installation and
servicing
Your Ideal installation and servicing guide
See reverse for users guide
ENGINEERED FOR PEACE OF MIND
When replacing any part on this appliance, use only spare parts that you can be
assured conform to the safety and performance specification that we require. Do not
use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
plus
III
Models F95, F145, F190
& F235, F285, F330
plus
III
March 2009 UIN 204111 A01
back
2
CONTENTS
1
GENERAL INFORMATION ..................................................................................................................................................................................
3
1.1
Symbols used in this guide ...........................................................................................................................................................................
3
1.2
Correct use of the appliance ........................................................................................................................................................................
3
1.3
Water treatment .............................................................................................................................................................................................
3
1.4 I
nformation to be passed over to the person in charge of the appliance ..................................................................................................
3
1.5
Safety warnings .............................................................................................................................................................................................
4
1.6
Data badge ....................................................................................................................................................................................................
5
1.7
General warnings ..........................................................................................................................................................................................
6
2
TECHNICAL FEATURES AND DIMENSIONS ...................................................................................................................................................
7
2.1
Technical features .........................................................................................................................................................................................
7
2.2
Dimensions ....................................................................................................................................................................................................
8
2.3
Performance data .........................................................................................................................................................................................
9
2.4 RHS view showing main components ................................................................................................................................................10
3
INSTRUCTIONS FOR THE INSTALLER ..........................................................................................................................................................
11
3.1
General warnings .......................................................................................................................................................................................
11
3.2
Installation standards ................................................................................................................................................................................
12
3.3
Packaging ...................................................................................................................................................................................................
13
3.4
Boiler location in a boiler room .................................................................................................................................................................
13
3.5
Installation on existing systems ................................................................................................................................................................
14
3.6 Boiler connection ....................................................................................................................................................................................... 15
3.7
Gas connection ..........................................................................................................................................................................................
16
3.8
Connection return and flow system pipes ................................................................................................................................................
17
3.9
Primary circuit pump or boiler pump
......................................................................................................................................................... 18
3.10
Sealed system requirements ....................................................................................................................................................................
19
3.11
Wiring diagram for additional safety devices ........................................................................................................................................... 20
3.12 Safety pressure relief valve ..................................................................................................................................................................... 20
3.13 Mixing header filter .................................................................................................................................................................................... 21
3.1
4 Boiler freeze protection ............................................................................................................................................................................. 22
3.1
5 Mixing header ............................................................................................................................................................................................ 22
3.1
6 Condensing drain ...................................................................................................................................................................................... 23
3.1
7 Water treatment ......................................................................................................................................................................................... 24
3.1
8 Flue chimney connection .......................................................................................................................................................................... 25
3.
19 Room sealed version ................................................................................................................................................................................. 25
3.2
0 Operation ................................................................................................................................................................................................... 27
3.2
1 Electrical connections ............................................................................................................................................................................... 29
3.2
2 Functional wiring diagram ......................................................................................................................................................................... 30
3.2
3 Wiring diagram for connection and managing ......................................................................................................................................... 32
3.2
4 Installation examples (functional wiring and connections description).................................................................................................. 34
Connections for boilers in cascade, controlled by outer compensators ............................................................................................... 36
3.2
5 Cascade manager BCM ........................................................................................................................................................................... 38
3.2
6 Configuration with a modulating pump ..................................................................................................................................................... 42
3.2
7 Filling the system ....................................................................................................................................................................................... 43
3.2
8 Burner adjustment .....................................................................................................................................................................................
44
3.
29
Emergency functions ...............................................................................................................................................................................
45
3.3
0
Lighting and shutting down procedures ...................................................................................................................................................
46
4
SERVICING SCHEDULE ..................................................................................................................................................................................
47
Warning: this manual contains instructions to be used exclusively by the
installer and/or a competent person in accordance with the current laws in
force.
The end user MUST not make any alterations to the boiler.
Failure to follow the instructions indicated in this manual, which is supplied
with the boiler, could cause injury to persons, animals or damage to property.
Ideal Boilers shall not be held liable for any injury and/or damage.
back
3
General Information
1.1 - SYMBOLS USED IN THIS GUIDE
When reading this guide particular care has to be given to the parts marked with the followings symbols:
1.2 - CORRECT USE OF THE APPLIANCE
The Imax Plus appliance has been designed utilizing today's heating technology and in compliance with the
current safety regulations.However, following an improper use, dangers could arise for the safety and life
of the user or of other people, or damage could be caused to the appliance or other objects.The appliance
is designed to be used in pumped hot water central heating systems. Any other use of this appliance will
be considered improper. Ideal Boilers declines any responsibility for any damage or injuries caused
by an improper use; in this case the risk is completely at the user's responsibility. In order to use the
appliance according to the scopes it was designed for it is essential to carefully follow the instructions
indicated in this guide.
1.3 - WATER TREATMENT
·
The Imax Plus III boiler has an Aluminium alloy heat exchanger.
· Ideal Boilers strongly recommends the system is thoroughly cleaned prior to the use of a suitable inhibitor.
For further details see section 3.17.
1.4 - INFORMATION TO BE HANDED OVER TO THE USER
1
GENERAL INFORMATION
NOTE!
Suggestions for the
user
WARNING!
Indicates a potentially dangerous
situation for the product and the
environment
DANGER!
Indicates serious danger
for your personal safety
and for your life
The user has to be instructed on the use and operation of his heating system, in particular:
·
Hand over these instructions to the end user, together with any other literature regarding this appliance, placed
inside the envelope contained in the packaging. The user has to keep these documents in a safe place in
order to always have them at hand for future reference.
·
Inform the user on the importance of air vents and of the flue outlet system, stressing the fact that is absolutely
forbidden to make any alterations to the boiler.
·
Inform the user how to check the system's water pressure as well as informing him how to restore the correct
pressure.
·
Explain the function of time and temperature controls, thermostats, heating controls and radiators, to ensure
the greatest possible fuel economy.
·
Remind the user that the appliance should be serviced annually by a Gas Safe Registered Engineer or in IE
by a competent person.
·
If the appliance is sold or transferred to another owner or if the present user moves home and leaves the
appliance installed, ensure yourself that the manual always follows the appliance so that it can be consulted by
the new owner and/or installer.
Failure to follow the instructions indicated in this guide, which is supplied with the boiler, could cause
injury to persons, animals or damage to property. The manufacturer shall not be held liable for any such
injury and/or damage.
back
4
General Information
WARNING!
The installation, adjustment, and servicing of this appliance must be carried out by a competent person
and installed in accordance with the current standards and regulations. Failure to correctly install this
appliance could cause injury to persons, animals or damage to property. The manufacturer shall not be
held liable for any injury and/or damage.
DANGER!
Servicing or repairs of the appliance must be carried out by a Gas Safe Registered Engineer or in IE by a
competent person. Ideal Boilers recommends drawing up a service contract. Bad or irregular servicing could
compromise the safe operation of the appliance, and could cause injury to persons, animals or damage to property
for which Ideal Boilers shall not be held liable.
Modifications to parts connected to the appliance
Do not carry out any modifications to the following parts:
-
the boiler
-
to the gas, air, water supply pipes and electrical current
-
to the flue pipe, safety relief valve and its drainage pipe
-
to the constructive components which influence the appliance's safe operation
WARNING!
When tightening or loosening the screw pipe connections, use only adequate fork spanners.
The improper use and/or the use of inadequate equipment can cause damage (for example water or gas
leakages).
Smell of gas
If you smell gas follow these safety indications:
-
Do not turn on or off electrical switches
-
Do no smoke
-
Do not use the telephone
-
Close the main gas tap
-
Open all windows and doors where the gas leakage has occurred
-
Inform the gas society or a company specialized in installing and servicing heating systems
Explosive and easily inflammable substances
Do not use or leave explosive or easily inflammable material (as for example: petrol, paint, paper) in the room
where the appliance has been installed.
1.5 -
SAFETY WARNINGS
WARNINGS
The boiler has to be installed in such way as to avoid,
under the expected operation conditions, the freezing of the water and
to prevent the control devices being exposed to a temperature
lower than -15°C and higher than 40°C.
The boiler has to be protected against environmental variations with:
- The insulation of the hydraulic pipelines and the condensate evacuation
- The adoption of specific antifreeze products in the C.H. installation.
back
5
General Information
1.6 - DATA PLATE
CE Marking
The CE marking documents that the boilers satisfy:
- The essential requirements of the Directive regarding gas
appliances (Directive 90/396/CEE)
- The essential requirements of the Directive regarding
electromagnetic compatibility (Directive 89/336/CEE)
- The essential requirements of the Efficiency Directive
(Directive 92/42/CEE)
- The essential requirements of the low voltage Directive
(Directive 73/23/CEE)
2
3
9
24
28
25
23
21
26
27
19
17
15
16
12
13
10
8
5
NOx Class
G.C. No.
Boiler Code
22
20
18
14
11
7
4
1
T. max °C
T. max °C
kg/h
m³/h
Flow rate (15°C - 1013 mbar)
Appliance type
Nom. Heat Input kW
Model:
Serial Nr.
Category
Nominal Output kW
Gas Type Supply Press.
G20 (Natural) 20 mbar
G31 (Propane) 37 mbar
Boiler to be installed with a gouverned meter.
Serial Letter Code
Specific flow rate D l/min
C.H. system : Max press. PMS bar
D.H.W. system: Max press. PMW bar
Electrical supply: W:
P.I.N. Code
Ideal Boilers Ltd.
Po Box 103, National Avenue
Hull, HU5 4JN
Manufacture date
Country of destination
1 = P.I.N. code
2 = Boiler type
3 = Model
4 = Serial Nr.
5 = Manufacture date
6 = Country of destination
7 = Gas category
8 = Appliance type
9 = Nominal heat output
10 = Nominal heat input
11 = Adjusted for gas type X
12 = Gas flow rate (min)
13 = Gas flow rate (max)
14 = Adjusted for gas type X
15 = Gas flow rate (min)
16 = Gas flow rate (max)
17 = Boiler code
18 = Serial letter code
19 = Gas Council No.
20 = Specific flow rate
21 = NOx class
22 = C.H. system max press PMS
23 = C.H. flow temp (max)
24 = Not applicable
25 = Not applicable
26 = Electrical supply
27 = Maximum absorbed power
28 = Protection rating
29 = CE no.
6
back
6
General Information
SAFETY
Current Gas Safety (Installation and Use) Regulations or rules
in force.It is the law the that all gas appliances are installed
and serviced by a Gas Safe Registered Engineer, or in IE, by a
competent person, in accordance with the regulations below.
Failure to install appliances correctly could lead to prosecution.
It is in your own interest, and that of safety, to ensure the law is
complied with.
