installation and
servicing
Your Ideal installation and servicing guide
ENGINEERED FOR PEACE OF MIND
When replacing any part on this appliance, use only spare parts that you can be
assured conform to the safety and performance specification that we require. Do not
use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
Falcon GTE
GTE 4, GTE 5, GTE 6, GTE 7 & GTE 8
2
Falcon GTE -
Installation & Servicing
GENERAL
Note.
Fuel rates and flue gas data relate to maximum output ratings.
Gas firing data relates to the use of NATURAL GAS ONLY.
Details for the use of LPG are available on request from Caradon
Ideal Ltd.
Natural gas consumption is calculated using a calorific value of
38.7MJ/m
3
(1038Btu/ft
3
) gross or 34.9MJ/m
3
(935Btu/ft
3
) nett at
15
o
C and 1013.25mbar.
Oil rates relate to Gas Oil using a calorific value of 45.56 MJ/kg
gross or 42.69 MJ/kg nett.
Table 1 Performance Data
Boiler
GTE 4
GTE 5
GTE 6
GTE 7
GTE 8
Number of Sections
4
5
6
7
8
Maximum
kW
50
64
78
92
102
Heat Ouptut
Btu/hx10
3
170
218
266
314
348
Minimum
kW
36
50
64
78
92
Heat Output
Btu/hx10
3
123
170
218
266
314
Hydraulic
mbar
20.3
33.3
49.3
68.4
84.0
Resistance at 11k
in w.g.
8.1
13.3
19.7
27.4
33.6
Hydraulic
mbar
6.1
10.1
14.9
20.7
25.4
Resistance at 20k
in w.g.
2.5
4.0
6.0
8.3
10.2
Combustion Chamber
mbar
0.4
0.6
0.6
0.6
0.8
Resistance (at zero draught)
in w.g.
0.16
0.24
0.24
0.24
0.32
Minimum Draught at Smokehood mbar
0
0
0
0
0
Outlet (for max. output)
in w.g.
0
0
0
0
0
HEALTH & SAFETY DOCUMENT NO. 635
The electricity at work regulations, 1989. The manufacturer's
notes must NOT be taken, in any way, as overriding statutory
obligations.
IMPORTANT. These appliances are CE certified for safety and
performance. It is, therefore, important that no external control
devices, e.g. flue dampers, economisers etc., are directly
connected to these appliances unless covered by these
Installation and Servicing Instructions or as otherwise
recommended by Caradon Ideal Limited in writing. If in doubt
please enquire.
Any direct connection of a control device not approved by
Caradon Ideal Limited could invalidate the certification and the
normal appliance warranty. It could also infringe the Gas Safety
Regulations and the above regulations.
Maximum Gross
l/h
5.61
7.18
8.80
10.38
11.51
Oil Rate
gal/h
1.23
1.58
1.93
2.27
2.52
Maximum Flue
m
3
/s
0.031
0.040
0.049
0.058
0.064
Gas Volume
ft
3
/min
66
85
104
123
136
Flue Gas CO
2
/ Temperature
% /
o
C
12 / 200
12 / 200
12 / 200
12 / 200
12 / 200
Oil
Maximum
m
3
/h
5.58
7.16
8.78
10.33
11.48
Gas Rate
ft
3
/h
197.5
252.8
309.8
365.4
405.1
Maximum Flue
m
3
/s
0.032
0.042
0.051
0.061
0.067
Gas Volume
ft
3
/min
69
89
109
128
142
Flue Gas CO
2
/ Temperature
% /
o
C
9 / 200
9 / 200
9 / 200
9 / 200
9 / 200
Gas
Table 2 General Data
Flow Connection
R 1
1
/
4
"
R 1
1
/
4
"
R 1
1
/
2
"
R 1
1
/
2
"
R 1
1
/
2
"
Return Connection
R 1
1
/
4
"
R 1
1
/
4
"
R 1
1
/
2
"
R 1
1
/
2
"
R 1
1
/
2
"
Maximum Operating Pressure
bar
4
4
4
4
4
Boiler Thermostat Setting
o
C
30-90
30-90
30-90
30-90
30-90
Safety Thermostat Setting
o
C
110
110
110
110
110
Nominal Flue
m m
153
153
180
180
180
Diameter
in.
