background image
range
W, Plus
Condensing boilers 45-280kW
Commercial & Industrial Boilers
background image
Contents
Introduction
3
The Range
4 - 5
Product specification
6 - 9
Option kits
10 - 11
Flueing
12 - 15
System requirements
16 - 19
General & performance data
20 - 21
Dimensional data
22 - 23
the range
2
W
Plus
background image
W
The Ideal W wall mounted boiler comes in a range of outputs
45, 60 or 80kW and all are capable of being installed as a single
unit or in simple modular formations for even bigger outputs. The
W is a highly efficient fully condensing boiler - up to 98%
efficient nett (88.5% gross) non condensing and an impressive
108% nett (97.3% gross cv) at 30% load, fully condensing. Even
higher efficiencies are achieved at lower system temperatures. The
fully modulating gas/air design ensures that maximum efficiency is
maintained down to very low loads reflecting the needs of modern
systems. At its heart is a robust cast aluminium heat exchanger
providing a compact, space saving design making this the ideal
boiler for plant rooms where space is at a premium.
Ideal boilers are fan assisted and have been designed with
siting flexibility in mind. Flues can be concentric, twin duct, room
sealed or open flued in single or multiple installations. It is one of
the easiest commercial boiler ranges to install and service.
The premix burner design ensures the lowest level of emissions. The
range has been approved to the most stringent European Standards
governing safety and performance of commercial boilers and is
classified as low NOx (Class 5).
The Ideal W incorporates an advanced microprocessor based
control system which operates all electrical functions of the boiler
including ignition, flame detection, temperature control and burner
modulation. In addition the system has full commissioning and fault
diagnostic displays.
The boilers are offered with an extensive range of option kits
including flues, system controls and modular header kits for
maximum flexibility and ease of specification.
Conforms with all relevant
European standards and
requirements
modulation to low outputs for
high operating efficiencies
Plus
The Plus extends the Ideal condensing boiler range with
outputs from 80kW to 280kW in a range of six compact floor
standing boilers and can be installed in multiple formation to provide
even larger outputs if the system requires.
High efficiencies are the norm for boilers and the Plus
is up to 96.6% efficient nett (87% gross cv) non-condensing, and
108.4% nett (97.7% gross cv) at 30% load. Even higher efficiencies
are achieved at lower temperatures. The fully modulating gas/air
design ensures maximum efficiency is maintained down to as low as
11.6kW output. This class-leading figure is achieved even with the
largest model as the unique Plus design optimises load
matching. The robust cast aluminium heat exchanger comprises of
several sections, each flueway or module has its own burner fan, gas
valve, ignition and safety controls and after all have modulated down
to their combined minimum, modules are switched off to further
match a reducing system load. Wasteful on/off cycling is reduced to
the absolute minimum with the Plus, and a further benefit is
that standby support is built into the design.
Plus boilers are designed for ease of installation and the flue
can be positioned to left, right or rear, whilst system and gas
connections can be made to left or right of the boiler. All to ensure
boiler house siting is as simple and fast as possible.
Naturally the range meets the most stringent European Standards
governing safety and performance and is classified as low NOx (Class
5). It is also the quietest boiler of its size at less than 50dBA.
The Plus uses advanced microprocessor based controls to
operate all electrical functions and provides full commissioning and
fault diagnostic displays. Furthermore it takes into account each
modules' operating hours and evens out their usage. Further benefits
are that Hours Run Meters and BMS control is built-in as standard,
whilst an outside sensor for weather compensation is supplied with
each boiler.
3
Introduction
Customers increasingly demand higher efficiencies and lower emissions from the heating plant. All this must be achieved in ever smaller
dimensions. Ideal now provide a range of solutions with the high efficiency condensing wall hung boilers and Plus floor standing range.
background image
The W
control panel
W
45 - 80kW
·
High operating efficiencies with close load matching
·
Natural gas and propane
·
Single unit or modular configuration, wall or frame mounted
·
Wide modulating output range from 13 - 80kW
·
Robust cast aluminium heat exchanger
·
Integral commissioning and fault diagnostics
·
Flue flexibility, concentric and twin duct, room sealed or open
flue applications
·
Easy to install and service
·
Simple UK voltage system controls wiring
·
Comprehensive control options
·
Meets Building Regulations 2000 (Part L)
the range
4
background image
The Plus
control panel
(F120 shown)
Plus
80 - 280kW
·
Range of six models from 80 - 280kW
·
Compact size - small footprint
·
High modulation - Close load matching (all models down to
11.6kW)
·
108.4% Net efficiency (fully condensing) at 30% part load
·
Boilers consist of several modules giving built-in standby
capability
·
Robust cast aluminium heat exchanger
·
Integral commissioning and fault diagnostics
·
Optional flue and system connections for fast installations
·
Meets Building Regulations 2000 (Part L)
5
background image
Performance
The Ideal range offers high operating efficiencies,
together with the lowest possible emissions, and is certified to
comply with the Gas Appliance Directive (90/396) and the Boiler
Efficiency Directive (92/42), the European Directives governing
safety and performance of gas boilers ensuring high quality
performance.
