2
Buccaneer GTE -
Installation & Servicing
GENERAL
Note.
Fuel rates and flue gas data relate to maximum output ratings.
Gas firing data relates to the use of NATURAL GAS ONLY.
Details for the use of LPG are available on request from Caradon
Ideal Ltd.
Natural gas consumption is calculated using a calorific value of
38.7MJ/m
3
(1038Btu/ft
3
) gross or 34.9MJ/m
3
(935Btu/ft
3
) nett at
15
o
C and 1013.25mbar.
* The value is used in the UK Government's Standard Assessment
Procedure (SAP) for energy rating of dwellings. The test data from
which it has been calculated have been certified by a notified body.
Table 1 Performance Data
Boiler
GTE 4
GTE 5
GTE 6
Number of Sections
4
5
6
Maximum
kW
27
33
39
Heat Output
Btu/hx10
3
92.1
112.6
133.1
Minimum
kW
21
27
32
Heat Output
Btu/hx10
3
71.7
92.1
109.2
Hydraulic
mbar
5.3
7.9
10.9
Resistance at 11k
in w.g.
2.1
3.2
4.4
Hydraulic
mbar
1.6
2.4
3.3
Resistance at 20k
in w.g.
0.6
1.0
1.3
Combustion Chamber
mbar
0.23
0.23
0.22
Resistance (at zero draught)
in w.g.
0.01
0.01
0.01
Minimum Draught at Smokehood mbar
0.12
0.12
0.11
Outlet (for max. output)
in w.g.
0.048
0.048
0.044
HEALTH & SAFETY DOCUMENT NO. 635
The electricity at work regulations, 1989. The manufacturer's
notes must NOT be taken, in any way, as overriding statutory
obligations.
IMPORTANT. These appliances are CE certified for safety and
performance. It is, therefore, important that no external control
devices, e.g. flue dampers, economisers etc., are directly
connected to these appliances unless covered by these
Installation and Servicing Instructions or as otherwise
recommended by Caradon Ideal Limited in writing. If in doubt
please enquire.
Any direct connection of a control device not approved by
Caradon Ideal Limited could invalidate the certification and the
normal appliance warranty. It could also infringe the Gas Safety
Regulations and the above regulations.
Maximum Gross
l/h
3.11
3.80
4.48
Oil Rate
gal/h
0.683
0.836
0.986
Maximum Flue
m
3
/s
0.017
0.022
0.025
Gas Volume at 12% CO
2
ft
3
/min
36
47
53
Flue Gas CO
2
/ Temperature
% /
o
C
12 / 180
12 / 190
12 / 190
Oil
Maximum
m
3
/h
3.10
3.79
4.47
Gas Rate
ft
3
/h
109.4
133.9
158.0
Maximum Flue
m
3
/s
0.019
0.026
0.027
Gas Volume at 9% CO
2
ft
3
/min
40
49
57
Flue Gas CO
2
/ Temperature
% /
o
C
9 / 180
9 / 190
9 / 190
Gas
Part Load Efficiency (Gross)
%
86.0
85.0
84.4
*Seasonal Efficiency (SEDBUK)
[79.9]% Band D
[79.9]% Band D
[79.9]% Band D
Table 2 General Data
Flow Connection
R 1
1
/
4
"
R 1
1
/
4
"
R 1
1
/
4
"
Return Connection
R 1
1
/
4
"
R 1
1
/
4
"
R 1
1
/
4
"
Maximum Operating Pressure
bar
4
4
4
Boiler Thermostat Setting
C
30 - 90
30 - 90
30 - 90
Safety Thermostat Setting
C
110
110
110
Nominal Flue
m m
125
125
153
Diameter
in.