6
6
7
7
7
Boiler Water
l
36
43
50
57
64
Content
gal
7.9
9.5
11.0
12.5
14.1
Boiler DRY Weight
kg
254
295.5
343.5
380.5
422.5
less Burner Unit
lb
560
651.5
757.5
839
931.5
3
Falcon GTE -
Installation & Servicing
GENERAL
CONTENTS
Assembly. ................................................................... 11-22
Boiler Clearances. ............................................................ 6
Burner Connection. ........................................................ 11
Commissioning and Testing. ................................ 26 & 27
Electrical Connections. ............................................. 22-24
Electrical Supply. .............................................................. 5
Flue Installation. ................................................................ 5
Fluing. .............................................................................. 10
Gas Safety Regulations .................................................... 4
Gas Supply. ........................................................................ 5
Hydraulic Resistance. ...................................................... 2
Initial Lighting. ................................................................. 27
Introduction. ...................................................................... 3
Installation. ...................................................................... 10
Option Kits. ........................................................................ 3
Performance Data. ........................................................... 2
Servicing. ........................................................................ 28
Ventilation. ........................................................................ 7
Water Circulation. ............................................................ 5
Water Connections. ......................................................... 7
Water System Requirements. ......................................... 8
Water Treatment. ............................................................. 5
Wiring Diagrams. ................................................... 23 & 24
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance, care should be taken when handling edges of sheet steel components.
Falcon GTE
Gas and Fuel Oil
PI No. 0049AT2527
Destination Countries: GB, IE
INTRODUCTION
The Falcon GTE boilers are a range of cast iron sectional
pressure jet boilers offering high efficiency operation, ease of
maintenance, fuel flexibility and low emissions in a compact
package. Suitable for oil or gas operation the Falcon GTE range
is supplied in a choice of 5 standard models, rated in outputs
from 36kW (123,000 Btu/h) to 102kW (348,000 Btu/h) the range
has a maximum operating pressure of 4 bar. The GTE 7 and
GTE 8 may be high/low operation.
Designed with a large combustion chamber and 3 pass,
horizontal flue way incorporating fins and cast iron turbulators,
the Falcon GTE ensures maximum heat transfer efficiency (up to
93% net).
The boilers are suitable for: combined indirect pumped
domestic hot water and central heating systems; independent
indirect pumped domestic hot water or central heating systems.
Fully pumped systems may be open vented or sealed.
The boilers are NOT suitable for:
1. Gravity DHW systems
2. Gravity heating systems
3. Direct domestic hot water supply
Options
Hours run meter (IC8)
Burners with high/low operation are available on Models GTE 7
and GTE 8 with DR31 control panel
4
Falcon GTE -
Installation & Servicing
GENERAL
SAFETY
Current Gas Safety (Installation and Use) Regulations or
rules in force.
It is law that all gas appliances are installed and serviced by a
CORGI registered installer in accordance with the regulations
below. Failure to install appliances correctly could lead to
prosecution. It is in your own interest, and that of safety, to
ensure the law is complied with.
The following must be conformed with:
Current Building Regulations and Clean Air Act
Water Authority Regulations
Local Authority Regulations and Regional Bylaws
Gas Safety Regulations
Any special regional requirements of local Electricity and Gas
undertaking.
Fire Service and Insurance Company requirements.
In the interests of safety, a competent installer should be
employed to effect the installation of the appliance.
Manufacturer's notes must NOT, in any way, be taken as over
riding statutory obligations.
The installation of the boiler MUST also be in accordance with
the latest I.E.E. (BS7671) Wiring Regulations, local buildings
regulations, bye-laws of the local water authority, the building
regulations and the Building Standards (Scotland) and any
relevant requirements of the local authority.
Detailed recommendations are contained in the following
Codes of Practice:
BS 799 Pt4 & 7 Oil burning equipment.
BS 799 Pt5
Oil storage tanks.
BS 5410 Pt1
Installation for space heating and hot water
supply.