The design of the boiler ensures high efficiencies at both full
and part loads to meet the new `Building Regulations 2000'
conservation of fuel and power. Approved efficiencies are up to 98%
at 80°C flow based on net calorific value of fuel (88.5% gross) at full
load. At 30% part load the efficiencies exceed 108% net (97.3%
gross).
Electrical Controls
The boilers incorporate an advanced microprocessor based
control system which operates all electrical functions of the boiler
including ignition, flame detection, flow/return temperature sensors
and output modulation. In addition the microprocessor displays
boiler status and a fault diagnosis program.
Boiler
Range
Certificate No.
Notified Body
Reference
W
W45 - 80
0063BN3218I
Gastec NV
0063
Plus
F80 - 280
49BM3615
AFNOR, Paris
0049
Boiler Operation
W
On a call for heat, air is drawn into the boiler variable speed fan.
The fan inlet incorporates a special mixing arrangement for gas
supplied from the gas valve. The gas/air mixture is automatically
ignited at low rate beneath the burner via a spark electrode and
ignition proved by a flame rectification electrode. The flue gases pass
downwards through the heat exchanger and via the sump and flue
outlet to atmosphere. A plume of vapour will be visible at the
terminal due to the low exit temperature.
The boiler modulates its output according to demand via the
flow/return sensors and any external controls. The fan speed and gas
flow are adjusted under this electronic control to provide the correct
mixture and output. This maintains high efficiency part loads.
Condensation within the boiler will start to occur when the
return temperature is below the dew point (55°C). The flue gases will
condense and increase boiler efficiency by giving up their latent heat
to the system. Condensation formed within the boiler is removed via
the integral drain.
Plus
When the boiler receives a call for heat, the boiler control
Modular Boiler Drive (MBD) calculates the necessary output
according to the difference between the set flow temperature (or
compensated flow temperature for a CH call when using an outside
sensor) and the boiler modules' combined flow temperature. The first
module fan operates and the gas/air mixture is automatically ignited
below the burner via a spark electrode and proved by a detection
electrode. Ignition occurs in 5 seconds and once detected the
module starts operating. Subsequently, additional modules will fire
to provide the load required.
The boiler principle method of operation is to run as many
modules simultaneously, at the lowest possible load, for maximum
efficiency e.g.
If an F160 with 160kW max. output is only requested to provide
72kW.
72 / 4 = 18kW per module
Therefore, the boiler operates all modules at the reduced rate of
18kW. If the required load is less than the min. 12kW per module,
then one module after the other will automatically shut down and the
load shared by the remaining modules. The modules with the lowest
number of hours run are automatically chosen to satisfy the demand.
In order to give you assurance and peace of mind a Certification of
Compliance to the Building Regulations 2000 can be obtained from
the commercial heating department.
product specification
6
background image
Quality
As with all Ideal boilers, the W & Plus boilers are
engineered to the highest quality standards. Ideal Boilers products
meet or exceed the requirements of all relevant standards. Before
despatch each boiler is fired and fully tested. The control valves are
also adjusted to give the correct gas flow rate. Ideal Boilers are
recognised as a World Class Manufacturer.
assurance of quality
BS EN ISO 9001: 2000
Packing
The Ideal is despatched from works in separate packs
as follows:
W contains:
Plus contains:
Complete boiler
Assembled boiler body
with separate:-
Casing pack
Flue option packs
Condensate pipe & fixings
Control option packs
Flue manifold, socket & gasket
Modular header kits
Outside sensor pack
A full commissioning service is available at an extra charge.
System Application
Ideal boilers are designed for central heating of large
domestic and commercial premises and also for supplying domestic
hot water via a calorifier or plate heat exchanger. They are suitable
for fully pumped, open vented or pressurised systems and can be
connected to heating and/or domestic hot water systems.
They are not suitable for direct hot water supply or gravity
heating/hot water systems.
W
Plus
Maximum static head:
40.7 metres
61 metres
(134 feet)
(200 feet)
Maximum working pressure:
4 bar
6 bar
(58.7psi)
(87psi)
Maximum design flow temperature is 82°C (180f)
(This is adjustable to 90°C if required at the control panel).
Pump overrun is provided as standard, and a period of 5 minutes
must be allowed for in system design.
Frost protection is built into the boiler control, if the boiler sensor
falls below 7°C, this will result in the appliance firing.
This will protect the boiler only, not exposed system elements.
7
background image
1.
Jacket side panel
2.
Jacket front panel assy.
3.
Controls fascia
4.
Controls door assy.
5.
Wall mounting plate
6.
Internal flue tube
7.
Air pressure switch
8.
Fan
9.
Mounting plate manifold
10.
Gas valve
11.
Upper gas pipe
12.
Lower gas pipe
12A. Gas pipe
13.
Sight glass complete
14.
Ignition/detection electrode
15.
Auto air vent
16.
Manifold flow
17.
Heat exchanger assy.
18.
Inspection cover assy.
19.
Condensate outlet pipe
20.
Manifold return
21.
Thermistor flow or return
22.
Transformer
23.
Control module
24.
Pressure gauge
25.
Water pressure switch
31.
Gas manifold
(W80 model shown)
W45 & W60
product specification
8
W Boiler Construction
Ideal W wall mounted boilers are constructed from cast
aluminium heat exchangers with tubular steel flow and return manifolds.