5
5
6
Boiler Water
l
24.5
30
35.5
Content
gal
5.4
6.6
7.8
Boiler DRY Weight
kg
182
210
237.5
less Burner Unit
lb
401.5
463
523.5
Part Load Efficiency (Gross)
%
89.5
88.5
87.8
*Seasonal Efficiency (SEDBUK)
[85.7]% Band C
[85.7]% Band C
[85.7]% Band C
3
Buccaneer GTE -
Installation & Servicing
GENERAL
CONTENTS
Assembly. ................................................................... 11-18
Boiler Clearances. ............................................................ 6
Burner Connection. ........................................................ 10
Commissioning and Testing. ................................ 25 & 26
Electrical Connections. .................................................. 19
Electrical Supply. .............................................................. 5
Flue Installation. ................................................................ 5
Fluing. ................................................................................ 9
Gas Safety Regulations .................................................... 4
Gas Supply. ........................................................................ 5
Hydraulic Resistance. ...................................................... 2
Initial Lighting. ................................................................. 26
Introduction. ...................................................................... 3
Installation. ........................................................................ 9
Option Kits. ........................................................................ 3
Performance Data. ........................................................... 2
Servicing. ........................................................................ 27
Ventilation. ........................................................................ 7
Water Circulation. ............................................................ 5
Water Connections. ......................................................... 7
Water System Requirements. ......................................... 8
Water Treatment. ............................................................. 5
Wiring Diagrams. ....................................................... 20-22
COMBINATION MODELS ONLY
Assembly. ................................................................... 32-36
Boiler Clearances. .......................................................... 30
Introduction. .................................................................... 29
Servicing. ........................................................................ 37
Start Up. .......................................................................... 36
Technical Data. ...................................................... 29 & 30
Water Connections. ....................................................... 31
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance, care should be taken when handling edges of sheet steel components.
Buccaneer GTE
Gas and Fuel Oil
PI No. 0049 BM 3528
Destination Countries: GB, IE
INTRODUCTION
The Buccaneer GTE boilers are fully automatically controlled
floor standing boilers designed for connecting to a flue pipe and
require a separate automatic fuel oil or gas burner.
The boilers have a maximum heat output of 27-39kW.
The boilers are suitable for: combined indirect pumped
domestic hot water and central heating systems; independent
indirect pumped domestic hot water or central heating systems.
Control features include as standard, the ability to control two
heating zones.
Fully pumped systems may be open vented or sealed.
The boilers are NOT suitable for:
1. Gravity DHW systems.
2. Gravity heating systems.
3. Direct domestic hot water supply.
Option
DHW Remote Sensor Kit (AD 212)
buc5487
buc5536
4
Buccaneer GTE -
Installation & Servicing
GENERAL
SAFETY
Current Gas Safety (Installation and Use) Regulations or
rules in force.
It is law that all gas appliances are installed and serviced by a
CORGI registered installer in accordance with the regulations
below. Failure to install appliances correctly could lead to
prosecution. It is in your own interest, and that of safety, to
ensure the law is complied with.
The following must be conformed with:
Current Building Regulations and Clean Air Act
Water Authority Regulations
Local Authority Regulations and Regional Bylaws
Gas Safety Regulations
Any special regional requirements of local Electricity and Gas
undertaking.
Fire Service and Insurance Company requirements.
In the interests of safety, a competent installer should be
employed to effect the installation of the appliance.
Manufacturer's notes must NOT, in any way, be taken as over
riding statutory obligations.
The installation of the boiler MUST also be in accordance with
the latest I.E.E. (BS7671) Wiring Regulations, local buildings
regulations, bye-laws of the local water authority, the building
regulations and the Building Standards (Scotland) and any
relevant requirements of the local authority.
Detailed recommendations are contained in the following
Codes of Practice:
BS 799 Pt4 & 7 Oil burning equipment.
BS 799 Pt5
Oil storage tanks.
BS 5410 Pt1
Installation for space heating and hot water
supply.
BS 5440
Installation and maintenance of flues and
ventilation for gas appliances of rated input
not exceeding 70kW net (1st, 2nd and 3rd
family gases).
Part 1
Specification for installation of flues
Part 2
Specification for installation and maintenance
of ventilation for gas appliances.
BS 5449
Forced circulation hot water central heating
systems for domestic premises. Note: only
up to 45kW.
NOTE TO THE INSTALLER: LEAVE THESE INSTRUCTIONS ADJACENT TO THE BOILER.
BS 5482 Pt1
Domestic butane and propane gas burning
installations.
BS 5546
Installation of gas hot water supplies for
domestic purposes.