The installation of the boiler MUST also be in accordance with
the latest I.E.E. (BS7671) Wiring Regulations, local buildings
regulations, bye-laws of the local water authority, the building
regulations and the Building Standards (Scotland) and any
relevant requirements of the local authority.
Detailed recommendations are contained in the following codes
of practice:
BS 5854 Flues and Flue Structures in Buildings.
BS.6644 Installation of gas fired hot water boilers of
rated inputs between 70kW and 1.8MW (net)
(2nd and 3rd family gases).
BS.6880 Low temperature hot water heating systems of
output greater than 45kW.
Part 1 Fundamental and design considerations.
Part 2 Selection of equipment.
Part 3 Installation, commissioning andmaintenance.
73/23 EECLow Voltage Directive (Relevant Standard is
EN60335.1).
89/336 EEC Electro Magnetic Compatibility Directive.
IGE/UP/1 Soundness testing and purging of industrial
and commercial gas installations.
IGE/UP/2 Gas installation pipework, boosters and
compressors on industrial and commercial
premises.
IGE/UP/10 Installation of gas appliances in industrial and
commercial premises.
1.7 - GENERAL WARNINGS
This instruction manual is an integral and indispensable part
of the product and must be retained by the person in charge
of the appliance.
Please read carefully the instructions contained in this manual
as they provide important indications regarding the safe
installation, use and servicing of this appliance.
Keep this manual in a safe place for future reference.
The installation and servicing must be carried out in
accordance with the regulations in force according to the
manufacturer's instructions and by a Gas Safe Registered
Engineer or, in IE, by a competent person.
Bad or irregular servicing could compromise the safe operation
of the appliance, and could cause injury to persons, animals
or damage to property. The manufacturer shall not be held
liable for any such injury and/or damage.
Before carrying out any cleaning or servicing turn off the
electrical supply to the boiler by means of the ON/OFF switch
and/or by means of the appropriate shutdown devices.
Do not obstruct the intake/outlet terminal ducts.
In the event of failure and/or faulty functioning of the appliance,
switch off the boiler. Do not attempt to make any repairs: contact
qualified technicians.
Any repairs must be carried out a Gas Safe Registered
Engineer or, in IE, by a competent person using only
original spare parts.
Non-observance of the above requirement may jeopardize
the safety of the appliance.
To guarantee the efficiency and correct functioning of the
appliance the boiler should be serviced annually by a
qualified person.
If the boiler remains unused for long periods, ensure that any
dangerous parts are rendered innocuous.
Only original accessories must be used for all appliances
supplied with optionals or kits (including electrical ones).
This appliance must be used only for the purposes for which it
has been expressively designed. Any other use shall be
considered incorrect and therefore dangerous.
back
7
Technical features and dimensions
2.1 - TECHNICAL FEATURES
·
Imax Plus is a compact, gas fired, Low NO
x
, condensing
boiler, made up
of one sectional boiler body,
This boiler body consists of two or more modules (from 2 to
7), which cannot be separated from each other, being
under the same protecting casing, and are set to operate
separately or in cascade. These modules are connected to
a single flue exhaust manifold and are controlled by a
single microprocessor, which manages completely the
temperatures from the point of view of both operation and
safety.
· Efficiency at full load with temperature 30/50°C = 101%.
At part load (30% of the nominal) with 30°C return
temperature = 106.8%.
· Each module is composed of a combustion chamber,
metallic fiber pre-mix burner, modulating fan, gas valve,
ignition electrode, flame detection, NTC sensor for
management control (BMM), local temperature control
and safety thermostat.
· Each single boiler is equipped with NTC sensors for global
temperature control on the flow and return manifolds.
· Integral, non allergic, synthetic wool insulation.
· Fully pre-mixed, radiating, modulating, metallic sponge
burner,
automatic no return diaphragm for separation from
combustion chamber.
· Combustion air intake system from boiler house (type B 23
appliances) or directly from outside the boiler house, via
an air duct (type C 63 appliances)
· Nominal input, per module: max. 48 kW, min. 12 kW.
· Noise level at maximum output: lower than 49 dBA.
· Modules configuration possibilities:
· Possible cascade installation of 2 or more
Imax Plus
· Heating Operation: setting of instantaneous output by a
main microprocessor, with a comparison parameters
presetting between the requested temperature (or
calculated by the outer compensator) and the global flow
temperature.
· Logic of operation:
A) Output sharing on as many modules as possible at min.
load (down to 12 kW) for the max. efficiency..
B) Automatic operation hour splitting-up system for each
module to guarantee the best homogeneous use.
C) D.H.W. production, via a storage tank loading pump or a
three way diverting valve, controlled by a priority sensor
through the E8 heating controller.
D) Output check of each module for any calibration and/or
assistance by secret access code.
· Possibility of controlling the output of each single module.
·
Heating request control: temperature set point
and
modulation level.
·
Monitoring of boiler and temperature status.
·
Alarm control.
·
Parameters setting.
·
Relay for control of the operation of a pump at constant
flow rate.
·
0
-10V analogical output for control of a modulating pump.
·
Emergency operation: it avoids C.H. system shut down
caused by
an interruption in communication with the boiler
plant's automation system: : (in case of remote control of
the complete boiler house):
·
Input for "Constant setpoint": 55°C, maximum output 50%.
·
Alarm reset input.
·
Alarm relay signal.
· Gas connecting pipes, flow/return water pipes, arranged
for any connection (by the opposite end).
· Integral easily removable panel set (painted steel panels).
·
Flue exhaust pipe, adjustable on the right, the left and
behind the heating system.
· Condensate collecting tank equipped with drain
trap
and stainless steel
flue chamber.
· Built-in air vent.
· Weights and dimensions are limited (see table at par. 1.2).
SENSORS supplied with the boiler:
· outdoor temperature sensor
· flow temperature sensor for mixed zone
· boiler temperature sensor
· D.H.W. storage temperature sensor
Optional accessories
· Air inlet socket & blanking plate kit
· Condensate level harness
(190-330 models LH or Rear flue) (see page 10).
· Cascade control-E8
Cascade control wall mounting kit
2
TECHNICAL FEATURES
AND DIMENSIONS
2
3
4
5
6
7
95
145
190
2
35
2
85
3
30
back
8
Technical features and dimensions
M
CH flow system
R
CH safety system return
Imax Plus
Dimension
No. of Modules
Height
mm
Width ''L''
mm
Depth ''C''
mm
Depth ''A''
mm
Depth ''B''
mm
Connections
Gas
mm (inch)
C.H. system Flow M
mm (inch)
C.H. system Return R
mm (inch)
Chimney connection ''D''
mm
Chimney width ''H''
mm
Condensate drain diameter
mm
145
3
1053
695
820
695
820
38(1½ )
50 (2)
50 (2)
150
240
40
190
4
1053
834
820
695
820
38(1½ )
50 (2)
50 (2)
150
240
40
235
5
1053
968
820
695
820
38(1½ )
50 (2)
50 (2)
200
240
40
285
6
1053
1102
820
695
820
38(1½ )
50 (2)
50 (2)
200
240
40
330
7
1053
1236
820
695
820
38(1½ )
50 (2)
50 (2)
200
240
40
95
2
1053
695
820
695
820
38(1½ )
50 (2)
50 (2)
150
240
40
2.2 - DIMENSIONS
Warning:
Flow/Return connections ( M / R ) change their position
whether they are on the R.H. or on the L.H. side of the
boiler (see views).
FRONT VIEW
RIGHT HAND SIDE VIEW
(Delivery condition for R.H. side connection)
LEFT HAND SIDE VIEW
UPPER VIEW
G
Gas inlet
S
Outlet condensate drain
Øi D
268
350
345
A
B
C
H
223
223
L
= =
315 425
S
340
340
695
455
137
103
M
R
G
17
5
265
220
393
105
3
92
7
126
483
212
452
137
106
M
R
G
30
1
220
53
2
483
212
back
9
Technical features and dimensions
BOILER TYPE
Imax Plus
Appliance category
II2H3P
Nominal Heat Input on P.C.I. Qn
kW
Minimum Heat Input on P.C.I. Qmin
kW
Nominal Output (Tr 60 / Tm 80 °C) Pn
kW
Minimum Output (Tr 60 / Tm 80 °C) Pn min
kW
Nominal Output (Tr 30 / Tm 50 °C) Pcond
kW
Minimum Output (Tr 30 / Tm 50 °C) Pcond min
kW
Efficiency at max. output (Tr 60 / Tm 80°C)
%
Efficiency at min. output (Tr 60 / Tm 80°C)
%
Efficiency at max. output (Tr 30 / Tm 50°C)
%
Efficiency at min. output (Tr 30 / Tm 50°C)
%
Efficiency at 30 % at part load (Tm 50°C)
%
Efficiency at 30 % at part load (Tr 30°C)
%
Efficiency Class acc. to Directive 92/42 CEE
Efficiency Class acc. to Directive 92/42 CEE (100%)
%
Efficiency Class acc. to Directive 92/42 CEE (30%) %
Combustion efficiency at nominal load
%
Combustion efficiency at part load
%
Stand-by losses (Q min.)
%
Stand-by losses (Q nom.)
%
Flue gas temperature tf-ta (min)
°C
Flue gas temperature tf-ta (max)
°C
Flue gas mass flow rate (min)
kg/h
Flue gas mass flow rate (max)
kg/h
Excess of air
%
CO
2
(at min. output)
%
CO
2
(at max. output)
%
NO
X
(value according EN 297/A3 + EN 483)
mg/kWh
NO
X
class
Flue losses with burner in operation (min.)
%
Flue losses with burner in operation (max)
%
Flue losses with burner off
%
Min. water flow rate in CH circuit (
T 20°C)
l/h
Minimum pressure in CH circuit
bar
Maximum pressure in CH circuit
bar
Gas Consumption Natural gas G 20 (20 mbar) Qn
m
3
/h
Gas Consumption Natural gas G 20 (20 mbar) Qmin m
3
/h
Boiler Dry Weight (un-packaged) kg
Max. available pressure at the chimney base
Pa
Condensate production
min-max kg/h
Emissions
Sound level
dBA
Electrical Data
Voltage / Frequency
V/Hz
Fuse on main supply
A (F)
Max power / Min power absorbed
W
Insulation degree
IP
Standby Consumption
W
2.3 -
PERFORMANCE DATA
The Technical data plate is placed under the
casing front panel next to the panel board.