BS 5440
Installation and maintenance of flues and
ventilation for gas appliances of rated input
not exceeding 70kW net (1st, 2nd and 3rd
family gases).
Part 1
Specification for installation of flues
Part 2
Specification for installation and maintenance
of ventilation for gas appliances.
BS 5854
Flues and flue structures in buildings.
BS 5885 Pt1
Gas burners - with inputs 60kW and above.
NOTE TO THE INSTALLER: LEAVE THESE INSTRUCTIONS ADJACENT TO THE BOILER.
BS 6644
Installation of gas fired hot water boilers of
rated input between 70kW and 1.8MW (net)
(2nd and 3rd family gases).
BS 6798
Installation of gas fired hot water boilers of
rated input not exceeding 70kW.
BS 6880
Low temperature hot water heating systems of
output greater than 45kW.
Part 1
Fundamental and design considerations
Part 2
Selection of equipment.
Part 3
Installation, commissioning and maintenance.
BS 6891
Installation of low pressure gas pipework of up
to 28mm (R1) in domestic premises (2nd
family gas).
EN 303.1
Heating boilers with forced draught burners.
General requirements.
EN 303.2
Heating boilers with forced draught burners
with atomising oil burners.
EN 304
Test code for heating boilers for atomizing oil
burners.
73/23 EEC
Low voltage directive. (Relevant standard is
EN60335.1)
89/336 EEC
Electromagnetic Compatibility Directive.
(Relevant standards are EN50081.1,
EN50082.1 and EN55014.)
90/396 EEC
Gas Appliances Directive. (Relevant standards
are EN303.1, EN303.2 and EN304.)
92/42 EEC
Boiler Efficiency Directive.
IGE/UP/1
Soundness testing and purging of industrial
and commercial gas installation.
IGE/UP/2
Gas installation pipework, boosters and
compressors on industrial and commercial
premises.
IGE/UP/10
Installation of gas appliances in industrial and
commercial premises.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation
panels, which can cause irritation to the skin. No asbestos,
mercury or CFCs are included in any part of the boiler or its
manufacture.
Assembly and Installation Instructions for Ideal Falcon GTE heating boilers should be read in conjunction with the general
technical data tables enclosed and any other technical publication supplied with the burner.
5
Falcon GTE -
Installation & Servicing
GENERAL
GAS SUPPLY
The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an
adequate supply of gas. An existing service pipe must NOT be
used without prior consultation with the local gas supplier.
A gas meter can only be connected by the local gas supplier or
by a registered CORGI engineer.
An existing meter should be checked, preferably by the gas
supplier, to ensure that the meter is adequate to deal with the
rate of gas supply required. A minimum working gas pressure
of 17.5mbar MUST be available at the boiler inlet.
Do not use pipes of smaller size than the burner inlet gas
connection.
The complete installation MUST be tested for gas soundness
and purged in accordance with the appropriate standards listed
on page 4.
FLUE INSTALLATION
IMPORTANT
It is the responsibility of the installer to ensure, in practice, that
products of combustion discharging from the terminal cannot re-
enter the building or any other adjacent building through
ventilators, windows, doors, other sources of natural air
infiltration, or forced ventilation / air conditioning.
If this should occur the appliance MUST be turned OFF, labelled
as 'unsafe' and corrective action taken.
The flue must be installed in accordance with the appropriate
standards listed on page 4.
WATER CIRCULATION SYSTEM
The system pump MUST be connected to the boiler.
The boiler must NOT be used for direct hot water supply. The
hot water storage cylinder MUST be of the indirect type.
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating nor
are they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of
the useful heating surface, should be lagged to prevent heat
loss and any possible freezing - particularly where pipes run
through roof spaces and ventilated underfloor spaces.
The boiler must be vented.
Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler
and hot water storage vessel. They should be at least 1/2" BSP
nominal size and be in accordance with BS. 2879.
The central heating system should be in accordance with the
relevant standards listed on page 4.