BS 5854
Flues and flue structures in buildings.
BS 5885 Pt2
Gas burners - with inputs up to 60kW.
BS 6798
Installation of gas fired hot water boilers of
rated input not exceeding 60kW.
BS 6891
Installation of low pressure gas pipework of up
to 28mm (R1) in domestic premises (2nd
family gas).
EN 303.1
Heating boilers with forced draught burners.
General requirements.
EN 303.2
Heating boilers with forced draught burners
with atomizing oil burners.
EN 304
Test code for heating boilers for atomizing oil
burners.
73/23 EEC
Low voltage directive. (Relevant standard is
EN60335.1)
89336 EEC
Electromagnetic Compatibility Directive.
(Relevant standards are EN50081.1,
EN50082.1 and EN55014.)
90396 EEC
Gas Devices Directive. (Relevant standards
are EN303.1, EN303.2 and EN304.)
92/42 EEC
HH Efficiency Directive.
IGE/UP1
Soundness testing and purging of industrial
and commercial gas installation.
IGE/UP2
Gas installation pipework, boosters and
compressors on industrial and commercial
premises.
IGE/UP10
Installation of gas appliances in industrial and
commercial premises.
British Gas IM11 Flues for commercial and industrial gas fired
boilers and air heaters.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation
panels, which can cause irritation to the skin. No asbestos,
mercury or CFCs are included in any part of the boiler or its
manufacture.
Assembly and Installation Instructions for Ideal Buccaneer GTE heating boilers should be read in conjunction with the general
technical data tables enclosed and any other technical publication supplied with the burner.
5
Buccaneer GTE -
Installation & Servicing
GENERAL
GAS SUPPLY
The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an
adequate supply of gas. An existing service pipe must NOT be
used without prior consultation with the local gas supplier.
A gas meter can only be connected by the local gas supplier or
by a registered CORGI engineer.
An existing meter should be checked, preferably by the gas
supplier, to ensure that the meter is adequate to deal with the
rate of gas supply required. A minimum working gas pressure
of 17.5mbar MUST be available at the boiler inlet for Natural gas
and 37mbar for Propane.
Do not use pipes of smaller size than the burner inlet gas
connection.
The complete installation MUST be tested for gas soundness
and purged in accordance with the appropriate standards listed
on page 4.
FLUE INSTALLATION
IMPORTANT
It is the responsibility of the installer to ensure, in practice, that
products of combustion discharging from the terminal cannot re-
enter the building or any other adjacent building through
ventilators, windows, doors, other sources of natural air
infiltration, or forced ventilation / air conditioning.
If this should occur the appliance MUST be turned OFF, labelled
as 'unsafe' and corrective action taken.
The flue must be installed in accordance with the appropriate
standards listed on page 4.
WATER CIRCULATION SYSTEM
The system pump MUST be connected to the boiler.
The boiler must NOT be used for direct hot water supply. The
hot water storage cylinder MUST be of the indirect type.
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating nor
are they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of
the useful heating surface, should be lagged to prevent heat
loss and any possible freezing - particularly where pipes run
through roof spaces and ventilated underfloor spaces.
The boiler must be vented.
Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler
and hot water storage vessel. They should be at least 1/2" BSP
nominal size and be in accordance with BS. 2879.
The central heating system should be in accordance with the
relevant standards listed on page 4.
Due to the compact nature of the boiler the heat stored within the
castings at the point of shutdown of the burner must be
dissipated in order to avoid overheating. In order to allow pump
operation after burner shutdown the boiler control box
incorporates a pump overrun facility. In order to make use of
this, the pump must be supplied from the terminals inside the
boiler. Note: for pumps requiring greater than 1.0amp current,
they must be connected via a relay.
WATER TREATMENT FOR HOT WATER AND
HEATING BOILERS
There is a basic need to treat the water contained in all heating
and indirect water systems, particularly open vented systems. It
is assumed, incorrectly, that because boilers are operating in
conjunction with what is apparently a closed circuit an open
vented system will not, under normal circumstances, allow
damage or loss of efficiency due to hardness salts and
corrosion once the initial charge of water has been heated up a
few times.