The heat exchanger is mounted in a sealed white enamelled
steel casing.
A premix downfiring burner is mounted above the heat exchanger.
A cast aluminium sump is fitted below with condensate drain
connection.
The concentric flue outlet and air inlet is positioned on the
boiler top, with gas and system connections at the base.
Controls are accessible behind a drop down door. Maintenance
and servicing is all achieved from the boiler front.
background image
9
Plus Boiler Construction
The construction of the Plus sectional heat exchanger
design is of cast aluminium. Individual downfiring burners, fans, gas
valves and ignition safety controls for each flueway or module are
provided. A non-return valve ensures no reverse circulation of flue
products through modules not operating. A stainless steel sump
collects the flue products and diverts them to the flue, whilst
allowing drainage of condensate products.
background image
Option Kits
Modulating sequencer kit
Programmable room thermostat kit
Control interface kit
Outside sensor kit
*
Tank sensor kit
Remote indication kit
*
Hours run meter(s)
*
*
BMS (0-10V) kit
*
Pump kit
Multi boiler frame and header kits
*Provided as standard
W
Plus
option kits
Control Interface Kit
Remote Indication Kit
Programmable Room
Thermostat Kit
Modulating Sequencer Kit
Tank Sensor Kit
BMS (0-10v) Kit
Outside Sensor Kit
10
The boiler range comes with a host of options designed to
give greater flexibility and control to your heating system.
W Flue Kits
Horizontal wall flue kit
A range of concentric flue pipes
together with wall mounted grille for
horizontal flue applications.
Vertical roof flue kit
A range of concentric flue pipes
together with terminal grille for roof
flue applications.
Twin pipe flue kits
Air and flue pipe terminals for extra
long runs using twin ducts.
Open flue kit
A range of air inlet grilles for direct
installation to the boiler with flue
connection.
For more information see Flueing page 12.
Flue Options
background image
W Multiple Boiler Frame Kit
W boilers are also designed for multiple boiler installations.
Such installations can be an advantage in many situations:
· Compact size means easier location, transportation and
handling.
· Close load matching means higher annual operating
efficiencies.
· Inherent reliability and service continuity. One boiler may be
shut down for servicing whilst the remainder continue
operating.
· A sequencer kit and multiple boiler pipework kits are available
for the W.
The header kit comes complete with all the components
necessary to complete a multiple installation:
· Gas and water headers (2 or 3 boilers)
· Mixing header
· Individual flow, return and gas connection pipework
incorporating isolating valves
· All necessary mounting brackets for pipework
Ideal W boilers are also designed for use with a boiler
frame mounting kit which allows boilers to be mounted onto a free
standing boiler frame rather than onto the wall.
This frame mounting kit is especially useful when wall space is
at a premium or wall condition is suspect. The frame mounting kit is
suitable for use with installations of 1 or more boilers.
1. Non-return valve
2. Safety valve
3. Service valve
4. Expansion vessel
5. Mixing header
6. Flow sensor
7. System pump
8. Modulating
Sequencer kit
9. Flue gas terminal
10. Room Temp. sensor
11. Drain cock
12. Outdoor sensor
W Multiple Boiler Kit Installations
1. Frame kit
2. 3 Blr. flow & return
header kit
3. 3 Blr. gas header kit
4. Connection kit
5. Mixing header
6. Pump
(For dimensions
see page 22)
11
Plus boilers are suitable for installations where the load
requires more than one boiler.
e.g. 2 x F280 = 560kW or in larger multiples
The flexibility of flue connection position (left, right or rear) and
system and gas connections (left or right) allows multiple boilers to
be sited more easily in confined boiler homes.
Plus boilers can be laid out for example with rears
towards each other and flues at the same end. Many more options
are possible to minimise plant room area.
Plus Multiple Boiler Installations
background image
concentric and
twin duct systems
W Flue Kits
W Only
The flue kits are suitable for use with the Ideal boiler only.
These kits and the associated options are suitable for both roof
and wall mounting applications.
Several flue options are available:
· Horizontal flue kits (80/125mm or 100/150mm dia.)
· Vertical roof flue kits (80/125mm or 100/150mm dia.)
· Twin pipe flue kits
· Open flue kits
The twin pipe flue kit is suitable where particularly long flue
runs are required and compact flue and air ducts are required.
The roof kit is suitable for both flat and pitched roof termination,
using a concentric flue (tube within tube) to run vertically from the
top of the boiler and terminating above the roof level.
If obstructions prevent direct flue routing then both 90° and 45°
elbows can be provided to offset any of the flue systems.
Accessories
Flue duct extension kits are available for flue lengths extending
beyond 1 metre. These packs contain additional 1 metre ducts and
may be cut to the desired length.
Elbows, 90° and 45°, are also available.
flueing
12
Weatherproofing
Where the flue passes through the roof line an adequate seal
must be made. This can be achieved by using either:
· Flat weather collar 125mm or 150mm
· Pitched weather collar 125mm or 150mm
Additional information covering selection and installation can be
found within this guide.
Flue Systems
To ensure safe and satisfactory operation, the boiler must be
connected to a chimney system capable at all times of adequately
evacuating the combustion products (see performance data table on
page 14 for approximate volumes).