330
336
12
329,52
11,23
339,36
12,74
98,07
93,6
101
106,2
103,2
106,8
4
98,04
96,55
98,1
98,43
4,83
0,03
30,4
40,1
20,2
554,3
26,84
8,8
9
52
5
1,57
1,90
0,3
14169
0,5
6
35,53
1,27
357
100
21,1-56,4
<49
230/50
4
507/40
40
10
285
288
12
282,24
11,23
289,87
12,74
98
93,6
100,65
106,2
103,2
106,8
4
97,90
96,35
97,96
98,43
4,83
0,01
30,4
41,2
20,2
475
26,84
8,8
9
52
5
1,57
2,04
0,3
12136
0,5
6
30,45
1,27
312
100
18,1-48
<49
230/50
4
435/40
40
10
235
240
12
234,72
11,23
240,96
12,74
97,8
93,6
100,4
106,2
103,2
106,8
4
97,76
96,13
97,8
98,43
4,83
0,02
30,4
43,1
20,2
396
26,84
8,8
9
52
5
1,57
2,18
0,3
10265
0,5
6
25,38
1,27
272
100
15,1-40,8
<49
230/50
4
362/40
40
10
190
192
12
187,39
11,23
192,38
12,74
97,6
93,6
100,2
106,2
103,2
106,8
4
97,55
95,82
97,7
98,43
4,83
0,14
30,4
44,8
20,2
317
26,84
8,8
9
52
5
1,57
2,26
0,3
8058
0,5
6
20,30
1,27
230
100
12,1-32,4
<49
230/50
4
290/40
40
10
145
144
12
140,11
11,23
144,14
12,74
97,3
93,6
101,1
106,2
103,2
106,8
4
97,29
95,44
97,6
98,43
4,83
0,31
30,4
47,2
20,2
237,6
26,84
8,8
9
52
5
1,57
2,39
0,3
6025
0,5
6
15,23
1,27
191
100
8,9-24
<49
230/50
4
210/40
40
10
95
96
12
93,22
11,23
95,90
12,74
97,1
93,6
99,9
106,2
103,2
106,8
4
96,94
94,91
97,5
98,43
4,83
0,42
30,4
49,1
20,2
158,4
26,84
8,8
9
52
5
1,57
2,48
0,3
4008
0,5
6
10,15
1,27
156
100
6-15,9
<49
230/50
4
145/40
40
10
back
10
Technical features and dimensions
The gr
illes for the air intake are placed
on the Right side, Left side and
Rear.
On the casing panels of the boiler there are some pre-cuttings for the gas connection. Once the connection
position has been selected, remove the
relevant pre-cut part.
Unless
a special order is placed, the boiler is supplied with:
-
Flue and condensate evacuation connection
on the R.H. side
.
-
C.H. flow connection
on the R.H. side
.
-
C.H. return connection
on the R.H. side
.
-
Gas connection
on the R.H. side
.
2.4 - R.H. SIDE VIEW, WITH MAIN COMPONENTS
I
f the position of the flue connection, for boilers Imax Plus 190 - 235 - 285 - 330, is changed from the
standard one (right side) it is necessary to place an order for the harness of the condensate
level sensor.
FAN
GAS VALVE
GAS PIPE
BURNER
COVER
IGNITION
IONIZATION
LOCAL NTC
SENSOR
BURNER
ALUMINIUM
HEAT
EXCHANGER
CONDENSATE
DRAIN
TRAP
CONDENSATE
COLLECTING
TRAY-
FLUE
MANIFOLD
C.H.
RETURN
C.H. FLOW
GLOBAL FLOW
NTC TEMPERAT.
SENSOR
AUTOMATIC
AIR VENT
H.L.
THERMOSTAT
DRAINING TAP
Min. Depth 100 mm
BOILER FRAME
CONDENSATE
LEVEL SENSOR
back
11
Instructions for the installer
3
INSTRUCTIONS FOR
THE INSTALLER
3.1 -
GENERAL WARNINGS
WARNING!
This boiler has to be destined for the use for
which it has been expressively designed for.
Any other use shall be considered improper
and therefore dangerous.
This boiler is designed to heat water at a
temperature inferior to boiling point at an
atmospheric pressure.
WARNING!
These appliances are exclusively designed
to be installed inside adequate boiler rooms.
Therefore these appliances must not be
installed and operated externally.
Before installing the boiler the following points
have to be carried out by a competent engineer:
a) An accurate washing of all the pipes of the
installation to remove possible residues or
impurity that could jeopardize the good
operation of the boiler, also from the sanitary
point of view.
b) Check that the boiler has been preset for
operating with the gas type available.
This is verifiable via the indication on the
packaging and on the data badge.
c) Check that the chimney/flue pipe has an
adequate draught, does not have any
constrictions, and that no other appliance's
flue outlets have been fitted, unless the chimney
is serving more than one heating appliance,
according to the specific standards and
regulations in force.
The connection between the boiler and
chimney/flue outlet can be made only after this
verification has been carried out.
WARNING!
In rooms where there is the presence of
aggressive vapours or dust the appliance
must operate independently from the air
present in the boiler's location room!
WARNING!
The appliance must be installed by a Gas
Safe Registered Engineer or, in IE, by a
competent person
WARNING!
Install the appliance respecting the minimum
clearances for operation and servicing.
The boiler must be connected to a heating
system which is compatible to its performances
and output.
back
12
Instructions for the installer
3.2 -
STANDARD CODES FOR
INSTALLATION
The appliance must be installed in compliance to the
instructions contained in this manual.
The installation must be carried out by a Gas Safe Registered
Engineer or, in IE, by a competent person.
The installation must be carried in accordance to the codes of
practice, the regulations and the requirements hereby indicated
which constitute an indicative list, but not a complete one, as
these continue to undergo evolve devolpments.
Moreover, the boiler must be installed in accordance to all the
regulations regarding the boiler room, the building regulations
and the prescriptions regarding central heating plants in force
in the country where the boiler is installed.
The appliance must be installed, commissioned and serviced
according to the regulations in force. This is also valid for the
hydraulic system, the flue outlet system and the boiler location
room.
For relevant codes of practice and safety information see page 6
back
13
Instructions for the installer
3.3 - PACKING
The
Imax Plus boiler is delivered assembled and
protected by a plastic bag inside a strong
cardboard box and fixed on
a pallet. This allows the
boiler to be handled by
a forklift. The boiler,
with the packaging, can go through a door of 800
mm, whereas, without packaging, it can go
through a door of 700 mm.
Remove both straps and finally the cardboard
box from above, making sure the product is
intact. The packing elements (cardboard box,
straps, plastic bags, etc...) shall not be left in
children's hands since they may be
dangerous.
Inside the packing, you can find,
on the boiler back:
- the front casing
attached to the back one by a plastic
film
- the condensate drain pipe,1 m long, placed under the
casing rear panel.
on the L.H. side of the boiler:
- the R.H. side panel
attached to the L.H. side one by a
plastic film.
on the boiler front:
- the
flue chamber/condensate collecting tray screwed to
the pallet
- a plastic bag containing:
· 3 gaskets (1 rectangular between condensate tray and
flue terminal, 1 square between flue socket base and flue
terminal and 1 for flue socket Ø 150 or Ø 200 mm according
to the model
· 2 bends + 1 Tee piece + 1 plastic plug, Ø 40 mm for
candensate drain.
· the screws necessary for fixing
· 1 plastic box containing the outer sensor.
on the boiler top:
- a plastic bag containing:
· This instruction manual
3.4 - BOILER LOCATION INSIDE A BOILER HOUSE
Special attention shall be paid to local regulations and laws
about boiler houses and particularly to the obligation of keeping
minimum clearances and empty space around the boiler. The
installation shall be in compliance with all latest regulations
and laws about boiler houses, installations of heating and hot-
water systems, ventilation, chimneys capable of evacuating
the flue gases of condensing boilers and any other applicable
requirement.
When selecting the position for the installation of the
boiler it has to be considered that, for the cleaning and
washing operations of the boiler body, one of the boiler
sides must be accessible for the removal of a special
baffle placed under the aluminum sections.
This baffle can be fixed
either from the R.H or L.H.
side of the condensate tray. If no modification has been
made, the boiler must have its R.H. side accessible, with the
flue connection fitted on the R.H or L.H. side. But, if the
· Warranty certificate
· Hydraulic certificate
· Controls instructions E8
flue terminal, with the flue socket, is left on the R.H. side
and if, from this same side, the baffle has to be re
moved,
then the flue socket must have the possibility to be
also
removed.
If it is preferred, the baffle can be moved in order to have its
fix
ing screw on the opposite side, regardless the position
of the
flue outlet.
The boiler can be put on a flat and sufficiently strong base
with the same dimensions as th
ose of boiler and at least
100mm high (see fig. 2), in order to assemble the conden-
sate drain
trap. An alternative to this base may be a
100mm deep well next to the boiler as
a trap housing
(see fig. 2). After installation the boiler shall be perfectly
horizontal and stable, to reduce any possible vibra
tions
or noises.
C
B
A
770
770
908
1042
1176
1310
95
145
190
2
35
2
85
3
30
780
780
780
780
780
780
181 kg
215 kg
256 kg
300 kg
341 kg
387 kg
1250
1250
1250
1250
1250
1250
back
14
Instructions for the installer
When the appliance is installed on existing systems, ensure
yourself that:
- The flue outlet pipe is suitable for condensing boilers, for
the temperature of the products of combustion, calculated
and manufactured according to the regulations in force. It
must be installed as much as possible in a straight line,
tested for soundness and must not have any occlusions
or restrictions.
- The flue outlet pipe has a connection for the discharge of
condensate.
- The boiler room has a suitable outlet for the discharge of
condensate produced by the boiler.
- The electrical system has been fitted in compliance to the
specific norms and the work has been carried out by a
competent person.
- The circulation pump's output, the head and flow direction
are suitable.
- The gas feed supply pipe is constructed according to the
regulations in force.
- The expansion vessels assure the total absorption of the
expansion of the fluid contained in the system.
- The system has been cleaned of impurities and lime scale.
When a
n Imax Plus boiler is installed onto an existing
heating system:
Before the replacement of an existing boiler in
an old system can be programmed, it
is
necessary to thoroughly clean out the system
with a basic solution. The system must be
cleaned 4 weeks before the substitution, with
the system firing at a temperature of 35°C to
40°C.
WARNING!
If it is noticed that a new
Imax Plus has replaced an existing
boiler in an old system without having first performed what is
said in the previous paragraph,
do not wash the system now
as residual products, present in the circuit, could lead to
them
gathering in the boiler body, causing damage.
Ideal Boilers recommends contacting a specialised company
for water treatment.
If installing an Imax Plus boiler in a new system,
it is
recommended to thoroughly clean out the system with an
adequate product and fit a filter
/strainer with two isolating valves
on
the boiler's return pipe, so that, when necessary, it can be
cleaned. This filter will protect the boiler from the dirt coming
from the heating system.
When sizing pumps, it is necessary to take into consideration
the pressure losses which occur
in the primary circuit.
3.5 -
INSTALLATION ON EXISTING HEATING SYSTEMS
A
B
C
Trap
A > 400 mm
B > 400 mm
*
C = 100 mm
D = 500 mm
D
Give the boiler the minimum
clearances as shown in the
drawing, in order to be able to
make the normal service and
cleaning operations.