1mm of lime reduces the heat transfer from metal to water by
10%.
In practice the deposition of these salts is liable to cause noises
from the boiler body or even premature boiler failure. Corrosion
and the formation of black iron oxide sludge will ultimately result
in premature radiator failure.
Open vented systems are not completely sealed from the
atmosphere if proper venting and expansion of system water is
to be achieved. The same tank is used to fill the system with
water and it is through the cold feed pipe that system water
expands into the tank when the boiler passes heat into the
system.
Conversely, when the system cools, water previously expelled is
drawn back from the tank into the system together with a quantity
of dissolved oxygen.
Even if leakage from the heating and hot water system is
eliminated there will be evaporation losses from the surface of
the tank which, depending upon ambient temperature, may be
high enough to evaporate a large portion of the system water
capacity over a full heating season.
There will always be corrosion within a heating or hot water
system to a greater or lesser degree, irrespective of water
characteristics, unless the initial fill water from the mains is
treated. Even the water in closed systems will promote
corrosion unless treated. For the reason stated, Caradon Ideal
Limited strongly recommend that when necessary the systems
is thoroughly cleaned, prior to the use of stable inhibitor, which
does not require continual topping up to combat the effects of
hardness salts and corrosion on the heat exchangers of the
boiler and associated systems.
Caradon Ideal Limited advise contact directly with specialists on
water treatment such as:
Betz Dearborn Ltd
or
Fernox Manufacturing Co. Ltd.
Widnes,
Tandem House, Marlowe Way,
Cheshire,
Croydon, Surrey, CRO 4XS
Tel: 0151 424 5351
Tel: 0870 601 5000
ELECTRICAL SUPPLY
WARNING
This appliance must be earthed.
A 230V - 50Hz mains supply is required, fused at 5amps.
Wiring external to the appliance MUST be in accordance with the
current I.E.E. (BS7671) Wiring Regulations and any local
regulations which apply.
The point of connection to the mains should be readily
accessible and adjacent to the boiler.
LOCATION OF THE BOILER
The boiler must stand on a non-combustible floor (i.e. concrete
or brick) which must be flat, level and of a suitable load bearing
capacity to support the weight of the boiler (when filled with
water) and any ancillary equipment.
If the boiler is mounted on a plinth then the dimensions must
exceed the plan area of the boiler by at least 75mm on each side.
The boiler must not be fitted outside.
6
Buccaneer GTE -
Installation & Servicing
GENERAL
1
BOILER DIMENSIONS
B
C
D
E
F
GT 4
692
812
125
427
50
GT 5
819
939
125
554
50
GT 6
946
1066
153
681
99
buc5489
355
C
60
F
60
300
35
835
289
570
E
163
B
392
562
137
1
4
2
3
120
285
570
158
1 Heating supply R 1
1
/
4
2 Heating return R 1
1
/
4
3 Drain cock
(connection for pipe ø int. 14 mm)
4
4 x M8 on
110
Insulation Cutout
2
BOILER CLEARANCES
The minimum dimensions indicated on
the following drawing must be respected
to ensure good access around the
boiler.
Note.
To allow the inlet of the combustion air,
the boiler room must be adequately
ventilated, the section and the location of
which must comply with local
recommendations.
0.5
m
A
1m
0.5
m
0.5
m
570
835
Boiler A
(mm)
GTE 4
692
GTE 5
819
GTE 6
946
buc5490
7
Buccaneer GTE -
Installation & Servicing
GENERAL
3
VENTILATION
The ventilation requirements in the gas fired boiler standard
are also valid for oil fired boilers of the same heat input.
The ventilation requirements of these boilers is dependant on
the type of flue system used, and their heat input. All vents
must be permanent with no means of closing, and positioned
to avoid accidental obstruction by blocking or flooding.
Detail reference should be made to BS 5440 Pt. 2. The
following notes are for general guidance only:
If installed in a room or internal space then a permanent air
vent is required. The sizes for vents directly communicating
with outside air shall have a free area of 5cm
2
per kW of boiler
rated input in excess of 7kW.