The Ideal W & Plus boilers are suitable for use in
both room sealed and open flue fan assisted operation. Connections
for combustion air inlet and flue products discharge are located on
the top of the appliance ( Plus: separate vertical flue outlet to
left, right or rear, air inlet at left or right).
The jacket of the Ideal condensing boiler is constructed
such that it forms an air tight seal. It is therefore important that the
jacket of the unit is fitted properly whilst the boiler is in operation.
The boiler is suitable for use in either single or multiple flue
configurations and can be fitted with a wide variety of flue systems.
Horizontal flue runs MUST be inclined at 2.5° to the horizontal
in order that any condensate formed can be discharged through the
boiler.
W & Plus
All joints or connections in the flue system must be impervious
to condensate leakage and also any low points in the flue system
should be drained using pipe of material resistant to condensate
corrosion.
The flue duct termination point must be positioned so that it will
not be affected by adverse wind conditions and be free from any
obstructions. Note: A vapour plume will be visible at the terminal.
Therefore where possible terminal positions which could cause
problems due to plumeing should be avoided.
The use of a fan on the boiler permits long flue runs however,
the resistance of bends etc will reduce the overall length. Full details
of the W flue sizes and resistances can be found on page 13
of this booklet.
NO additional diverter, stabiliser, or draught break should be
installed in the chimney system without prior consultation with
Caradon Ideal Ltd.
Flues and terminal positions should be designed with strict
regard to the requirements of BS 5440: Part 1, BS 6644, IGE
UP/10 and the Building Regulations Part J as appropriate. Particular
attention should be paid to these for multiple boiler installations and
if required, the Clean Air Act.
background image
W Flue Termination Position
Concentric Wall Terminal Positions
Minimum spacing
A. Below an opening (1)
300 mm
12 in
B. Above an opening (1)
300 mm
12 in
C. Horizontally to an opening (1)
300 mm
12 in
D. Below gutters, soil pipes or drain pipes
75 mm
3 in
E. Below eaves
200 mm
8 in
F. Below balcony or car port roof
200 mm
8 in
G. From a vertical drain pipe or soil pipe
150 mm
6 in
H. From an internal or external corner or to a boundary alongside the terminal
300 mm
12 in
I.
Above ground, roof or balcony level
300 mm
12 in
J. From a surface or a boundary facing the terminal
600 mm
24 in
K. From a terminal facing the terminal
1200 mm
48 in
L. From an opening in the car port into the building
1200 mm
48 in
M. Vertically from a terminal on the same wall
1500 mm
60 in
N. Horizontally from a terminal on the same wall
300 mm
12 in
Concentric Roof Terminal Positions
Directly below an opening, air brick, windows, etc
300 mm
12 in
Below plastic/painted gutters
500 mm*
20 in
Below painted surface
500 mm*
20 in
Below eaves or balcony
500 mm
20 in
From wall
1000 mm
40 in
W Important - The boiler must be installed in a vertical position.
The pressure available at the boiler outlet is sufficient to
overcome the resistance of considerable flue lengths. The maximum
straight length of concentric flue may be as long as 31.6 metres,
dependent on model. A twin duct arrangement can be up to 29
metres combined flue and air pipes, with small wall terminals.
The maximum potential length for each flue type by boiler model
is shown in the table opposite, although allowances must be made
when elbows are used. The length to be subtracted for each elbow
used is also provided in the table below.
Maximum equivalent lengths (metres)
W45
W60
W80
Horizontal Wall Flue Kit 80/125
9.5
7.8
-
Horizontal Wall Flue Kit 100/150
31.6
26
16
Vertical Roof Flue Kit 80/125
9.5
7.8
-
Vertical Roof Flue Kit 100/150
31.6
26
16
Twin Pipe Flue Kit (W45 & W60 only)*
29
19
-
Open Flue Kit 80
20
13.3
-
Open Flue Kit 100
-
-
29
* Maximum combined air and flue ducts
Fitting equivalent lengths (metres)
W45
W60
W80
1 metre extension 80/125
1.0
1.0
-
1 metre extension 100/150
1.0
1.0
1.0
45° elbow 80/125
1.1
1.1
-
45° elbow 100/150
1.2
1.2
1.2
90° elbow 80/125
1.6
1.6
-
90° elbow 100/150
2.0
2.0
2.0
1 metre extension 80 dia. (Twin duct type)
1.0
1.0
1.0
90° elbow 80 dia. (Twin duct type) Air tube
1.4
1.4
-
90° elbow 80 dia. (Twin duct type) Flue tube
2.1
2.1
-
45° elbow 80 dia. (Twin duct type) Air tube
0.4
0.4
-
45° elbow 80 dia. (Twin duct type) Flue tube
0.6
0.6
-
Flue Data
If the terminal is fitted less than 500mm below
plastic gutters, painted eaves or any other painted
surface then an aluminium shield at least 1m long
should be fitted to protect the surface.
*
may be reduced to 300 mm if a shield fitted
(1) An opening here means an openable element, such as an openable window, or a fixed opening such as an air vent. However, in addition, the outlet should not be nearer
than 150 mm (fanned draught) to an opening into the building fabric formed for the purpose of accommodating a built in element, such as a window frame.