* - Minimum clearance of 50 mm one side only, with 400
mm on opposite side for flue baffle access and pipework
connections. For side flue outlet increase to 600 mm
clearance. For pipework only allow 300 mm clearance.
Front - 600 mm; except compartment access doors may be
closer, but not less than 200 mm, and 600 mm must still be
available for service across the full width of the boiler.
back
15
Instructions for the installer
3.6 - BOILER CONNECTION
A
s delivered the Imax Plus boiler has all the connections on
its R.H. side: hydraulic (flow / return), gas, and
flue outlet.
The locations of the air intake and the
flue outlet can be
decided on site by removing one of the notched parts available
on the boiler right, left and back sides. To fix the
terminal with
the flue socket, use the screws and the gaskets
supplied
inside the plastic bag and a min. 300 mm long cross
headed
screwdriver.
Hydraulic (flow/return) and gas connections can be also
moved
to the boiler L.H. side by inverting the madifolds
to the left side according to the following procedure:
- Remove the complete casing
- Remove the small plates fixing the flow and return global
temperature sensors
- Disassemble the flow and return manifolds, leaving
in their
place, on the aluminum sections, the rubber gaskets (on
the upper holes) and the diaphragms (on the lower holes).
The diaphragms on the end sections have a hole of 17
mm dia., while the others have a hole of 22 mm dia.
- Reassemble the manifolds with the threaded connection on
the opposite side as shown in the figure
right.
- Change, between them, the position of the drain cock and
the automatic air vent.
- Reposition the temperature sensor white and red leads onto
the new flow manifold and the temperature sensor white
and green leads onto the new return manifold.
- It is possible to keep the gas manifold inlet on the R.H. side
or, otherwise, it is possible to rotate it 180° to have it on
the L.H. side.
When changing the gas manifold from
R.H. side to L.H. side, only on the Imax Plus 95 will it be
necessary to
swap the plug C with the gas valve fitting A.
Ø 17 mm
Ø 22 mm
Ø 17 mm
Ø 22 mm
A
B
C
A
B
C
M
R
M
R
POSSIBLE GAS CONNECTION REVERSION
POSSIBLE WATER CONNECTIONS REVERSION
Ø 17 =
Diaphragm for the two collectors positioned at the
extreme ends
Ø 22 =
Diaphragm for the internal collectors.
REAR VIEW
C.H. Flow and Return R.H. side connections
(std delivery condition).
REAR VIEW
C.H. Flow and Return L.H. side connections
(after modification condition)
FRONT VIEW
Gas connections on the L.H. side
(after modification condition)
FRONT VIEW
Gas connections on the R.H. side
(std delivery condition).
back
16
Instructions for the installer
3.7 -
GAS CONNECTION
The gas supply pipe must be connected to the boiler by a
1½" G
as pipe as indicated on page 8.
The gas supply pipe must have a section which is identical or
greater then the one used on the boiler and must assure a
correct gas pressure.
It is however important to comply with the specific norms and
requirements in force, foreseeing on-off valves, gas filter, anti-
vibrating joint etc.
Before commissioning an internal gas distribution system and
therefore before connecting it to the gas meter, the complete
installation must be tested for gas soundness.
If any part of the system is concealed from view the gas
soundness test must be carried out before covering the pipes.
DANGER!
The gas connection must be carried out by
a Gas Safe Registered Engineer who will
have to respect and comply to the
regulations in force and to the requirements
indicated by the local gas supplier.
An incorrect installation could cause injury
to persons, animals or damage to property.
The manufacturer shall not be held liable for
any injury and/or damage.
Before installing the boiler it is recommended
to thoroughly clean all the supply piping in order
to remove any residual grime which could
compromise the boilers correct function
If you smell gas:
a. Do not turn on or off electrical switches, use
the telephone or any other object which can
provoke sparks;
b. Open all doors and windows in order to allow
fresh air to enter and purify the room;
c. Close all gas cocks
d. Contact a service engineer, qualified installer
or the gas supply company.
back
17
Instructions for the installer
3.8 -
FLOW AND RETURN PIPE
CONNECTIONS
The CH flow and return circuits have to be connected to the
boiler via the respective connections 2" M and R as indicated
on page 8.
When determining the size of the CH circuit pipes it is essential
to bear in mind the pressure losses induced by any of the
system's components and by the configuration of the system.
The route of the piping has to be conceived taking all the
necessary precautions in order to avoid air locks and to facilitate
the continuous purging of the system.
WARNING!
IT IS ABSOLUTELY FORBIDDEN TO FIT
ON-OFF VALVES ON THE BOILER BEFORE
THE SAFETY DEVICES
WARNING!
Before installing the boiler we recommend
that the system is flushed out with a suitable
product in order to eliminate any metallic
tooling or welding residues, oil and grime
which could reach the boiler and affect the
proper running of the boiler. The appoved
water treatments are given on page 24.
Non-observance of these instructions could
cause injury to persons, animals or damage
to property. The manufacturer shall not be
held liable for any such injury and/or
damage.
Ensure yourself that the system's piping is not
used as the earth clamps for the electrical or
telephonic system. They are absolutely
unsuitable for this use. In a short time this could
cause serious damage to the piping, boiler and
radiators.
back
18
Instructions for the installer
3.9 -
DETERMINATION OF PRIMARY BOILER PUMP OR BOILER SYSTEM PUMP
The size of the pumps must be determined
by installers or technical engineers
according to boiler data and system design.
The water side resistance curve of the boiler
is shown in the following diagram.
The pump is not an integral part of the boiler.
It is recommended to choose a pump with
the rate and delivery head at about 2/3 of its
characteristic heating curve.
The boiler pump must have a delivery head which can ensure
the water flow rate as shown in the diagram "Water pressure
losses".
The following table gives an indication of the pump's flow rate
in function of the Ät of the primary circuit if the installation has
a mixing header.
145 190 2
35 285 330
6025
8058 10265 12136 14169
8032 10743 13457 16181 18301
95
4008
5344
Boiler Model
Max water flow rate
Demanded in l/h ( t=15 K)
Max water flow rate
Demanded in l/h ( t=20 K)
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0
0
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21
MOD
95
MOD 190
MOD 2
35
MOD 2
85
MOD 3
30
MOD 145
WATER FLOW m³/h
P
R
E
SSU
RE L
O
SS
E
S
m
b
a
r
WATER SIDE PRESSURE LOSSES
NOTE: The use of a mixing header fitted between the boiler circuit and the system circuit is
always advisable. It becomes INDISPENSABLE if the system requires flow rates superior to the
maximum permitted boiler flow rates, which is to say lower than 15K.
For a
T 20 K, of an Imax Plus 235 boiler, the max. water flow rate requested is 10,3 m3/h.
From the graph of the boiler's pressure losses, it can be determined that the pump must be able
to guarantee a delivery head of at least 250 mbar.
back
19
Instructions for the installer
Working pressure 6.0 bar maximum, 0.8 bar minimum.
There is no minimum water pressure switch on the boiler, with
safety thermostats providing protection against dry firing.
However, should a minimum water pressure switch be
required in the system a ¼" connection is available on the
return manifold. The electrical connections should be made in
series with the minimum gas pressure switch.
Particular reference should be made to BS. 6644: Section 6
and Guidance note PM5 "Automatically controlled steam and
hot water boilers" published by the Health and Safety
Executive.
The information and guidance given below is not intended to
override any requirements of either of the above publications
or the requirements of the local authority, gas or water
undertakings.
In general commercial closed pressurised systems are
provided with either manual or automatic water make up.
On both instances it will be necessary to fit automatic controls
intended to protect the boiler, circulating system and ancillary
equipment by shutting down the boiler plant if a potentially
hazardous situation should arise.
3.10 - SEALED SYSTEM REQUIREMENTS
Examples of such situations are low water level and operating
pressure or excessive pressure within the system. Depending
on circumstances, controls will need to be either manual or
automatic reset. In the event of shutdown both visual and
audible alarms may be necessary.
Expansion vessels used must comply with BS. 4814 and must
be sized on the basis of the total system volume and initial
charge pressure.
Initial minimum charge pressure should not be less than 0.8
bar (11.6 psi) and must take account of static head and
specification of the pressurising equipment. The maximum
water temperatures permissible at the point of minimum
pressure in the system are specified in Guidance Note PM5.
When make-up water is not provided automatically it will be
necessary to fit controls which shut down the plant in the event
of the maximum system pressure approaching to within 0.35
bar (5 psi) of safety valve setting.
back
20
Instructions for the installer
3.11 - WIRING DIAGRAM FOR ADDITIONAL
SAFETY DEVICES
SAFETY
VALVE
VISIBLE
DRAIN
FUNNEL
Pump management via E8
to the terminal 4 (A10)
from the IV connector
LINE
230 V
RELAY
L1
N
LINE
230 V
Boiler mains
supply
230 V
N
L1
3.12-
PRESSURE RELIEF VALVE DRAIN
PIPE
A pressure relief valve must be fitted on the flow
pipe, immediately next to the boiler. It must be
suitable for the capacity of the boiler and
must comply to the regulations in force,
WARNING!
Please remember that it is forbidden to
install, between the boiler and the
pressure relief valve, any type of cut-off
device. Moreover it is recommended to use
cut-off valves which do not exceed the
maximum allowable operating pressure.
WARNING!
In respect to the heating pressure relief
valve see right the installation of a
discharge pipe with a funnel and a trap
which lead to an adequate drainage. The
drainage has to be controllable by sight.
If this precaution is not made, an eventual
intervention of the pressure relief valve
could cause injury to persons, animals or
damage to property. The manufacturer shall
not be held liable for any injury and/or
damage.
L1
N
N
L1
Terminals EXT-MIN
interface WILO
modulating pump
LINE
230 V
RELAY
LINE
230 V
Boiler mains
supply
230 V
ON-OFF PUMP
MODULATING PUMP
back
21
Instructions for the installer
3.13 -
MIXING HEADER FILTER
Ideal Boilers suggests the installation of a
filter/strainer on the return pipe so that it can
be cleaned if necessary.
This will protect the boiler from the
heating system dirt.
back
22
Instructions for the installer
3
.14 - BOILER FREEZE PROTECTION
Should the flow temperature (measured at global flow tempera-
ture NTC) decrease under 7°C, the system pump
will run. Should
this temperature decrease to under 3°C, all modules will start at
min. output until the return temperature reaches 10°C.
Such protection devices
are exclusively for the boiler. For the
protection of the system, a second frost protection thermostat is
necessary to switch on the heating system pump.
To protect the C.H. system from freezing when boiler is not in
operation during cold season, it is necessary to add to the C.H.
system water an anti freez
e solution.
NB: The antifreeze solution must be compatible with the
materials present in the system, and mainly with the
aluminum.