Due to the compact nature of the boiler the heat stored within the
castings at the point of shutdown of the burner must be
dissipated in order to avoid overheating. In order to allow pump
operation after burner shutdown the boiler control box
incorporates a pump overrun facility. In order to make use of
this, the pump must be supplied from the terminals inside the
boiler. Note: for pumps requiring greater than 1.0amp current,
they must be connected via a relay.
WATER TREATMENT FOR HOT WATER AND
HEATING BOILERS
There is a basic need to treat the water contained in all heating
and indirect water systems, particularly open vented systems. It
is assumed, incorrectly, that because boilers are operating in
conjunction with what is apparently a closed circuit an open
vented system will not, under normal circumstances, allow
damage or loss of efficiency due to hardness salts and
corrosion once the initial charge of water has been heated up a
few times.
1mm of lime reduces the heat transfer from metal to water by
10%.
In practice the deposition of these salts is liable to cause noises
from the boiler body or even premature boiler failure. Corrosion
and the formation of black iron oxide sludge will ultimately result
in premature radiator failure.
Open vented systems are not completely sealed from the
atmosphere if proper venting and expansion of system water is
to be achieved. The same tank is used to fill the system with
water and it is through the cold feed pipe that system water
expands into the tank when the boiler passes heat into the
system.
Conversely, when the system cools, water previously expelled is
drawn back from the tank into the system together with a quantity
of dissolved oxygen.
Even if leakage from the heating and hot water system is
eliminated there will be evaporation losses from the surface of
the tank which, depending upon ambient temperature, may be
high enough to evaporate a large portion of the system water
capacity over a full heating season.
There will always be corrosion within a heating or hot water
system to a greater or lesser degree, irrespective of water
characteristics, unless the initial fill water from the mains is
treated. Even the water in closed systems will promote
corrosion unless treated. For the reason stated, Caradon Ideal
Limited strongly recommend that when necessary the systems
is thoroughly cleaned, prior to the use of stable inhibitor, which
does not require continual topping up to combat the effects of
hardness salts and corrosion on the heat exchangers of the
boiler and associated systems.
Caradon Ideal Limited advise contact directly with specialists on
water treatment such as:
GE Betz Ltd
or
Fernox Manufacturing Co. Ltd.
Sentinel Division,
Cookson Electronics,
Foundry Lane,
Forsyth Road, Sheerwater
Widnes, Cheshire,
Woking, Surrey,
WA8 8UD
GU21 5RZ
Tel: 0151 424 5351
Tel: 01799 521 133
ELECTRICAL SUPPLY
WARNING
This appliance must be earthed.
A 230V - 50Hz mains supply is required, fused at 5amps.
Wiring external to the appliance MUST be in accordance with the
current I.E.E. (BS7671) Wiring Regulations and any local
regulations which apply.
The point of connection to the mains should be readily
accessible and adjacent to the boiler.
LOCATION OF THE BOILER
The boiler must stand on a non-combustible floor (i.e. concrete
or brick) which must be flat, level and of a suitable load bearing
capacity to support the weight of the boiler (when filled with
water) and any ancillary equipment.
If the boiler is mounted on a plinth then the dimensions must
exceed the plan area of the boiler by at least 75mm on each side.
The boiler must not be fitted outside.
6
Falcon GTE -
Installation & Servicing
GENERAL
0,5m
L1
1m
0,5m
0,5m
560
987
Boiler
L1
Dimension mm
GTE 4
754
GTE 5
881
GTE 6
1008
GTE 7
1135
GTE 8
1262
FAL5814
1
BOILER DIMENSIONS
2
BOILER CLEARANCES
The minimum dimensions indicated on
the following drawing must be respected
to ensure good access around the
boiler.
Note.
To allow the inlet of the combustion air,
the boiler room must be adequately
ventilated, the section and the location of
which must comply with local
recommendations.
Refer also to Frame 3.
560
987
50(1)
189
188
753
608
A
B
51
111
214
355
346
205
=
=
heating outlet
EO
heating
return
EO
3/4" tapped
draining tube
115
115
117
45
156
162
D
165
=
=
(1) Adjustable feet: basic height 50mm with 35 to 65mm adjustment range.
