 46 settings
40
Flue thermistor open circuit
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
44
Internal Failure
Check wiring harness & connections
If wiring OK replace control module
52
Flue gas temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
60
Error reading parameters
Press reset. If fault keeps re-occuring replace control module.
61
Air pressure switch closed when it should be open
Check for blockages in air pressure switch sensing pipes
Check air pressure switch and replace if necessary
107
Heat exchanger thermistor short circuit
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
108
Heat exchanger thermistor open circuit
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
109
Heat exchanger temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
110
Heat exchanger temperature too low
Check no air in system or boiler
Check adequate flow of water through boiler
111
Heat exchanger to return temperature differential too high
Check no air in system or boiler
Check adequate flow of water through boiler
112
Heat exchanger temperature rise too fast
Check no air in system or boiler
Check adequate flow of water through boiler
113
No valid mains frequency detected
Check power supply to boiler
114
Invalid or conflicting cascade address
Press reset. If fault keeps re-occuring replace control module.
115
Internal error
Check wiring harness & connections
If wiring OK replace control module
MASTER AND SLAVE BOILER CONTROL MODULE ERROR CODES CONTINUED
54
xtra
-
Installation & Servicing
FAULT FINDING
FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING
Code
Description
Action
08
Air Pressure Switch did not close
Check motorised damper operating
Check air damper is opening
Check flue for blockage
Check/clean burner
Check Air Pressure Switch sensing pipes
condition
Check fan speed
Check air Pressure Switch & replace if
necessary
18
Flow temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
19
Return temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
24
Return temperature > Flow temperature for excessive time
Check no air in system or boiler
Check adequate flow of water through boiler
25
Flow temperature rise too fast
Check no air in system or boiler
Check adequate flow of water through boiler
28
No tacho signal from fan
Check wiring to fan
If wiring OK replace fan
29
Incorrect tacho signal from fan
Check wiring to fan. If wiring OK replace fan.
30
Flow/return temperature differential too high
Check no air in system or boiler
Check adequate flow of water through boiler
33
Tank sensor short circuit
Not fitted check parameter 46 settings
35
Flue thermistor short circuit
Check wiring
Disconnect terminals from thermistor &
confirm short circuit using meter
Replace thermistor
38
Tank sensor open circuit
Not fitted check parameter 46 settings
40
Flue thermistor open circuit
Check wiring
Disconnect terminals from
thermistor & confirm open circuit using meter
Replace thermistor
43
Parameter values in EEPROM values out of range
Replace control module.
52
Flue gas temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
65
Fanspeed during start not within the dead band
Check wiring to fan. If wiring OK replace fan.
109
Heat exchanger temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
116
Mains frequency deviation > 1.5Hz or processor oscillator error
If mains supply frequency OK replace control module.
118
Flame current lost during burner on
Check wiring
Check condition of ignition/detection
electrode & replace if necessary
MASTER AND SLAVE BOILER CONTROL MODULE BLOCKING CODES
71 TECHNICAL CHARACTERISTICS - TEMPERATURE SENSORS
The table below gives the relationship between temperature and resistance for the following sensors; flow thermistor, return
thermistor, flue thermistor, heat exchanger thermistor, outside temperature sensor and DHW tank sensor.
Temperature in
o
C
Resistance in ohm
Temperature in
o
C
Resistance in ohm
10
22,800
60
32,250
20
14,700
70
2,340
30
9,800
80
1,710
40
6,650
90
1,260
50
4,610
100
950
55
xtra
-
Installation & Servicing
SHORT LIST OF PARTS
The following are parts commonly required as replacements,
due to damage or expendability.
A full list of spares is held by Ideal Stelrad Group distributors
and merchants.
Their failure or absence will affect the safety and/or
performance of this appliance.
When ordering spare parts please quote:
1. Boiler model
2. Boiler serial no. (refer to the data plate on boiler*)
3. Boiler P.I. No. (refer to the data plate on boiler*)
4. Description
5. Quantity
6. Part no.
* Note. Data plate, (refer to Frame 7), can be accessed by
removing front panel, (refer to Frame 52).
Key No.
Description
Qty.
Part No.
Per Module
3
Pressure Gauge
1
172 669
8
Fan
1
174 376
9
Gas Valve
F320
1
174 378
F400-F560
1
174 379
12
Control Module
F320 Master
1
174 667
F320 Slave
1
174 668
F400 Master
1
174 669
F400 Slave
1
174 670
F480 Master
1
174 671
F480 Slave
1
174 672
F560 Master
1
174 673
F560 Slave
1
174 674
13
Display Board
1
172 660
14
Alarm / Boiler Run Relays Board
1
174 391
21
Water Pressure Switch
1
172 667
26
Burner
F320
1
174 407
F400
1
174 408
F480
1
174 409
F560
1
174 410
28
Gasket - Burner Manifold
1
174 412
29
Gasket - Fan
1
174 413
31
Thermistor (temperature sensor)
4
174 415
33
Air Pressure Switch
1
174 418
36
Transformer
1
172 657
37
Relay
2
172 658
47
Ignition / Detection Electrode
1
174 432
51
Control Module Fuses
1
172 663
52
Mains Fuse
1
174 449
54
OT Center
1
174 679
59
Flue Damper Actuator
1
174 686
When replacing any part on this appliance use only spare parts that you can be assured conform to the safety and performance
specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal boilers.
Note. Each spares kit ordered contains only one replacement part.
56
xtra
-
Installation & Servicing
SHORT LIST OF PARTS
72 SHORT LIST
21
37
31
im8475b
47
51 & 52
54
59
36
12
3
13
14
9
33
8
28
29
26
57
xtra
-
Installation & Servicing
NOTES
58
xtra
-
Installation & Servicing
NOTES
59
xtra
-
Installation & Servicing
NOTES
Ideal Boilers, P.O. Box 103, National Ave, Kingston upon Hull, HU5
4JN. Telephone: 01482 492 251 Fax: 01482 448 858. Registration
No. London 322 137.
Technical Training
Ideal Stelrad Group pursues a policy of continuing improvement
in the design and performance of its products. The right is
therefore reserved to vary specification without notice.
The Ideal Boilers Technical Training Centre offers a series of first class training courses for domestic, commercial and
industrial heating installers, engineers and system specifiers. For details of courses please ring: .......... 01482 498 432
Ideal Installer/Technical Helpline: 01482 498 376
www.idealboilers.com