Plus
Proprietary flue systems are available for use with this range. A
pressure of 100Pa is available at the flue outlet.
13
background image
W Flue Designs
Flue designs are calculated against the maximum available
resistance using the flue data table on page 10. The examples
provided are given as a guide only, therefore a greater number of
variations can be obtained
Example of Calculating Flue Resistance/Lengths -
Horizontal Concentric Flue
Horizontal flue for W45 (80/125 dia.)
Part No.
Lengths (m)
Maximum equivalent length
9.5
Horizontal wall flue kit 80/125
158659
2 x 1m extension flue
152400
2
1 x 90° elbow
152616
1.6
Total length reduction
3.6
The total equivalent length reduction is 3.6 metres, which is less than the
maximum length possible of 9.5m. Therefore this arrangement is
satisfactory.
Example of Calculating Flue Resistance/Lengths -
Vertical Concentric Flue
Vertical Roof flue for W60 (80/125 dia.)
Part No.
Lengths (m)
Maximum equivalent length
7.5
Vertical flue kit 80/125
158654
2 x 1m extension flue
152400
2
2 x 45° elbows
152618
2.2
Total length reduction
4.2
The total equivalent length reduction is 4.2 metres, which is less than the
maximum length possible of 7.5m. Therefore this arrangement is
satisfactory.
flueing
14
background image
Example of Calculating Flue Resistance/Lengths -
Open Flue
Open flue for W60 (80 dia.)
Part No.
Lengths (m)
Maximum equivalent length
13.3
Open flue kit 80
158662
Vertical flue terminal 80
158769
2 x 1m twin extension pipes 80
158771
2.0
2 x 45° elbows 80
158775
2.0
Total length reduction
4.0
The total equivalent length reduction is 4.0 metres, which is less than the
maximum length possible of 13.3m. Therefore this arrangement is
satisfactory and a longer flue length is possible if required.
Example of Calculating Flue Resistance/Lengths -
Twin Duct
Twin Duct for W45 & W60(80 dia.)
Part No.
Horizontal flue terminal 80
158777
Horizontal air terminal 80
158778
1m flue extension pipes 80 (pair)
158771
90° elbow 80
158773
Calculation
1. Air pipe length Y = 8.5m.
2. Refer to graph below and plot vertical line on air axis at 8.5m as shown.
Where vertical line intersects the bold W45 line, read off maximum
allowable flue length.
In this example maximum straight flue pipe length is 14m.
3. Bend allowance to be subtracted from flue length.
In this example is 2 x 90° bends = 2 x 3.5m = 7m.
Therefore X = 14 - 7 = 7 metres max. flue pipe.
W Flue Designs
15
background image
Open Systems
The system should be vented directly off the boiler flow pipe, as
close to the boiler as possible. The cold feed entry should be
inverted and MUST be positioned between the pump and the vent,
and not more than 150mm (6") away from the vent connection.
There should be a minimum height, 500mm (20") of open vent
above the cistern water level. The vertical distance between the
highest point of the system and the feed/expansion cistern water
level MUST not be less than 3 metres.
The information provided is based on the following assumptions:
The boiler is at the highest point of the circulation system.
Systems designed to raise above the flow tappings will, of course,
automatically require a minimum static head higher than shown.
The position of the open vent/safety pipe above the expansion
cistern water level is given as a guide only. The final position will
depend upon particular characteristics of the system. Pumping over
of water into the expansion cistern should be avoided.
Cold Feed/Open Vent
The independent cold feed and the open vent must comply with
BS 6644 and be of the following minimum size:
Boiler output (kW)
Cold feed
Open vent
45 ­ 60
61 - 150
151 - 300
3
/
4
" (19mm)
1" (25mm)
1
1
/
4
" (32mm)
1" (25mm)
1
1
/
4
" (32mm)
1
1
/
2
" (38mm)
Sealed (Pressurised) Systems
W
Working pressure 4 bar (58psi) maximum.
Plus
Working pressure 6 bar (87psi) maximum.
Particular reference should be made to BS 6644: Section 2;
Subsection 11, Guidance note PM5 "Automatically controlled steam
and hot water boilers" published by the Health and Safety Executive
and Water Regulations Guide.
The information and guidance given below is not intended to
override any requirements of either of the above publications or the
requirements of the Local Authority, gas or water undertakings.
In general, commercial closed pressurised systems are provided
with either manual or automatic water make up.
In both instances it will be necessary to fit automatic controls
intended to protect the boiler circulating system and ancillary
equipment by shutting down the boiler plant if a potentially
hazardous situation should arise.
Examples of such situations are low water level and operating
pressure or excessive pressure within the system. Depending on
circumstances, controls will need to be either manual or automatic
reset. In the event of shut down, both visual and audible alarms may
be necessary.
Pressure vessels used must comply with BS 4814 and must
be sized on the basis of the total system volume and initial
charge pressure.
Initial minimum charge pressure should not be less than 0.5 bar
(7.2psi) and must take account of static head and specification of
the pressurising equipment. The maximum water temperatures
permissible at the point of minimum pressure in the system is
specified in Guidance Note PM5.