If installed in a compartment, then permanent air vents are
required at high and low level. These vents may
communicate direct to outside air, or to a room/internal space.
If to room/internal space, it must itself be adequately
ventilated as above.
4
HYDRAULIC CONNECTION
buc5492
355
562
137
Flow
Connection 1
1
/
4
"
Return
Connection 1
1
/
4
"
Drain Cock
120
158
Note.
Remember that boilers installed in or close to rooms in which
the atmosphere is polluted with chlorine or fluorine compounds
may be subject to high corrosion.
For example: hairdressing salons, industrial premises
(solvents), cooling equipment etc.
Boiler installed in such locations shall not be covered by the
warranty.
Minimum vent free area
(cm
2
) per kW of boiler
rated input positioned at:
Open-flued
To room or
internal space
Direct to
outside air
High Level
Low Level
10
20
5
10
FILLING THE SYSTEM
Filling shall be performed with a low flow rate from a low point
in the boiler room in order to ensure that all the air in the boiler
is bled from the high point of the system.
Always stop the pump before filling.
IMPORTANT. Instructions for starting up the boiler for the first
time after the system is fully or partly drained:
If all the air is not bled naturally to an expansion vessel which
opens out onto the air, the system must include manual
bleeder valves, in addition to automatic bleeder valves with the
capability to bleed the system by themselves when it is
operating. The manual bleeder valves are used to bleed all
the high points of the system and to make sure that the filled
system is free of air before the burner is turned on.
General
Recommendations relating to the water system are contained
in BS. 5449 and BS. 6880.
8
Buccaneer GTE -
Installation & Servicing
GENERAL
6
SEALED SYSTEM REQUIREMENTS
5
OPEN VENTED SYSTEM REQUIREMENTS
Detail reference should be made to the appropriate
standards listed on page 4.
The information and guidance given below is not intended to
override any requirements of the above publications or the
requirements of the local authority, gas or water undertakings.
The vertical distance between the pump and feed/expansion
cistern MUST comply with the pump manufacturer's minimum
requirements, to avoid cavitation. Should these conditions
not apply either lower the pump position or raise the cistern
above the minimum requirement specified by Caradon Ideal
Limited. The isolation valves should be fitted as close to the
pump as possible.
The boiler is fitted with an automatic air vent, located in the left
top side of the interior. This air vent must never be shut off, as
this could result in dry firing of the boiler and subsequent
damage to the heat exchanger.
ima5352
Hose unions
Temporary hose
(disconnect after filling)
Additional
stop valve
Double check valve
assembly
(note direction of flow)
Note. The method of filling, refilling, topping up or flushing
sealed primary hot water circuit from the mains via a temporary
hose connection is only allowed if acceptable to the local water
authority.
1. General
a. Detail reference should be made to the appropriate
standards listed on page 4. The information and
guidance given below is not intended to override any
requirements of these publications or the requirements
of the local authority, gas or water undertakings.
b. The installation should be capable of working with flow
temperatures of up to 90
o
C and a temperature
differential of up to 20
o
C.
c. All components of the system, including the heat
exchanger of the indirect cylinder, must be suitable for a
working pressure of 4 bar (60lbf/in
2
) and temperature of
110
o
C. Care should be taken in making all connections
so that the risk of leakage is minimised.
d. The boiler is fitted with an automatic air vent, located in
the left top side of the interior. This air vent must
never be shut off, as this could result in dry firing
of the boiler and subsequent damage to the
heat exchanger.
2. Safety Valve
A spring loaded safety valve
complying with the relevant
requirements of BS. 6759 Pt. 1
must be fitted in the flow pipe
as close to the boiler as
possible and with no
intervening valve or restriction.
The valve should have the
following features:
a. A non-adjustable preset lift pressure not exceeding 4bar
(60lbf/in
2
).
b. A manual testing device.
c. Provision for connection of a discharge pipe. The valve
or discharge pipe should be positioned so that the
discharge of water or steam is visible, but will not cause
hazard to user or plant.
3. Pressure Gauge
A pressure gauge covering at least the range 0-4bar must
be fitted to the system. The gauge should be easily seen
from the filling point and should preferably be connected at
the same point as the expansion vessel.