3.15 -
MIXING HEADER
D
1/2''
KV
KR
HR
g
a
b
c
h
e
HV
1/2''
1/2''
1/2''
g
CH FLOW
CH RETURN
F
I
L
T
E
R
CH FLOW
CH RETURN
Boiler
Circuit
Heating
System
Circuit
In order to ensure correct boiler operation it is
advisable to
use a mixing header which guarantees:
-
the separation and collection of circuit dirt
-
optimal air venting
-
hydraulic de-coupling of the two hydraulic circulation circuits
-
balancing of the circuits
WARNING
AFTER A LONG INOPERATION PERIOD OF
THE BOILER, IN CASE THE BOILER TEMPE-
RATURE IS BELOW 3°C, ABSOLUTELY DO
NOT TRY TO START THE BOILER.
THIS CAN BE ALLOWED ONLY IF YOU ARE SURE THAT AN
ANTIFREEZE SOLUTION HAS BEEN ADDED, IN THE PRO-
PER PERCENTAGE, TO THE C.H. WATER.
4.000
8.000
12.000
20.000
30.000
50.000
100
150
200
200
250
300
95 kW
145
190
2
35
kW
kW
- 2
85 kW
power supply
over > 3
30 kW
50
65
80
100
125
150
50
65
80
100
125
150
200
200
200
200
200
250
1.000
1.000
1.000
1.000
1.000
1.000
300
300
300
300
300
300
150
150
150
150
150
150
1.650
1.650
1.650
1.650
1.650
1.700
200
200
200
200
200
200
Note: The mixing header is not supplied by
Ideal Boilers. The information is provided as advice.
TABLE FOR THE RECOMMENDED DIMENSION OF THE
HYDRAULIC COMPENSATOR
The use of a mixing header means that compensating
controls can be used to operate mixing valves on a
variable temperature circuit, without affecting the water
flow rate through the boiler.
back
23
Instructions for the installer
3.16 - CONDENSATE DRAIN
Avoid the condensate stagnation inside the combustion
products evacuation system, (for this reason the
condensate
d
rain must have an inclination toward the drain of at least 30
mm/m (3/8 in. / ft) except the liquid column, inside the
condensate
trap, which needs to be filled with water after
installation: its minimum height, when all the fans are in oper-
ation, must be at least 25 mm (1 in.).
In order to avoid ice formation while the boiler is operating,
which can cause the
boiler to stop, the whole condensate
evacuation system has to be well insulated. It is forbidden to
evacuate the condensate through a gutter
due to a risk of ice
forming and corrosion.
The connection to the sewer will be through a visible drain.
Given the acidity degree (pH 3 to 5) only plastic ma
terial
can be used for the condensate evacuation pipes.
Moreover it must be dimensioned and constructed so as
to allow the correct out-flow of drains, preventing any bot-
tleneck and any leakage.
BACK SIDE
BOILER
HOUSE
FLOOR
150
150
INITIAL
TRAP
FILLING-UP PLUG
The upper part of the drain
pipe shall not be higher
than the tray bottom.
*
Min. height of the condensate column, with all fans
operating at max. speed, requested by the EN
standards.
** Min. height of the condensate column, with all fans
operating at max. speed. If it is not possible to create
a 100 mm boiler base, install the boiler on the floor
and create a min. 100 mm deep well to lodge the trap.
The outlet of the condensate drain pipe will be on the same
side of the
flue chamber, passing below the flue cham-
ber.
Before commissioning the boiler fill the condensate trap
with water, from the dedicated filling-up plug.
back
24
Instructions for the installer
3.17 - WATER TREATMENT
The imax plus
I
II
boiler has an ALUMINIUM alloy heat exchanger.
Corrosion will always occur within a heating/hot water system to
a greater or lesser degree irrespective of water characteristics,
unless the initial fill water from the mains is treated. For these
reasons Ideal Boilers strongly recommends that the
system
be thoroughly cleaned prior to the use of a stable inhibitor
which does not require continual topping up to combat the effects
of hardness, salts, and corrosion on the heat exchanger and its
associated systems.
Therefore it is important that if water treatment is used it is
suitable for the material of the heat exchanger. The ONLY water
treatments approved are Fernox Copal or MB1 or GE Betz
Sentinel X100 inhibitors and associated water treatments, which
must be used in accordance with manufactures instructions.
Current suitability should be confirmed directly with the
manufacturer.
Sentinel Performance Solutions
The Heath Business & Technical Park
Runcorn, Cheshire. WA7 4QX
Tel 0800 389 4670
www.sentinel-solutions.net
or
Fernox Manufacturing Co. Ltd.,
Cookson Electronics, Forsyth Road,
Sheerwater, Woking, Surrey, GU21 5RZ
Tel: 01799 521133
Artifically softened water must NOT be used to fill the system.
back
25
3.18 - CONNECTION TO THE CHIMNEY
In a condensing boiler the
flue gases are evacuated at a
very low temperature (Max about 84°C). It is necessary that
the chimney is perfectly impermeble to the condensate of
the combustion products and is made of materials corrosion
resistant.
The different spigot joints must be well sealed and equipped
with suitable gaskets, in order to prevent the outlet of
condensate and the inlet of air.
Concerning the cross section and the height of the chimney, it
is necessary to make reference to the national and local rules
in force.
In order to prevent
the formation of ice, during the operation,
the temperature
of the internal wall of the combustion product
evacuation system, in all its length, has not to be below 0°C.
For condensation operating conditions of the appliance at the
external design temperature, it will be necessary to
install a
condensate evacuation system, discharging according to the
installation condition, in the boiler condensate tray or in
another dish
pan separated from it.
The
Imax Plus boiler is suitable also for installation in C 63
type, by taking the combustion air from outside the boiler
house via an air duct.
To convert the boiler for type C 63 operation, a special kit
is available
for order from Ideal Boilers - Air inlet socket & blanking plate kit
3.19 - ROOM SEALED VERSION
2
3
4
5
6
7
95
145
190
2
35
2
85
3
30
150
150
150
200
200
200
The type of flue pipe used should be 316 grade Stainless Steel
or be of equivalent corrosion resistance. Advice regarding the
availability of proprietary types of flue system can be obtained
by contacting Ideal Boilers. All joints or connections in the
flue system must be impervious to condensate leakage.
Low points in the flue system should be drained using pipe of
material resistant to condensate corrosion. All drains in the
flue should incorporate a water trap.
Flue Connections
It is possible to combine flue connections at any of the
positions of left, right and rear. To change connections,
simply remove the blanking plates from the connection
required and attach the flue connections. Seal off the
unused connections with the removed blanking plates.
Air Connections
Boiler sizes 95-145 are delivered with an air inlet filter
fitted on the right side with the left side and rear
connections blanked off. If required the filter can be
moved to the left side, using the removed end panel
and blanking plate on the right side. Boiler sizes
190-235 have an air inlet filter fitted to both sides.
Boiler sizes 285-330 have filters fitted to both sides
and the rear. Ducting air directly to the boiler from
outside is possible to the left or right side or rear by the
removal of all filter(s) andthe use of air inlet spigot kit(s).
These kits are obtainable from the boiler manufacturer.
Instructions for the installer
Maximum pressure available at flue outlet : 100Pa
back
26
Instructions for the installer
Imax Plus
95
145
190
235
285
330
Flue gas mass
flow rate (max)
kg/h
158,4
237,6
317
396
475
554,3
Example:
Imax Plus 235
Flue gas mass flow rate
=
396 Kg/h
Chimney height
=
25 m
Chimney connection Ø
=
250 mm
NOTE:
The diagram shows
t
he indicated values
Flue gas mass flow rate
CO
2
content
d 125
a
d 400
a
d 315
a
d 250
a
d 200
a
d 160
a
d 110
a
d 75
a
6
7
8
9
10
12
14
16
18
20
30
40
50
60
70
80
90
100
120
140
160
180
200
300
400
500
600
700
800
900
1000
1200
1400
4,4
5,9
6,6
7,4
8
9
10
12
22
30
37
44
52
59
66
74
89
104
119
133
148
222
296
370
444
519
593
668
741
889
1037
3,4
3,9
4,4
5,0
5,6
7
8
9
11
17
22
28
34
39
44
50
56
67
78
89
100
111
167
222
277
333
389
445
555
667
778
0,001
0,002
0,003
0,004
0,005
0,006
0,007
0,008
0,009
0,010
0,015
0,020
0,030
0,035
0,040
0,050
0,060
0,070
0,080
0,090
0,100
0,150
0,200
0,250
0,300
0,350
0,400
0,500
0,600
5
0,700
9,0
10,8
12,0
14,4
22
25
29
32
36
54
72
90
108
126
144
180
216
252
288
324
360
540
720
900
1080
1260
1440
1800
2160
2520
6
7
8
9
10
12
14
16
18
20
30
40
50
60
70
80
90
100
120
140
160
180
200
300
400
500
600
700
800
900
1000
1200
1400
8%
6%
kg/s
kg/h
10%
10
15
20
25
30
5
10
15
20
25
30
mass flow rate
40 Pa
40°C
396
Chimney dimension
DIN 4705
Pressure avaible
Flue Gas Temperature
N
o
mi
na
l
H
e
at
i
n
p
u
t
(
k
W
)
No
m
i
n
a
l He
a
t
in
p
u
t
(
k
W)
wi
t
h
CO
le
v
e
l
a
t
1
0
%
2
Flue gas
back
27
Instructions for the installer
The boiler consists of mutally connected combustion cham
bers:
each of them has its own burner - fan, with air pressure
switch for control - gas valve, with ignition and ionisation
device - BMM (Burner Modular Manager) control PCB.
In each cast aluminum section there is a temperature sensor
NTC (Negative Temperature Coefficient), called local NTC,
which locally checks the flow temperature of each aluminum
section, and a High Limit thermostat.
The flow temperature at the boiler outlet and the return
temperature at the boiler inlet are controlled by global NTC
temperature sensors.
When more heat is requested by heating or DHW systems, the
boiler st
arts up and water will be heated by an aluminum boiler
body. Then the boiler pump sends water to the mixing
header,
and, from here, the C.H. pump will send it to the radiators,
according to the heating system chosen.
The combustion air is supplied by fans and taken in from the
boiler room (for type B 23 boilers), or from outside through
pipes (for type C 63 boilers, i.e. room sealed combustion
boilers).
The combustion air is then pushed into the pre-combustion-
chamber through a diaphragm.
Beyond the diaphragm, the air mixes with gas and such
mixture
passing through the non-return valve is sent to the burner.
Then, on leaving the burner surface, the air/gas mixture
ignites electrically and the resulting combustion gases, after
being transported (and cooled) through pinned sections, enter
the condensate collecting manifold and then are evacuated
through the boiler chimney.