When make up water is not provided automatically it will be
necessary to fit controls which shut down the plant in the event of
the maximum system pressure approaching to within 0.35 bar (5psi)
of the safety valve setting.
Other British Standards applicable to commercial sealed
systems are:
BS 6880: Part 2
BS 1212
BS 6281: Part 1
BS 6282: Part 1
BS 6283: Part 4
* Plus only: For head heights less than 8m the pump must be
fitted on the return.
system requirements
16
background image
System Design
The efficiency of this range of boilers is higher than conventional
boilers because of the increased heat exchange area.
At return temperatures of 55°C and below, the differences
become more marked because the water in the flue gases starts to
condense releasing its latent heat.
In general, the lower return temperature, the better the efficiency.
In new systems it is best to design for the lowest flow and return
temperatures that are practical (subject to the lower limit mentioned
above). For optimum operation it is advised that the system be
designed on a temperature differential of 20°C.
Installation
For safety, a competent CORGI (Council for the Registration of
Gas Installers) registered installer must fit this appliance. CORGI
requires its members to work to satisfactory standards.
Boiler installation should comply with relevant British Standard
Specifications, Codes of Practice, and current Building Regulations,
together with any special regional requirements of the Local
Authorities, Gas Supplier, and Insurance Company, and in particular:
BS 6891 Low Pressure Installation Pipes, BS 6644 Installation
of Gas Fired Boilers, BS 6880 Part 1-3 Central Heating by Low
Pressure Hot Water, CP 342.2 Centralised Hot Water Supply,
IGE/UP/10 Installation of Gas Appliances in Industrial & Commercial
Premises, Part 1: Flued appliances.
All electrical wiring must comply with lEE Regulations.
Manufacturer's notes must not be taken as overriding statutory
obligations.
Minimum clearances from walls or other fixed objects to allow
for installation, maintenance, and the free access of combustion air
are shown in the boiler clearance diagram.
17
background image
Water Treatment
Corrosion will always occur within a heating/hot water system to
a greater or lesser degree irrespective of water characteristics, unless
the initial fill water from the mains is treated. For these reasons Ideal
Boilers Solutions strongly recommends that when necessary the
system be thoroughly cleaned prior to the use of a stable inhibitor
which does not require continual topping up to combat the effects of
hardness, salts and corrosion on the heat exchanger and its
associated systems.
The Ideal W & Plus boilers have an aluminium alloy
heat exchanger. Therefore it is important that if water treatment is
used it is suitable for the material of the heat exchanger. The ONLY
water treatments approved are `Fernox Copal' and `Sentinel X 100'.
Current suitability should be confirmed with the manufacturer direct:
BetzDearborn Ltd, Sentinel Division, Foundry Lane, Widnes,
Cheshire WA8 8UD Telephone: 0151 424 5351 or Fernox, Fry
Technology UK, Tandem House, Marlowe Way, Beddington Farm
Road, Croydon CRO 4XS Telephone: 01799 550811 for technical
information.
Any other treatment used will render the guarantee of Caradon
Ideal Limited for this product INVALID. The use of artificially
softened water is NOT permitted.
Gas
W & Plus
Natural Gas models: If there is any doubt concerning the
capacity of the gas meter, available gas pressure, adequacy of
existing pipes or the size required for new service pipes, contact the
Gas Region for advice. Installation pipework should be fitted and
tested for gas soundness in accordance with BS 6891. The local Gas
Region must be consulted if a gas pressure booster is needed.
W Only
Propane Gas models: Contact the local Propane Gas supplier at
the installation planning stage to ensure availability of an adequate
supply of gas. Installation pipes, cylinders and pressure regulators
should be fitted in accordance with BS 5482: 1. Bulk tank
installations must comply with the Home Office Codes of Practice for
the storage of LPG at fixed installations.
Ventilation
Open flued application
Safe, efficient, and trouble-free operation of conventionally flued
gas boilers is vitally dependent on the provision of an adequate
supply of fresh air to the room in which the appliance is installed.
Ventilation by grilles communicating directly with the outside air
is required at both high and low levels. The minimum free areas of
these grilles must be according to the scale below. The use of an
extractor fan in the same room as the boiler (or in an adjacent room
in communication) can, in certain conditions, adversely affect the
safe operation of the boiler. Where such a fan is already fitted, or if
an extractor fan is likely to be installed at a later date, then the
advice of the gas supplier should be obtained.
W45 & W60 Only
BS 5440: 2 - Inputs not exceeding 70kW (nett)
Total nett input
Air vent areas
rating of boilers
(air direct from outside)
Up to 70kW
5cm
2
per kW nett input
Total gross input
Position of
Air vent areas
rating of boilers
air vents
(air direct from outside)
270cm
2
plus 2.25cm
2
60kW to 2MW
High level
per kW in excess of
60kW total rated input
540cm
2
plus 4.5cm
2
60kW to 2MW
Low level
per kW in excess of
60kW total rated input
Balanced flue applications
Room sealed installations require no air for combustion as this is
drawn direct from the outside atmosphere. However, air may be
required to ventilate the boiler house and remove any excess heat
generated by the boiler.
W boilers have a standard range of balanced flues
available.
Plus boilers have an air inlet connection which may be
used with proprietary ducting if required. A separate flue connection
is still required.