Boiler
Dimension A
Dimension B
Dimension C
Dimension D
Dimension E
mm
mm
mm
mm
in BSP
754
592
153
423
R1
1
/
4
"
881
719
153
550
R1
1
/
4
"
1008
846
180
673
R1
1
/
2
"
1135
973
180
800
R1
1
/
2
"
1262
1100
180
927
R1
1
/
2
"
GTE 4
GTE 5
GTE 6
GTE 7
GTE 8
Rp : Tapped
R : Threaded
CO
flue gas
spigot
360
110
10
FAL5813
7
Falcon GTE -
Installation & Servicing
GENERAL
3
VENTILATION
Safe, efficient and trouble-free operation of conventionally
flued gas boilers is vitally dependent on the provision of an
adequate supply of fresh air to the room in which the
appliance is installed.
Ventilation by grilles communicating directly with the outside
air is required at both high and low levels. The minimum free
areas of these grilles must be according to the following
scale:
5
FILLING THE SYSTEM
Position ventilation grilles to avoid the risk of accidental
obstruction by blockage or flooding. If further guidance on
ventilation is required then consult BS 6644.
The supply of air by mechanical means to a space housing the
boiler should be by mechanical inlet with natural or mechanical
extraction. Mechanical extract ventilation with natural inlet must
not be used.
Where a mechanical inlet and a mechanical extract system is
applied, the design ventilation flow rates should be as in Table 4
of BS 6644.
Note.
For mechanical ventilation systems an automatic control should
be provided to cause safety shutdown or lockout of the boiler(s)
in the event of failure of air flow in either inlet or extract fans.
IMPORTANT. The use of an extractor fan in the same room as
the boiler (or in an adjacent communicating room) can, in
certain conditions, adversely affect the safe operation of the
boiler.
Where such a fan is already fitted (or if it is intended to fit an
extractor fan after installation of the appliance) the advice of the
gas supplier should be obtained.
The temperature within a boiler room shall not exceed 25
o
C
within 100 mm of the floor, 32
o
C at mid height and 40
o
C within
100 mm of the ceiling.
Filling shall be performed with a low flow rate from a low point
in the boiler room in order to ensure that all the air in the boiler
is bled from the high point of the system.
Always stop the pump before filling.
IMPORTANT. Instructions for starting up the boiler for the first
time after the system is fully or partly drained:
If all the air is not bled naturally to an expansion vessel which
opens out onto the air, the system must include manual
bleeder valves, in addition to automatic bleeder valves with the
capability to bleed the system by themselves when it is
operating. The manual bleeder valves are used to bleed all the
high points of the system and to make sure that the filled system
is free of air before the burner is turned on.
General
Recommendations relating to the water system are contained in
BS. 5449 and BS. 6880.
4
BOILER WATER CONNECTIONS
Flow and return connections are positioned at the rear of the
boiler and vary in size depending upon the output model.
Refer to Table 2, page 2 for sizes.
The flow and returns are provided with threaded connections.
A
3
/
4
" drain connection is provided at the rear bottom of the
boiler heat exchanger.
189
188
753
355
205
165
=
=
fal5921
Required area (cm
2
) per kW of total rated input (net)
Boiler room
Enclosure
Low level (inlet)
4
10
High level (outlet)
2
5
Note: Where a boiler installation is to operate in summer
months (e.g. DHW) additional ventilation requirements
are stated, if operating for more than 50% of time (refer
to BS6644).
8
Falcon GTE -
Installation & Servicing
GENERAL
7
SEALED (PRESSURISED) SYSTEMS
6
OPEN VENTED SYSTEM REQUIREMENTS - minimum static head requirements
The Falcon GTE boiler has a minimum static head requirement of
5.0 metres (16.5 feet approx.) depending on the particular
characteristics of the system design (see diagram). The information
provided is based on the following assumptions.
1. An open vent/safety pipe connection is made immediately after
the flow connection.
2. A cold feed/expansion pipe connection is made to the system
return pipe within 0.75m of the boiler return connection.
3. The maximum flow rate through the boiler is based on a
temperature difference of 11
o
C (20
o
F) at full boiler output with the
circulating pump positioned in the flow of the system.