3.20 - BOILER OPERATION
Fan
C.H. Flow
Global Return
NTC temperat. sensor
Global Flow
NTC temperat. sensor
Burner
Ionization
electrode
Ignition
electrode
Combustion
Chamber
Local NTC
sensor
H.L.
Thermostat
Heat
e
xchanger
Condensate
collecting
tray
flue
manifold
Air press
ure switch
Gas valve
Flue outlet chamber
Gas
back
28
Instructions for the installer
1
Thermal element
(module) = 48 kW = 100%
4
Thermal elem.
= 48 kW x 4 = 192 kW = 400%
400% : 192 kW = 200% : X
X = (192 x 200) : 400 = 96 kW
input shared on 4
thermal elements
Input shared on 4 thermal elements : total input
= 96 : 192 = 0,5 = 50%
P
(kW)
10
100
103,2
% (p.c.i.)
20
48
30
102,4
100 % = 48 kW
50 % = 24 kW
12
40
24
1 thermal
element
1 thermal
element
When there is a heat request from the E8 controller or from a
BCM (Boiler Cascade Manager), the E8 or BCM calculates
the necessary output according to the difference between the
set temperature (or the temperature calculated by the outer
compensator) and the global flow temperature. The number
of thermal elements (each thermal element represents a ma-
ximum input of 48 kW) x 100% determines the maximum input
expressed in %.
When the input has been determined, the boiler pump (not
supplied by
Ideal) starts and the fan of one thermal element
is set in motion at starting speed. The gas valve opens
and
ignition occur
s within 5 sec. When the ionisation electrode
detects the flame, the thermal element starts operating.
Subsequently other thermal elements are likely to start in the
same way. One of the operation principles for this boiler is
letting as many burners as possible operate simultaneously
at minimum load to reach the maximum efficiency.
For example, if a 4 thermal element boiler is requested to
operate at its max input, this shall be 400% i.e. :
48 kW x 4 thermal elements = 192 kW = 400%.
If it is requested to operate at 200% input, thanks to the input
4 thermal elements of 48 kW each working
at 50% of the output give = 96 kW = (200%),
i.e. 24 kW / thermal element
0
5
10
15
20
25
30
35
40
kW
mo
d
1
sharing system on the highest number of thermal elements,
each thermal element will operate at 50% output i.e. :
200% : 4 thermal elements = 50%
equal to a total of 96 kW, that is 24 kW for each thermal
element.
Such
a principle provides clearly efficiencies much higher than
those obtained in traditional groups of small boilers installed
in cascade.
When the input shared on each thermal element is less than
12 kW
, one thermal element after the other is automatically
excluded and the remaining input is shared on thermal
elements having the smallest number of operation hours (by
the automatic operation-time calculating system).
Modulation, i.e. input reduction, is based on the difference
between the set temperature (or the temperature calculated
by the outer compensator) and the global flow temperature.
When no ignition occurs, the ignition device repeats two more
times the ignition sequence and then puts to lock out position
the thermal element concerned.
Efficiency of a thermal element working at full capacity
48 kW = 100 %
(in condensation)
Efficiency of a thermal element working at reduced capaci-
ty
24 kW = 102,4 %
(in condesation)
Efficiency of a thermal element working at minimum capa-
city
12 kW = 103,2 %
(in condesation)
All the thermal elements work in parallel at the same output,
equalizing, thus, the C.H. system efficiency to the one of the
thermal element.
back
29
Instructions for the installer
3.21 -
ELECTRICAL CONNECTIONS
Regulato
ry Requirements
The gas and water feeding pipes and the CH system pipes
cannot be used as protective earth.
Connections
Ideal Boilers refuses responsibility for any damage arising
from failure to earth the boiler correctly.
Wiring external to the appliance MUST be in accordance
with the current I.E.E. (BS7671) Wiring Regulations and
any local regulations which apply. For Ireland reference
should be made to the current ETCI rules for electrical
installations.
The point of connection to the mains should be readily
accessible and adjacent to the boiler.
For the appliance's general electrical supply the use of
adaptors, multiple sockets and/or extension cords is strictly
forbidden.
The use of any power supplied equipment implies the
observance of several fundamental rules, such as:
- Do not touch the appliance with any wet part of your body
and/or barefooted;
- Do not pull the supply cables
- Do not expose the boiler to sunlight, rain, etc.
- Do not permit children or non-expert people to use the
appliance.
Mains electrical supply connection 230V
The electric connections of the boiler are shown in the section
named "WIRING DIAGRAMS" (paragraph 3.18 page 30)
A mains supply of 230 V 50 Hz is required.
WARNING!
The appliance MUST be wired with a
permanent live supply. Use the plug
provided for this purpose. The boiler is
phase sensitive so correct connection
of the live and neutral wires is essential.
The supply must not be interrupted by
any system controls. Controlling the
mains input in this way will prevent the
pump over-run sequence and may cause
damage to the heat exchanger.
DANGER!
The electrical connections must be carried
out only by a qualified engineer.
Before carrying out the connections or any
other operation on the electrical parts,
always switch off and disconnect the
electricity supply and ensure yourself that it
cannot be accidentally turned on.
It is necessary to fit a double pole switch on the electrical supply
line, having a 3 mm contact separation in both poles, in an
easy accessible position in order to make quick and safe the
servicing operations.
The boiler electrical supply (230 V 50 Hz single phase) is
to be
made using the three pole plug supplied with the
boiler.
WARNING!
230 V cables shall be separated from 24 V
ones, using the two plastic conduits
supplied within the boiler casing L.H. side
panel.
back
30
Instructions for the installer
3.22 -
FUNCTIONAL WIRING DIAGRAM
TL
TL1
25
4
1
L1
N
PE
RI
L
.
/RE
G
.
AL
I
M
.
23
0V
VM1
RED
RED
WHITE
WHITE
BROWN
WHITE
1° Modul
RED
E.RIL.1
SR1
SRR
SR
YEL/GREEN
PG
F6A
13
12
11
10
9
8
7
6
4
3
2
1
BROWN
BLUE
BROWN
BLUE
BLACK
ORANGE
BROWN
BROWN
RED
BLACK
BLUE
LIGHT BLUE
BROWN
F10A
YE
L
-
G
R
EEN
BROWN
BR
O
W
N
BL
U
E
BLUE
BLUE
BROWN
BROWN
BROWN
BROWN
BLUE
230 V - 50Hz
1
2
3
4
5
6
7
8
9
10
II
A1
A2
A3
A4
A5
A6
N
L1
L1
'
M
T1T2
1
2
A7
T3T
4
VI
1
2
3
4
5
A8
A9
A10
A11
IV
4
M
2
1
3
n
1
2
3
4
IX
L
H
BUS
1
2
3
III
IMP
0 -10
V
F17
F15
3
1
FBR
1
2
VIII
PT1000
F14
F13
1
2
V
SPF
F12
F1 1
VF
AF
KF
/ SPF
VF
F9
F8
F6
F5
F3
F2
F1
FBR
eBU
S
FA
0 -1
0 V
1
2
I
VII
6
7
8
9
10
1
2
3
4
5
1
2
1
NL
1L
1
M1
M2
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
IG
1
2
3
Y2
4
5
6
7
Y3
1
2
3
Jp1
1
2
3
Y4
4
DL1 DL2
DL3
1
2
3
Y1
4
5
6
A1
SW1
0-
10
V
M
o
dbu
s - B
Mo
db
us
- A
PLC /
BMS
BCM
eB
U
S
-
eB
U
S
+
+
24
V
PR
IG
GREY
PINK
WHITE
WHITE
BLACK
BROWN
BR
O
W
N
BL
A
C
K
RE
D
M3
BROWN
VT
( -
)
( -
)
( +
)
KF
5
BROWN
15
14
LIGHT BLUE
BROWN
BLUE
BLUE
BROWN
BLUE
BROWN
BROWN
BROWN
BLUE
BLUE
1
2
C
ORANGE
ORANGE
BROWN
RELE'
5
1
2
3
SL
WHITE
BLUE
BROWN
1a
1b
TLG
BROWN
LTLG
7 moduls
2 to 6 moduls
II
I
O
1
1a
1b
SE8/BCM
BROWN
BL
AC
K
CONTROL E8
MAIN SUPPLY
CONNECTION
WIRE NEUTRAL (N)
CONTROL
MODULATION
PUMP
SI
G
N
A
L
AL
AR
M
PU
M
P
B
O
IL
ER
C
I
R
C
U
I
T
RE
S
E
T
IN
SER
T
BCM
eBUS
remote
(
Cascade manager)
external
PI
N
K
GR
E
Y
ORANGE +
BLACK (-)
BROWN (PWM)
BLUE (TACHO)
LIGHT BLUE (N)
BROWN (L1)
YEL/GREEN
WHITE
WHITE
LI
G
H
T
B
L
U
E
BR
O
W
N
YEL
L
-
G
R
EE
N
WHITE
LI
G
H
T
B
L
U
E
LI
G
H
T
B
LU
E
BR
O
W
N
WH
I
T
E
YEL
L
-
G
R
EE
N
LI
G
H
T
B
LU
E
LI
G
H
T
B
LU
E
ARANCIO +
NERO (-)
MARRONE (PWM)
BLU (TACHO)
AZZURRO (N)
MARRONE (L1)
PV1
GIA/VER
SMG
WHITE
NE
RO
BR
O
W
N
BL
U
E
BL
U
E
RED
Note: The pictures shown on the actual
wiring diagram, is purely indicative.
back
31
Instructions for the installer
0
0
0
0
0
0
0
1
1
1
1
1
1
1
2
2
2
2
2
2
2
3
3
3
3
3
3
3
4
4
4
4
4
4
4
5
5
5
5
5
5
5
6
6
6
6
6
6
6
7
7
7
7
7
7
7
8
8
8
8
8
8
8
9
9
9
9
9
9
9
Module 1
(Pos 0)
Module 2
(Pos 1)
Module 3
(Pos 2)
Module 4
(Pos 3)
Module 5
(Pos 4)
Module 6
(Pos 5)
Module 7
(Pos 6)
Setting of modules
selectors
Gas pressure swich
Fan pressure swich
High limit thermostat
Global
Ionization
Main switch
Global Flow Temperature Sensor E8
Minimum (not
supplied)
Global Flow Temperature Sensor BCM
Local Flow NTC Temperature sensor
Local Flow NTC Temperature sensor
Global Return NTC Temperature sensor
Local High limit thermostat
Gas Valve
Ignition Transformer
Modulating Fan
Ignition electrode
electrode
High limit thermostat
PG
SR
SR
SRR
TL
TL 1....7
TLG
VG
E.ACC 1....7
E.RIL 1....7
IG
KF
PV 1....7
SMG
1....7
1....7
TRA.ACC 1....7
VM 1....7
TR.ACC.1
E.ACC.1
VG1
TL2...TL7
PV2...PV7
SR2...SR7
25
4
1L
1
N
PE
RI
L
.