W & Plus
BS 6644 - Inputs greater than 60kW (gross)
system requirements
18
background image
Condensate Drain
Ideal boilers will produce condensate whenever the
temperature of the return water from the system is below
approximately 55°C (the dew point of the combustion products).
Natural Gas condensate is mildly acidic with a pH value of about
4 and therefore corrosion resistant materials must be used in the
construction of the condensate drain. Standard PVC pipe is suitable
for this purpose and should be connected to the plastic drain fitted
on the boiler.
W
A condensate trap is supplied for fitting to the boiler and the
drain may be led directly into the normal drainage system. The pipe
should be installed with an adequate slope (eg 1 in 50) and
consideration should be given to frost protection.
Plus
Pipework is supplied for fitting beneath the boiler and includes a
filling point for initial charging of a condensate siphon (not
supplied). The pipe should be installed with an adequate slope (eg 1
in 50) and consideration should be given to frost protection.
19
Plus Condensate Drain
background image
Performance Data - W (45 - 80)
Model
W45 W45P
W60
W60P
W80
W80P
max
kW
46.9
45.9
62.3
60.6
82.7
80.0
Boiler output (condensing)
Btu/h
160,000
156,000
212,560
206,750
282,170
272,950
50/30°C
min
kW
13.9
13.7
13.9
13.6
21.3
20.7
Btu/h
47,600
46,600
47,600
46,400
72,700
70,600
max
kW
43.7
58.9
78.2
Boiler output (non-condensing)
Btu/h
149,000
200,960
266,800
80/60°C
min
kW
12.6
12.6
19.5
Btu/h
43,000
43,000
66,500
max
kW
45
60
80
Boiler input (Nett)
Btu/h
153,540
204,720
272,960
min
kW
13
13
20
Btu/h
44,350
44,350
68,240
max
kW
49.9
48.9
66.5
65.1
88.7
86.9
Boiler input (Gross)
Btu/h
170,250
166,850
227,000
222,300
302,700
296,350
min
kW
14.4
14.1
14.4
14.1
22.2
21.7
Btu/h
49,150
48,150
49,150
48,150
75,650
74,100
Gas rate
Natural Gas
m
3
/h
4.76
6.35
8.46
ft
3
/h
166
222
296
Gas rate
Propane
m
3
/h
1.84
2.45
3.27
ft
3
/h
65
86
115
Approx flue gas volume
Natural Gas
m
3
/s
0.02
0.027
0.036
(non condensing) max rate
ft
3
/min
42.33
57.67
77
Approx flue gas volume
Propane
m
3
/s
0.019
0.026
0.034
(non condensing) max rate
ft
3
/min
40
54.67
72.33
Seasonal efficiency *(SEDBUK)
%
90.4
91.3
90.4
92.1
90.2
91.6
Note: Gas rates are calculated using a C.V. of 37.8 MJ/m
3
gross (34 MJ/m
3
nett) for Natural Gas or 95.7 MJ/m
3
for Propane.
* The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings.
General Data - W (45 - 80)
Model
W45 & W45P
W60 & W60P
W80 & W80P
Flow connection
BSP
R1
1
/
4
"
Return connection
BSP
R1
1
/
4
"
Maximum static water head
m
40.79
ft
133.83
Maximum pressure
Bar
4.0
psi
58
Gas inlet connection
mm
22
Pressure required at the boiler inlet
mbar
17.5
for the rated input (Natural Gas)
in. w.g.
7.0
Electricity supply
230V 50Hz
Nominal flue size / concentric
mm
80 / 125
80 / 125
100 / 150
Nominal flue size / twin pipe
mm
80 / 80
80 / 80
100 / 100
Condensate drain
mm
25
NOx emissions
mg / kW / hr
45
55
60
ppm (0% O
2
)
26
31
34
Water content
l
8
8
10
gal
1.76
1.76
2.20
Weight
kg
87
88
101
lb
191
194
222
Power consumption
W
51
84
120
general & performance data
20
background image
Performance Data - Plus (80 - 280)
Model
F80
F120
F160
F200
F240
F280
max
kW
83.9
125.9
167.8
209.8
251.8
293.7
Boiler output (condensing)
Btu/h
286,300
429,600
572,550
715,850
859,200
1,002,150
Mean 50/30°C
min
kW
13.0
13.0
13.0
13.0
13.0
13.0
Btu/h
44,350
44,350
44,350
44,350
44,350
44,350
max
kW
77.3
116.0
154.6
193.2
231.8
270.5
Boiler output (non-condensing)
Btu/h
263,750
395,800
545,950
659,250
818,900
923,000
Mean 80/60°C
min
kW
11.6
11.6
11.6
11.6
11.6
11.6
Btu/h
39,600
39,600
39,600
39,600
39,600
39,600
Nett
kW
80
120
160
200
240
280
Boiler input maximum rate
Btu/h
272,950
409,450
545,950
682,450
818,900
955,400
Gross
kW
88.8
133.2
177.6
222.0
266.4
310.8
Btu/h
303,000
454,500
606,000
757,500
909,000
1,060,500
Nett
kW
12
12
12
12
12
12
Boiler input minimum rate
Btu/h
40,950
40,950
40,950
40,950
40,950
40,950
Gross
kW
13.3
13.3
13.3
13.3
13.3
13.3
Btu/h
45,400
45,400
45,400
45,400
45,400
45,400
Gas rate
Natural Gas
m
3
/h
8.42
12.63
16.83
21.04
25.26
29.46
ft
3
/h
297
446
594
743
892
1040
Approx flue gas volume
Natural Gas
m
3
/s
130
196
261
326
392
457
(non condensing) max rate
ft
3
/min
4,590
6,920
9,220
11,510
13,840
16,140
Note: Gas rates are calculated using a C.V. of 37.8 MJ/m
3
gross (34 MJ/m
3
nett) for Natural Gas.