4. The boiler is at the highest point of the system. Systems
designed to rise above the flow connections will, of course,
automatically require a minimum static head higher than shown.
5. The position of the open vent/safety pipe above the expansion
cistern water level is given as a guide only. The final position will
depend upon particular characteristics of the system. Pumping
over of water into the expansion cistern should be avoided.
6. Both open vent/safety pipe and cold feed/expansion pipes must
be of adequate diameter to suit the output of the boiler (see table
below).
Working pressure 4 bar maximum.
Particular reference should be made to BS. 6644: Section 2;
Subsection 11 and Guidance note PM5 "Automatically
controlled steam and hot water boilers" published by the
Health and Safety Executive.
The information and guidance given below is not intended to
override any requirements of either of the above publications
or the requirements of the local authority, as or water
undertakings.
In general commercial closed pressurised systems are
provided with either manual or automatic water make up.
In both instances it will be necessary to fit automatic controls
intended to protect the boiler, circulating system and ancillary
equipment by shutting down the boiler plant if a potentially
hazardous situation should arise.
Examples of such situations are low water level and operating
pressure or excessive pressure within the system.
Depending on circumstances, controls will need to be either
manual or automatic reset. In the event of a shutdown both
visual and audible alarms may be necessary.
Open vent
safety pipe
750mm
Cold feed/
expansion pipe
H = 5.0m
To
pump
FLOW
RETURN
Shunt pump
(if required)
Note: Height, H, MUST be
increased if necessary to
comply with the min.
head required by the
pump manufacturer
BOILER
This diagram does not show safety valves & water
flow switches etc necessary for safe operation
Expansion
cistern
FAL7405
Boiler Output kW
Open Vent (mm)
Cold Feed (mm)
30 to 60
25
20
60 to 150
32
25
Expansion vessels used must comply with BS. 4814 and must
be sized on the basis of the total system volume and initial
charge pressure.
Initial minimum charge pressure should not be less than 0.5
bar (7.2psi) and must take account of the static head and
specification of the pressurising equipment. The maximum
water temperatures permissible at the point of minimum
pressure in the system are specified in Guidance Note PM5.
When make up water is not provided automatically it will be
necessary to fit controls which shut down the plant in the event
of the maximum system pressure approaching to within
0.35bar (5psi) of the safety valve setting.
other British Standards applicable to commercial sealed
systems are:
BS. 6880: Part 2
BS. 1212
BS. 6281: Part 1
BS. 6282: Part 1
BS. 6283: Part 4
9
Falcon GTE -
Installation & Servicing
GENERAL
8
SYSTEM DESIGN
Minimum Water Flow
Design Flow Rates
The following table gives the flow rate required for each boiler
based on a design temperature difference of 11
o
C (20
o
F) at the
maximum rated output. For hydraulic resistance see General
Data table (page 2).
Minimum Flow Rates
It may be necessary to fit a shunt pump to ensure minimum flow
rates.
Boiler Size (no of sections)
4
5
6
7
8
Normal water flow rate
l/s
1.09
1.39
1.69
2.00
2.21
temperature difference 11
o
C (20
o
F) g.p.m.
14.4
18.4
22.3
26.4
29.2
Minimum water flow rate
l/s
0.34
0.44
0.53
0.63
0.70
temperature difference 35
o
C (63
o
F) g.p.m.
4.5
5.8
7.0
8.3
9.3
System Design
Recommendations relating to water system design are
contained in BS. 5410: Part 2, BS. 6798 and BS. 6880.
System design must allow for adequate internal circulation
within the boiler and sufficient heat release from the boiler
body during and immediately after burner firing. Heating and/
or hot water controls should be interlocked electrically with the
burner, to prevent firing when the system does not demand
heat.
Depending on system design it may be necessary to interrupt
electrical supply to the burner before any mixing valves are
completely closed to the boiler flow. This will dissipate residual
heat. Also a pump overrun of at least 5 minutes is required on
plant shutdown to avoid interference trip out of the overheat
thermostat. If system return temperature remains below 30
o
C
for most of the heating period some protection from
condensation is required.