4. Expansion Vessel
Expansion vessels used must comply with BS. 4814.
Connection to the system must not incorporate an isolating
valve.
Feed/expansion
cistern
500mm
minimum
1500mm
minimum
System
flow to
pump
Inverted cold
feed entry
Cold
Feed
Water
level
(cold)
Open vent
System
return
Connections
to boiler
buc7949
1500
minimum
9
Buccaneer GTE -
Installation & Servicing
INSTALLATION
7
FLUING
According to the output, the difference between the
temperature of the flue gas and the ambient temperature can
be as low as 160
o
C. The installer will have to respect all of the
usual precautions (dilution - piping - T for removal of
condensation) in order to prevent deterioration of the chimney.
30-45
500 minimum
buc5495
Boiler
FLUE SIZE
Refer to applicable regulations while determining the size
and height of the flue. Please note that GTE boilers have
pressurised and sealed combination chambers and that the
pressure at the outlet must not exceed 0 mbar.
Detailed recommendations relating to the design of flues for
GAS fired appliances are quoted in BS. 6644 and British Gas
Publication No. IM11, whilst BS. 5410 Pt. 1 similarly applies to
OIL fired boilers.
Boiler
Power
Required
Draught
Mass Flow of Flue Gases
kg/s
Natural Gas
9% CO
2
Flue Gas
Temperature
(1) (2)
Chimney:
Minimum Recommended
Dimensions
kW
mbar
o
C
Ø min
m m
Height
m
GTE 4
21-27
0.12
0.014
0.014
< 180
125
6.5
GTE 5
27-33
0.12
0.017
0.017
< 190
125
7
GTE 6
33-39
0.11
0.020
0.020
< 190
153
7
(1) : at boiler high power
(2) : Boiler temperature: 80
o
C (ambient temperature : 20
o
C)
Fuel Oil
12% CO
2
The table below contains the minimum dimensions of the flue
required for each boiler model in order to ensure sufficient
draught at the outlet.
However, care must be taken to comply with any applicable
national or local regulations.
285
392
F
Flue outlet
Boiler Dimension
F
GTE 4
50
GTE 5
50
GTE 6
99
buc5493
8
DIMENSIONAL INFORMATION REQUIRED FOR THE FLUE CONNECTION
Connection
The connection must be made in a competent manner with
airtight pipe in a material that is resistant to hot gases from the
combustion and possible acid condensation. This pipe must
be as short as possible, be removable and without any
sudden change in its section.
The diameter must always be at least equal to that of the boiler
outlet.
FLUE OUTLET
10
Buccaneer GTE -
Installation & Servicing
INSTALLATION
9
BURNER CONNECTION
Gas Supply
The gas supply MUST be sized in accordance with British Gas
recommendations.
The Local Gas Authority should be contacted, at a stage prior
to actual installation, for any advice or information required.
Details and advice, relating to the use of L.P.G. for firing the
BUCCANEER GTE range of heating boilers, are available on
request to Caradon Ideal Limited.
Oil Storage Tank
The oil storage tank, oil supply pipe and connections to the
burner unit MUST comply with the requirements of BS. 799.
The installation should conform to the recognised standards of
good practice in the trade and comply with the relevant Codes of
Practice, building Regulations and Local Authority, Fire and
Insurance requirements.
Piercing Ø of the burner door
300
104
> 0
10
deflector
buc5494
IMPORTANT. The burner head deflector must go past the door
insulation as shown opposite.
Connection, adjustment, start-up and maintenance. (Refer to
the instructions delivered with the burner)
INST
ALLA
TION
11
Buccaneer GTE -
Installation & Servicing
INSTALLATION
10 PACKAGING
The following table shows the box numbers included with the boiler to be installed.
The assembly of any options delivered with the boiler is described in the instructions accompanying the options.
A DHW Sensor Kit (AD 212) is available for use with the Buccaneer GTE range.
11 BOILER BODY PREPARATION
Put a protective piece of cardboard on the floor in front of the boiler body. Take the body off the pallet and put it down vertically on
the burner door.