General Data - Plus (80 - 280)
Model
F80
F120
F160
F200
F240
F280
Flow connection
BSP
R2"
Return connection
BSP
R2"
Maximum static water head
m
61
ft
200
Maximum pressure
Bar
6
psi
87
Gas inlet connection
BSP
R1
1
/
2
"
Pressure required at the boiler inlet
mbar
15.0
for the rated input (Natural Gas)
in. w.g.
6.0
Electricity supply
230V 50Hz
Nominal flue size
mm
150
150
150
200
200
200
Nominal air inlet size
mm
150
150
150
150
150
150
Condensate drain
mm
40
NOx emissions
mg / kW / hr
< 62
ppm (0% O
2
)
< 35
Water content
l
10.1
14.2
18.3
22.4
26.5
30.6
gal
2.22
3.13
4.03
4.93
5.84
6.74
Weight
kg
125
170
215
260
305
345
lb
276
375
474
573
673
761
Power consumption
W
175
250
325
400
475
550
21
background image
W Boiler Dimensions
W Boiler House Clearances
The following minimum clearances must be maintained for operation and servicing:
· Front of boiler
- 450mm
· Sides of boiler - 50mm
· Above boiler
- dependent upon the flue system
· Below boiler
- 300mm
dimensional data
W Multiple Frame Kit
A
B
C
D
E
F
G
2 Boiler, Frame & Header Kit W45/60
1648
1130
403.5
372
460
DN50 PN6
32NB
3 Boiler, Frame & Header Kit W45/60
2238
1720
403.5
372
460
DN50 PN6
32NB
2 Boiler, Frame & Header Kit W80
1868
1350
395
372
460
DN50 PN6
32NB
3 Boiler, Frame & Header Kit W80
2568
2050
395
380
455
DN65 PN6
40NB
22
background image
Plus Boiler Dimensions
23
Model
80
120
160
200
240
280
Modules No. off
2
3
4
5
6
7
A
695
695
832
968
1102
1236
B
150
150
150
200
200
200
Weight
kg
153
182
223
261
301
345
Connections
Gas
G : 1
1
/
2
"
Flow
M : 2"
Return
R : 2"
Condensate Drain
S : ø40
Plus Boiler House Clearances
The following minimum clearances must be maintained for operation and servicing:
· Rear of boiler
- 300mm; except with rear flue 600mm.
· Sides of boiler
- 50mm; except with side flue 600mm or pipework side 300mm.
· Front of boiler
- 700mm; except compartment access doors may be closer, but not less than 200mm, and 700mm must still be
available for service across the full width of the boiler.
· Between multiple boilers - 50mm; however due consideration must be respected for electrical connections, side pipework and flues if
located between boilers.
background image
20
40
100 150 200
600
800
1000
1500
3500
68
136
340 511 682
2047
2729
3412
5118
11942
Boiler output
Concord CXS/H, CXSD/H
W
Concord CXSi/H, CXDi/H
Concord ES/H
Concord Modular
Concord Super Series 4
Buccaneer GTE
Falcon GTE
Harrier GTE
Viceroy GT
Viscount GTE
Vanguard L
kW
Btu/h (000)
Concord CXA/H
40-120
40-120
80-280
110-180
140-380
80-720
50-600
45-80
Concord Super Plus
200-600
21-39
36-102
105-330
300-780
754-1450
130-3500
Buccaneer / Falcon
Combination Boilers
Senator Calorifiers
21-64
150-1000 litres
Atmospheric Boilers
High Efficiency Boilers
Pressure Jet Boilers
Hot water solutions
Ideal Boilers Limited, PO Box 103, National Avenue, Kingston upon Hull HU5 4JN.
www.idealcommercialboilers.com email: commercial_heating@idealboilers.com
Imax/1/04
Issued subject to standard conditions
Assurance of quality
BS EN ISO 9001: 2000
Contact Numbers
© 2004 Ideal Boilers Limited
Sales
Tel:
01482 498690
Fax:
01482 498621
Technical
Tel:
01482 498376
Fax:
01482 498621
Training
Tel:
01482 498432
Fax:
01482 498605
Approval
These appliances are certified to
G.A.D. 90/396 and B.E.D. 92/42
safety and performance Directives
for gas boilers.
Ideal Boilers pursues a policy of
continuous improvement in design
and performance of its products
and reserves the right to vary
specification without notice.
Statutory rights of the consumer
are not affected.
Condensing Boilers
GT Condenser
180-990
Plus
Concord CXC
49-116
The Ideal Commercial Range