Please contact Caradon Ideal Limited for further information.
The example assumes flow rate required through
the DHW storage cylinder is less than that required
by the boiler. A combined shunt/DHW primary pump siz ed
on the minimum flow to be required MUST be fitted.
Provided adequate heat dissipation can be achieved at all
times the combined pump only may run on during the
overrun period - allowing the heating pump to switch off.
In order to achieve adequate heat dissipation into the DHW
storage cylinder, the diverter valve MUST always open
during the overrun period of 5 minutes.
Example A - Heating only utilizing a mixing valve
Example B - Combined domestic hot wat er and heating using a mixing valve
Example C - Combined domestic hot wat er using a divert er valve, and heating using a mixing valve
Shunt
pump
Mixing valve
Heating pump
Bypass
Load
A shunt pump sized on the minimum flow rate required
MUST be fitted. Both heating and shunt pumps MUST run
on during the overrun period of 5 minutes.
The mixing valve MUST NOT be capable of complete
closure to bypass, in order that residual heat can be
dissipated.
DHW
storage
DHW Primary pump
Shunt
pump
Heating
pump
Bypass
Mixing valve
A shunt pump sized on the minimum flow rate required
MUST be fitted. Provided adequate heat dissipation can be
achieved at all times the shunt and DHW primary pumps
only may run on during the overrun period of 5 mins -
allowing the heating pump to be switched off. This
example assumes the DHW primary pump flow rate
required is less than that required for the shunt pump.
Load
Diverting
valve
Combined shunt and
DHW primary pump
Shunt
bypass
Bypass
Bypass
Heating pump
Load
Mixing valve
DHW
storage
Notes:
Minimum static head requirements with limit thermostat set at 100ºC (212ºF) : 2.5m.
The examples illustrated are intended as a general guide only.
Caradon Ideal Limited will be pleased to advise on specific applications.
Design and minimum flow rate tables are shown in this leaflet.
FAL5816
10
Falcon GTE -
Installation & Servicing
INSTALLATION
GTE 4
36-50
0
0.025
0.026
200
153
5
GTE 5
50-64
0
0.032
0.033
200
153
5
GTE 6
64-78
0
0.039
0.041
200
180
5
GTE 7
78-92
0
0.047
0.048
200
180
5
GTE 8
92-102
0
0.052
0.053
200
180
5
9
FLUING
According to the output, the difference between the
temperature of the flue gas and the ambient temperature can
be as low as 160
o
C. The installer will have to respect all of the
usual precautions (dilution - piping - T for removal of
condensation) in order to prevent deterioration of the chimney.
FLUE SIZE
Refer to applicable regulations while determining the size
and height of the flue. Please note that GTE boilers have
pressurised and sealed combination chambers and that the
pressure at the outlet must not exceed 0 mbar.
Detailed recommendations relating to the design of flues for
GAS fired appliances are quoted in BS. 6644 and IGE/UP/10,
whilst BS. 5410 Pt. 1 similarly applies to OIL fired boilers.
The table below contains the minimum dimensions of the
flue required for each boiler model in order to ensure
sufficient draught at the outlet.
(1) : at boiler maximum input.
(2) : Boiler temperature: 80
o
C (ambient temperature : 20
o
C).
However, care must be taken to comply with any applicable
national or local regulations.
10 DIMENSIONAL INFORMATION REQUIRED FOR THE FLUE CONNECTION
Connection
The connection must be made in a competent manner with
airtight pipe in a material that is resistant to hot gases from the
combustion and possible acid condensation. This pipe must
be as short as possible, be removable and without any
sudden change in its section.
The diameter must always be at least equal to that of the boiler
outlet.
Boiler
Heat
Output
Required
Draught
Mass Flow of Flue Gases
kg/s
Natural Gas
9% CO
2
Flue Gas
Temperature
(1) (2)
Chimney:
Minimum Recommended
Dimensions
kW
mbar
o
C
Ø min
m m
Height
m
Fuel Oil
12% CO
2
fal5922
214
608
45
30-45
500 minimum
fa
l
5926