/RE
G
.
AL
I
M
.
23
0V
43
2
Y1
1
+ 2
4
V
eB
U
S
+
eB
U
S
-
E.RIL.2...E.RIL7
2° - 7° Modul
TR.ACC.2...TR.ACC.7
E.ACC.2...E.ACC.7
VG2...VG7
RE
D
RE
D
BR
O
W
N
BL
AC
K
ORANGE +
BLACK (-)
BROWN (PWM)
BLUE (TACHO)
LIGHT BLUE (N)
BROWN (L1)
WHITE
WHITE
YEL/GREEN
PI
N
K
GR
E
Y
PI
N
K
GR
E
Y
LI
G
H
T
B
L
U
E
BR
O
W
N
YEL
L
-
G
R
EE
N
3° - 7° MODUL
3° - 7° MODUL
WHITE
LI
G
H
T
B
LU
E
LI
G
H
T
B
LU
E
BR
O
W
N
WH
I
T
E
YE
L
L
-
G
R
EE
N
LIGHT BLUE
LIGHT BLUE
BROWN
BROWN
LI
G
H
T
B
LU
E
BR
O
W
N
YEL
L
-
G
R
EE
N
RE
D
YEL
L
-
G
R
EE
N
LIGHT BLUE
LIGHT BLUE
BROWN
BROWN
LI
G
H
T
B
LU
E
BR
O
W
N
back
32
Instructions for the installer
3.23 - WIRING DIAGRAM FOR CONNECTIONS AND MANAGING
On the back side of the E8 regulator there are two terminal
blocks, of which one is for the mains (230 V) connections and
the other one is for the low
voltage connections.
The main controls, necessary for the C.H. system
management and for the boiler control, as well some
components which are part of the boiler house, must be
connected to the terminal blocks.
Power terminal assignments
Power
terminal
block
Sensor
terminal
block
1
2
3
4
5
6
7
8
9
10
II
A1 A2 A3 A4 A5
A6
N L1 L1'
M
T1 T2
1
2
A7
T3 T4
VI
1
2
3
4
5
A8 A9
A10 A11
IV
4
M
2
1
3
n
1
2
3
4
IX
L H
BUS
50 Hz 230 V
1
2
3
III
IMP
0-10 V
F17
F15
3
1
FBR
1
2
VIII
PT1000
F14 F13
1
2
V
SPF
F12 F11
VF
AF
KF / SPF
VF
F9 F8
F6 F5
F3 F2 F1
FBR
eBUS
FA
0-10 V
1
2
I
VII
6
7
8
9 10
1
2
3
4
5
N L1 L1 1 2
1
Power supply
PI
N
K
GR
E
Y
From BCM
BL
U
E
BR
OW
N
BL
AC
K
Terminal II
II
A1
A2
A3
A4
A
5
A6
NL
1
L
1
'
M
T1
T2
67
89
1
0
1234
5
NL
1
L
1
12
1
II
N:
L1:
L2:
:
:
:
:
:
Neutral conductor, mains
Power supply, unit
Power supply to relay
heating circuit pump HK 1
heating circuit pump HK 2
Storage tank charging pump
Mixer open, heating circuit 2
Mixer closed, heating circuit 2
12
A7
T3
T4
V
I
Terminal VI
VI
123
45
A8
A
9
A1
0
A
1
1
I
V
4
M
2
1
3
n
Terminal IV
IV
:
:
Mixer open, heating circuit 1
Mixer closed, heating circuit 1
Multifunction relay
Multifunction relay
Recycle pump /
2
1
4
3
back
33
Instructions for the installer
Sensor terminal assignments
Connection to BCM
For connection to remote control devices
Terminal VII
VII
eB
US
FA
0-
10
V
1
2
VI
I
Pin 1:
Pin 2:
eBUS (FA) or 0-10V output
(Ground)
Terminal I
I
1
2
3
4
5
6
7
8
9
10
AF
KF
/
S
P
F
VF
F9
F8
F6
F5
F
3
F2
F
1
FB
R
I
Pin 4:
Pin 5:
Pin 6:
Pin 7:
Pin 8:
Pin 9:
Pin 10:
Flow sensor, heating circuit 2 (ground)
Flow sensor, heating circuit 2
Storage tank sensor
Storage tank and boiler sensor (ground)
Boiler sensor
Outdoor sensor
Outdoor sensor (ground)
VF
VF
SPF
SPF
KF
AF
AF
Buffer storage tank low sensor
Buf. stor. tank middle sensor / FBR heat. circ. 1 (room sensor)
Buf. stor. tank top sensor / FBR heat. circ. 1 (set value)
1
2
V
SP
F
F1
2
F
1
1
VF
Terminal V
V
VF
SPF
Pin 1: Flow sensor heating circuit 1 / sensor multifunction 1
Pin 2: Service water low sensor / sensor multifunction 2
1
2
VI
I
I
P
T
1000
F1
4
F
1
3
Terminal VIII
F13
F14
Pin 1: Sensor HS2 / Solar 2 / Multifunction relay 3
Pin 2: Sensor Solar 1 / Sensor multifunction relay 4
Terminal III
III
1
2
3
II
I
IM
P
0-
10
V
F1
7
F
1
5
3
1
FB
R
Pin 1:
Pin 2:
FBR heating circuit 2 (room sensor) / 0-10V IN / Light
FBR heating circuit 2 (ground)
F15
F17
Pin 3: FBR heating circuit 2 (set value) / Pulse counter for
1
2
3
4
IX
LH
BU
S
Morsetto IX
IX
H
CAN Bus Pin 1 = H (Data)
CAN Bus Pin 2 = L (Data)
CAN Bus Pin 3 = - (ground, Gnd)
CAN Bus Pin 4 = + (12V supply)
L
-
+
back
34
Instructions for the installer
3.24 -
INSTALLATION EXAMPLES (functional wiring and connections description)
INSTALLATION OF A BOILER WITH CONNECTION TO A DIRECT HEATING ZONE
INSTALLATION OF A BOILER WITH CONNECTION TO TWO DIRECT HEATING ZONES + D.H.W. PRODUCTION
(9-10) outdoor sensor
(6-7) Storage tank sensor
(4) Pump heating circuit 1
(5) Pump heating circuit 2
(6) Cylinder charging pump
SPF
AF
n
(5) Re-circulation pump storage tank
VF
(4-5) Flow sensor heating circuit 2
(9-10) outdoor sensor
(4) Pump heating circuit 1
AF
(1) Flow sensor heating circuit 1
VF
10
I
(10) Ground outdoor sensor
(4) Collector pump
(4) Collector pump
M
R
Safety devices
3
AF
VF
1
VF
VF
Mixing Header
Filter
Primary
system pump
Heating Circuit 1
Outside
Sensor
*
(1) Flow sensor heating circuit 1
VF
10
I
(10) Ground outdoor sensor
M
R
F
Ric.
C
VF
VF
SPF
1
2
n
4
3
VF
VF
VF
AF
Filter
Heating Circuit 1
Heating Circuit 2
Outside
Sensor
Mixing Header
Safety devices
Primary
system pump
*
**
This sensor can also remain unused
necessary for enabling 2° circuit
**
This sensor can also remain unused
*
*
back
35
Instructions for the installer
INSTALLATION OF A BOILER WITH CONNECTION TO TWO MIXED ZONES + D.H.W. PRODUCTION
(9-10) outdoor sensor
(4-5) Flow sensor heating circuit 2
(Optional)
(6-7) Storage tank sensor
(4) Pump heating circuit 1
(5) Pump heating circuit 2
(6) Cylinder charging pump
(7) Mixer motor heating circuit 2 OPEN
(8) Mixer motor heating circuit 2 CLOSE
INSTALLATION OF A BOILER WITH CONNECTION TO ONE MIXED AND ONE DIRECT HEATING ZONES + D.H.W. PROD.
SPF
AF
(1) Mixer motor heating circuit 1 OPEN
(2) Mixer motor heating circuit 1CLOSE
n
(5) Re-circulation pump storage tank
VF
(7) Mixer motor heating circuit 2 OPEN
(8) Mixer motor heating circuit 2 CLOSE
n
(5) Re-circulation pump storage tank
(9-10) outdoor sensor
(6-7) Storage tank sensor
(4) Pump heating circuit 1
(5) Pump heating circuit 2
(6) Cylinder charging pump
SPF
AF
VF
(4-5) Flow sensor heating circuit 2
(4) Collector pump
(4) Collector pump
(1) Flow sensor heating circuit 1
VF
10
I
(10) Ground outdoor sensor
M
R
F
Ric.
C
VF
VF
SPF
2
1
n
4
3
VF
VF
VF
AF
Filter
Heating Circuit 1
Heating Circuit 2
Outside
Sensor
Mixing Header
Safety devices
Primary
system pump
*
(1) Flow sensor heating circuit 1
VF
10
I
(10) Ground outdoor sensor
Filter
Heating Circuit 1
M
R
F
Ric.
C
VF
Heating Circuit 2
VF
SPF
1
2
n
4
3
VF
VF
VF
AF
Outside
Sensor
Mixing Header
Safety devices
Primary
system pump
*
This sensor can also remain unused
*
necessary for mixing valve control
*
back
36
Instructions for the installer
INSTALLATION OF A BOILER WITH CONNECTION TO TWO MIXED ZONES + D.H.W. PRODUCTION BY SOLAR PANELS
(9-10) outdoor sensor
(4-5) Flow sensor heating circuit 2
(optional)
(6-7) Storage tank sensor
(4) Pump heating circuit 1
(5) Pump heating circuit 2
(6) Cylinder charging pump
SPF
AF
n
(5) Re-circulation pump storage tank
VF
V
(2) Hot water tank low / Multifunction relay sensor 2
(optional)
(2) PT1000 sensor solar 1 / Multifunction relay sensor 4
(optional)
PT1000
For the connection to a solar installation it is
necessary to change some parameters. See
Table:
Expert AREA
Þ
Level SOLAR / MF
Þ
MF 4
FUNCTION = `'23''
(4) Collector pump
(7) Mixer motor heating circuit 2 OPEN
(8) Mixer motor heating circuit 2 CLOSE
(1) Mixer motor heating circuit 1 OPEN
(2) Mixer motor heating circuit 1CLOSE
(1) Flow sensor heating circuit 1
VF
10
I
(10) Ground outdoor sensor
M
R
C
VF
VF
SPF
1
2
VF
VF
VF
AF
F
A11
5
4
PT1000
2+
F14
F12
2+
3
Mixing Header
Filter
Heating Circuit 1
Outside
Sensor
Heating Circuit 2
Safety devices
Primary
system pump
*
necessary for mixing valve control
*
back
37
Instructions for the installer
INSTALLATION OF A BOILER WITH CONNECTION TO TWO MIXED ZONES + D.H.W. PRODUCTION
Connections on to the MASTER controller
The connections of the secondary circuit have to be done on
to the MASTER controller.
n
(5) Re-circulation pump storage tank
ATTENTION!