Boiler
GTE 4
GTE 5
GTE 6
Boiler
FM 2
body
FM 3
FM 4
Jacket
+
FM 11
insulation
FM 12
FM 13
Control panel
FM 126
FM 126
FM 126
buc7937
buc5
497
INST
ALLA
TION
12
Buccaneer GTE -
Installation & Servicing
INSTALLATION
12 INSTALLING THE BASE AND DRAIN COCK
2
3
1
4
buc5498
1. Unscrew the
1
/
2
" plastic plug on the
rear section.
2. Attach the base onto the feet of the
boiler.
3. Clip the base onto the rear section.
4. Screw in the drain cock supplied in
the screw bag making the joint
water tight using hemp or sealing
paste.
5. Put the boiler body back on
its feet.
13 REVERSE THE DIRECTION OF OPENING OF THE BURNER DOOR IF
NECESSARY (OPENING AT LEFT)
1
2
1
2
buc5500
When the burner leaves the factory, the burner door
opens towards the right. Perform operations in
Frames 13 and Frame 14 to open the burner door
towards the left (if absolutely necessary).
1. Loosen the 2 top and bottom nuts.
2. Remove the lower and upper hinges.
INST
ALLA
TION
13
Buccaneer GTE -
Installation & Servicing
INSTALLATION
1
notch in front
buc5503
14 REVERSE THE DIRECTION OF OPENING OF THE BURNER DOOR CONT'D
2
1
2
3
buc5501
1. Remove the 2 screws securing the hinge.
2. Remove the cast iron hinge pin for the burner
door and replace the screws back on the right-
hand side.
3. Remove the 2 screws on the left-hand side..
4. Reinstall the cast iron hinge pin (2) for the
burner door on the left side.
15 INSTALLING THE INSULATING MATERIAL
1. Pass the strap between the cast iron body and
the base.
2. Install the insulation around the body, folding
the bottom on each side of the boiler inside the
base.
5. Re-install the hinge pins on the left side, fixing
them by tightening the two nuts on the burner door
hinge pins on the left side.
5
5
buc5502
Nuts
INST
ALLA
TION
14
Buccaneer GTE -
Installation & Servicing
INSTALLATION
16 SECURING THE INSULATION
3
2
1
buc5504
1. Secure the insulation using the strap(s)
(1), and the attachment buckle (2).
2. Put the back insulation into place and fix
it onto the previously installed insulation
using the fasteners (3) by folding.
17 INSTALLING THE CONTROL PANEL SUPPORT CROSS BAR
Put the support cross bar into
place on the boiler body,
positioning it on:
1. The M8 studs at the front.
2. The assembly rod.
3. The rear section positioning
pin.
4. Fix it at the front with two M8
flanged nuts.
5. Fix the rear section with one
M8 x 30 screw and flanged
nut on one side and one
flanged nut on the
assembly rod at the other
side.
Put the rear cross bar into place on
the lugs of the rear section facing
the outside of the boiler positioning
it on:
1. The assembly Rod.
2. The rear section positioning pin.
3. Fix the rear section with one M8
x 30 screw and flanged nut on
one side and one flanged nut on
the assembly rod at the other
side.
1
4
5
3
2
1
4
buc5528
F l a n g e d
N u t
3
1
2
buc5529
F l a n g e d
N u t
18 ASSEMBLING THE REAR CROSS BAR
INST
ALLA
TION
15
Buccaneer GTE -
Installation & Servicing
INSTALLATION
buc7938
1
2
19 INSTALLING THE CONTROL PANEL
1. Lift the window.
2. Slide the control panel into the opening.
20 FIXING THE CONTROL PANEL
1. Fix the back of the control panel on the
top of the boiler using the 3.9 x 12 self
tapping screw and plain washer.
2. Lift the control panel display forwards.
3. Fix the lower front part of the control panel
on the cross bar using two M3 x 16
screws and square nuts.
4. Replace the control panel display.
5. Fix the top part of the control panel using
the black screw for plastic supplied for
this purpose.
6. Fit the earth wire spade connector to the
earth tab.
21 ROUTING THE BURNER CABLE
1. Put the burner cable in the
grommet, (supplied in the
control panel instructi