In this type of installation it is necessary to adjust,
in the E8 controller, the parameter BUS-ID HS.
The external regulator E8 (MASTER) has to be set to:
----,
the boiler regulators E8 (SLAVES) have to be set to:
01 to 08.
(4) Collector pump
M
R
F
Ric.
C
VF
VF
SPF
1
2
n
4
3
VF
VF
VF
AF
M
R
3
Slave 1
Slave 2
KF
Filter
Heating Circuit 1
Outside
Sensor
Filter
Heating Circuit 2
Remote
E8
Master
Mixing Header
Safety devices
Primary
system pump
Safety devices
Primary
system pump
Boiler
Sensor
*
(1) Flow sensor heating circuit 1
VF
10
I
(10) Ground outdoor sensor
(9-10) outdoor sensor
(4-5) Flow sensor heating circuit 2
(optional)
(6-7) Storage tank sensor
(4) Pump heating circuit 1
(5) Pump heating circuit 2
(6) Cylinder charging pump
SPF
AF
VF
(7) Mixer motor heating circuit 2 OPEN
(8) Mixer motor heating circuit 2 CLOSE
(1) Mixer motor heating circuit 1 OPEN
(2) Mixer motor heating circuit 1CLOSE
necessary for mixing valve control
*
back
38
Instructions for the installer
3.25 - CASCADE MANAGER (BCM)
Application
:
The BCM completes the range of functions offered by the
Imax Plus boilers:
- ON/OFF alarm control
- Control of a modulating header pump with the aim of
significantly increasing efficiency at low heating loads.
- Possibility of integrating the
Imax Plus boilers in PLC
controlled boiler plants
- Thanks to LonWorks/Modbus protocol converters been
readily available also opens the road to installing
Imax Plus boilers in the most advanced Building
Automation Systems.
Features
:
The BCM can be connected to the automation system of
a boiler plant via one of its interfaces:
- eBUS: for connection to the series of E8 heating
controllers or to an additional BCM
- Modbus: application in PLC controlled boiler plants
The communication protocols enable complete system
management:
- Control of heating request: temperature set point and
modulation level
- Monitoring of boiler operation and temperature status
- Alarm control
- Functional parameters setting
Management of the header pump:
- Relay command for running a pump at fixed rate
- 0
-10 analogical output for control of a modulating pump
Special functions
Emergency: it avoids system shutdown caused by an
interruption in communication with the boiler plant's
automation system:
- Input for "Constant setpoint" request: 55°C, maximum
output 50%
- Alarm reset input
- Alarm relay signal
Monitor
:
a BCM connected to a group of heating generators
managed by a E8 heating controller, automatically selects
the "monitor" mode.
In this condition the following services are supplied:
- Acquisition of all the operating data and diagnostics via
the Modbus interface.
- Control of the modulating pump
- Control of the Alarm relays and control of the header
pump
- If the E8 malfunctions, the BCM automatically resets
normal boiler operation control and can enable the
emergency function previously described.
back
39
Instructions for the installer
Connection for boilers in a cascade arrangement managed by a E8 heating controller with PLC supervision.
WARNING!
In this connection the "BUS-ID HS,,
parameter must be set on the E8 heating
controller
The external E8 heating controller (MASTER) must be
set to: - - - -,
The E8 heating controllers fitted on each boiler (SLAVE)
must be set from: 01 to 08.
1
2
3
Y2
4
5
6
7
Y3
1
2
3
Jp1
1
2
3
Y4
4
DL
1
DL
2
DL
3
1
23
Y1
45
6
A1
SW
1
Modbus - B
Modbus - A
BC
M
eBUS -
eBUS +
+ 24 V
System Supervisor
PLC/BMS board
Modbus
II
A1
A2
A3
N
L1
L1
'
1
2
3
4
IX
LH
BUS
1
2
3
III
IM
P
0-
10
V
F1
7
F
1
5
31
FB
R
1
2
V
III
P
T
1000
F1
4
F
1
3
2
V
SPF
F1
2
F1
1
6
123
45
12
NL
1
L
1
1
2
3
4
IX
L
H
BUS
E8
Cascade Manager
- System Supervisor
E8
CanBUS
- Cascade Manager
PLC/BMS board
SLAVE 1
SLAVE 2
MASTER
Modbus
Change-over
in II position
I = Comunication
by MODBUS
II = Comunication
by E8
Position II
back
40
Instructions for the installer
Connection for boilers in a cascade arrangement connected to an external BCM and managed by PLC/BMS
(E8 disconnected).
WARNING!
In this connection the E8 heating controller
has to be disconnected from the eBUS on
the BCM board.
- Cascade Manager
- System Monitor
BCM board
eBUS
Modbus
- System Manager
- System Supervisor
PLC/BMS board
Modbus
0
1
2 3 4
5
6
78
9
BCM
(Pos 0)
0
1
2 3 4
5
6
78
9
BCM
(Pos 1)
0
1
2 3 4
5
6
78
9
BCM
(Pos 2)
The applications in a cascade arrangement
managed with an additional BCM or controlled
via Modbus also require the correct boiler
address setting within the cascade formation
via the BCM's internal SWI selector: 0....7, all
different and in sequence, exactly as
requested by the single burner modules.
1
2
3
Y2
4
5
6
7
Y3
1
2
3
Jp1
1
2
3
Y4
4
DL
1
D
L
2
DL
3
1
23
Y1
45
6
A1
SW
1
eBUS remoto
BC
M
eBUS -
eBUS +
+ 24 V
eBUS
Modbus
- System Manager
- System Supervisor
PLC/BMS board
Modbus
- Cascade Manager
- System Monitor
- System Manager
- System Supervisor
BCM board
eBUS remoto
Change-over
in I position
I = Comunication
by MODBUS
II = Comunication
by E8
Position I
back
41
Instructions for the installer
Connection for boilers in a cascade arrangement managed by an external PLC (E8 disconnected)
WARNING!
In this connection the E8 heating controller
has to be disconnected from the eBUS on
the BCM board.
1 for each multiple boiler formation
- System Supervisor
- Cascade Manager
PLC/BMS board
Modbus
1
2
3
Y2
4
5
6
7
Y3
1
2
3
Jp1
1
2
3
Y4
4
DL
1
D
L
2
DL
3
1
23
Y1
45
6
A1
SW
1
Modbus - B
Modbus - A
BC
M
eBUS -
eBUS +
+ 24 V
System Supervisor
PLC/BMS board
Modbus
Cascade Manager
Change-over
in I position
I = Comunication
by MODBUS
II = Comunication
by E8
Position I
back
42
Instructions for the installer
The BCM board monitors the data of the thermal head (Dt
between primary flow and return and supplied
heat
output). When the supplied heat output diminishes,
the
number of the pump's revolutions decreases and
subsequently the hourly rate, maintaining the thermal head
practically constant
, thus obtaining a higher efficiency in
condensing mode and reducing energy costs.
3.26 - CONFIGURATION WITH A:
The 0-10 Volt modulation signal is preset to:
-3 for minimum speed
-10 Volt for maximum speed
These values can be changed according
to the type of pump fitted. For further
information on the 0-10 Volt signal, please
also refer to the pump manual.
MODULATING PUMP
ON-OFF PUMP
MODULATING PUMP
1
2
3
Y2
4
5
6
7
Y3
1
2
3
Jp1
1
2
3
Y4
4
DL1 DL2
DL3
1
2
3
Y1
4
5
6
A1
SW1
PUMP
BCM
eB
U
S
-
eB
U
S
+
+ 2
4
V
N
L1
N
L1
P
N
L
POWER TERMINALS E8
AL
AR
M
Mains supply
230 V - 50 Hz
RELAY
Mains supply
230 V - 50 Hz
1
2
3
Y2
4
5
6
7
Y3
1
2
3
Jp1
1
2
3
Y4
4
DL1 DL2
DL3
1
2
3
Y1
4
5
6
A1
SW1
BCM
eB
U
S
-
eB
U
S
+
+
24
V
N
L1
N
TERMINALS 0-10 V
INTERFACE
WILO MODULATING PUMP
(-)
(0
-
1
0
V
)
L1
Supply
Modulating
Pump
APM
AL
ARM
Mains supply
230 V -50 Hz
back
43
Instructions for the installer
3.27 -
FILLING THE SYSTEM
Warning!
Always mix the CH system water with anti-
freeze or anti-corrosion solutions using the
correct concentration! Failure to do so could
cause damage to the washers and create
noise during normal boiler operation.
Ideal Boilers refuses all liability for injury to
persons, animals or damage to property
resulting from not following the above
mentioned recommendations.
The system itself shall be equipped with its own drain tap,
whose size depends on the system capacity. The
fitting
of a filter on the return pipe to the boiler is advisable.
back
44
Instructions for the installer
Follow this procedure also for the other
burners
If the CO
2
percentage is too low, check if the air and
flue
ducts are not obstructed. If they are not obstructed, check if the
burner and/or the exchanger (aluminium sections) are well
cleaned.
B)
MINIMUM OUTPUT ADJUSTMENT
-
Force the desired burner
to be working at minimum
output (CASCADE MAN 10%)
-
Check that the C0
2
values are within the values indicated
in the table "Burner pressures"
-
If necessary correct the value by turning the
adjustment screw "B" in a CLOCKWISE direction to
increase the value and in an ANTICLOCKWISE
direction in order to decrease it.
A)
MAXIMUM OUTPUT ADJUSTMENT
-
Remove the cap of the combustion gases sampling point
-
Connect a suitable C0
2
gas analyser to the sampling point
in the flue outlet terminal.
-
Force the desired burner
to be working at nominal output
(CASCADE MAN 100%)
-
Check that the C0
2
values are within the values indicated
in the table "Burner pressures"
-
If necessary correct the value by turning the adjustment
screw "A" in a CLOCKWISE direction to decrease the
value and in an ANTICLOCKWISE direction in order to
increase it.
Flue sampling point
3.28 -
BURNER ADJUSTMENT
WARNING!
All the instructions indicated below are for the
exclusive use of qualified Ideal Boilers
service technicians or installers.
All the boilers are supplied already calibrated
and tested.
MAXIMUM OUTPUT
ADJUSTMENT SCREW
MINIMUM OUTPUT
ADJUSTMENT
SCREW
back
45
Instructions for the installer
Check the C0
2
levels often, especially at low flow rate
INJECTORS PRESSURES
CO
2
levels (%)
Gas type
Supply
pressure
(mbar)
Starting
power
IG
(%)
Ø
Injectors
( m m )
Fan speed
Diaphragm
C)
COMPLETION OF THE BASIC
ADJUSTMENTS
-
Check the C0
2
values at the minimum and maximum outlet